Service
vacon • 65
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
4
Release the input busbar assembly. Remove:
1. six M10 nuts and M10x30 bolts (torque 40 Nm) from the upper busbars,
2. six M12 nuts and M12x40 bolts (torque 70 Nm) from the lower busbars,
3. two M8x20 screws (torque 20 Nm) from the back plate.
Take out the busbar assemblies, including the fuses.
Figure 46. Releasing the input busbar assembly
5
Release the output busbars. Remove three M12 nuts/bolts (tightening torque 70 Nm).
Figure 47. Output busbar mounting screws
13940_00
1
3
1
1
2
2
2
3
13941_00