AFE-operation mode
o Power control possible trough DC voltage reference. Needs controller if customer input
is power reference (instead of DC voltage reference).
o Cannot make or maintain grid by itself, needs existing grid
•
Island-operation mode
o Power control not possible, drive will give to the grid what the grid needs.
o Cannot operate parallel with other power sources.
o Makes a grid but cannot synchronize to the existing one.
When doing maintenance charging with the aim of a 100% full battery, charging must be done with
DC reference (possibly with a charging current limit).