BASIC VARIANTS
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 285
5.
BASIC VARIANTS
5.1
Direct to DC
Figure 18. Direct to DC
230 V Unit 500 V Unit 690 V Unit
Vac
Supply voltage max
240
500
690
Vac
Supply voltage min
208
380
Vac
Over voltage instantly
437
911
1200
Vdc
Over voltage U2t trip
-
-
1100
Vdc
DC high ready (Stop)
382
797
1099
Vdc
Normal Max
324
675
931
Vdc
Normal Min
280
513
708
Vdc
DC low run (Def.estim.)
242
475
656
Vdc
DC low ready (Stop)
239
436
602
Vdc
DC low running min
225
410
567
Vdc
Under voltage instantly
183
333
461
Vdc
#
Reference
#
Reference
A
Maximum tolerable U
DC
voltage for AFE
operation
B
Minimum tolerable U
DC
voltage for AFE to
stay in grid with cos
ᵩ
=1
A
B
Filter
Filter
voltage
drop
Transformer
voltage ratio
and drop
0
20
40
60
80
100
1C
2C
3C
6C
9C
u
INU
u
AFE
AFE DC
Grid converter
INU AC
AFE AC
SOC/%
Rectifying
DC/AC and
AFE control
marginal
u
GRID
Grid AC
+ Tolerance
1 pu
- Tolerance
Grid nominal
value and
voltage
tolerances