vacon • 76
Technical information
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Control
connections
Analogue input voltage
0…+10 V, R
i
= 200 kΩ.
Resolution 0.1%, accuracy ±1%
Analogue input current
0(4)…20 mA, R
i
= 250 Ω differential
Digital inputs (6)
Positive or negative logic; 18-30 V DC
Auxiliary voltage
+24 V, ±15%, max. 250 mA
Output reference v10 V, +3%, max. load 10 mA
Analogue output (1)
0(4)…20 mA; R
L
max. 500 Ω; Resolution 10 bit;
Accuracy ±2%
Digital outputs
Open collector output, 50 mA / 48 V
Relay outputs
2 programmable change over relay outputs
Switching capacity: 24 V DC / 8 A, 250 V AC / 8 A,
125 V DC / 0.4 A.
Min. switching load: 5 V / 10 mA.
Protection
Overvoltage protection
Undervoltage protection
NXA_5: 911 V DC; NXA_6: 1200 V DC
NXA_5: 333 V DC; NXA_6: 460 V DC
Ground fault protection
In case of an ground fault in the supply cable, the
ground fault protection only protects the NX AFE
itself.
Input phase monitoring
Trips if any of the input phases is missing.
Over current protection
Yes
Unit over temperature
protection
Yes
Short circuit protection of
+24 V and +10 V reference
voltages
Yes
Table 17. Technical specifications for active front-end (AFE) drives