technical data
vacon • 19
24-hour support: +358-(0)40-
8371 150 • Email: [email protected]
4
4.3
Technical information
Supply
connection
Input voltage U
in
465...800Vdc ( 380-500 Vac)
640...1100Vdc ( 525-690 Vac)
The waviness of the inverter supply voltage, which
is formed in rectification of the electric network's
alternating voltage in basic frequency, must be less
than 50V peak-to-peak.
Input current I
in
(sqrt3 × U
mot
× I
mot
× cos
ϕ
) / ( U
in
× 0,98)
DC bank capacitance
FI9_5 : 4950
µ
F; FI9_6 : 3733
µ
F
FI10_5: 9900
µ
F; FI10_6: 7467
µ
F
FI12_5: 19800
µ
F; FI12_6: 14933
µ
F
FI13_5: 29700
µ
F; FI13_6: 22400
µ
F
Starting delay
5 s (FI9 and greater)
Motor
connection
Output voltage
3 ~ 0 – U
in
/ 1,4
Continuous output
current
I
H
: A
mbient temperature max. +40°C,
overload 1.5 × I
H
(1 min./10 min.)
I
L
: Ambient temperature max.
+40°C,
overload 1.1 × I
L
(1 min./10 min.)
Starting torque
I
S
for two seconds, torque motor dependent
Peak current
I
S
for 2 s every 20 s
Output frequency
0…320 Hz ; 7200 Hz (Special)
Frequency resolution
Application dependent
Control
characteristics
Control method
Frequency control U/f
Open Loop Sensorless Vector Control
Closed Loop Frequency Control
Closed Loop Vector Control
Switching frequency
(see parameter 2.6.9)
NXI_5:
NXI_6:
1…10 kHz; Factory default 3.6 kHz
1…6 kHz; Factory default 1.5 kHz
Frequency reference
Analogue input
Panel reference
Resolution 0.1% (10-bit), accuracy ±1%
Resolution 0.01 Hz
Field weakening point
30…320 Hz
Acceleration time
0…3000 sec
Deceleration time
0…3000 sec
Braking torque
DC brake: 30% * T
N
(without brake)
Ambient
conditions
Ambient operating
temperature
–
10°C (no frost)…+40°C
Storage temperature
–
40°C…+70°C
Relative humidity
0 to 95% RH, non-condensing, non-corrosive,
no dripping water
Air quality:
-
chemical vapours
-
mechanical
particles
IEC 721-3-3, unit in operation, class 3C2
IEC 721-3-3, unit in operation, class 3S2
Altitude
100% load capacity (no derating) up to 1,000 m
1-% derating for each 100m above 1000.; max.
2000m
(Continues on next page)
Summary of Contents for NXI
Page 1: ...vacon nxi inverters fi9 fi14 user manual ...
Page 104: ......