cabling and connections
vacon • 41
24-hour support: +358-(0)40-
8371 150 • Email: [email protected]
6
6.1.1
Power connections
6.1.1.1
DC supply and motor cables
The power supply is connected to terminals B+ and B- and the motor cables to terminals U/T1, V/T2
and W/T3. A cable entry gland should be used at the motor cable end to reach the EMC levels, see
Table 6-1.
Use cables with a heat resistance of at least +70C. The cables and the fuses must be sized according
to the inverter nominal output current which can be found on the rating plate. Installation of cables
according to UL regulations is presented in Chapter 6.1.3 and aR fuse sizes in Tables 6-2 and 6-3.
If the motor temperature protection of the drive (see Vacon All in One Application Manual) is used as
an overload protection, the cable shall be chosen accordingly.
These instructions apply only to installations with one motor and one cable connection from the
inverter to the motor. In any other case, ask the factory for more information.
Cable type
EMC Level T
Power supply
Flexible conductor. Min. temperature endurance for isolation 70°C
Copper Busbar
Motor cable
Power cable equipped with concentric protection wire and intended
for the specific mains voltage. (PIRELLI/MCMK or similar
recommended).
Control cable
Screened cable equipped with compact low-impedance shield
(PIRELLI/jamak, SAB/ÖZCuY-O or similar).
Table 6-1. Cable types required to meet standards
6.1.1.2
Control cable
For information on control cables, see Chapter 6.2.1.1 and Table 6-1 above.
6.1.1.3
Fuses, NXI_xxxx 5
Type
Frame
I
L
[A]
Bussman aR
fuse type
Fuse
size
Fuse
U
n
[V]
Fuse
I
n
[A]
No. of fuses
NXI_0168 5
FI9
168
170M3819
DIN1
690
400
2
NXI_0205 5
205
170M3819
DIN1
690
400
2
NXI_0261 5
261
170M6812
DIN3
690
800
2
NXI_0300 5
300
170M6812
DIN3
690
800
2
NXI_0385 5
FI10
385
170M8547
3SHT
690
1250
2
NXI_0460 5
460
170M8547
3SHT
690
1250
2
NXI_0520 5
520
170M8547
3SHT
690
1250
2
NXI_0590 5
FI12
590
170M8547
3SHT
690
1250
2 × 2
NXI_0650 5
650
170M8547
3SHT
690
1250
2 × 2
NXI_0730 5
730
170M8547
3SHT
690
1250
2 × 2
NXI_0820 5
820
170M8547
3SHT
690
1250
2 × 2
NXI_0920 5
920
170M8547
3SHT
690
1250
2 × 2
NXI_1030 5
1030
170M8547
3SHT
690
1250
2 × 2
NXI_1150 5
FI13
1150
170M8547
3SHT
690
1250
6