Commissioning
vacon •
23
24-hour s358 (0)40 837 1150 • Email: [email protected]
1
4.
COMMISSIONING
The Vacon Ethernet board is commissioned with the control keypad by giving values to appropriate
parameters in menu M7 (or with NCIPConfig tool, read chapter IP Tool NCIPConfig). Keypad com-
missioning is only possible with NXS and NXP series AC drives. AC drives of the NXL series can only
be commissioned with the NCIPConfig tool.
4.1.
Expander board menu (M7)
The
Expander board menu
makes it possible for the user to see which expander boards are con-
nected to the control board and to reach and edit the parameters associated with the expander
board.
Enter the following menu level (G#) with the
Menu button right
. At this level, you can browse trough
slots A to E with the
Browser buttons
to see what expander boards are connected. On the lowermost
line of the display you see the number of parameter groups associated with the board. If you still
press the
Menu button right
once you will reach the parameter group level where there are one
group in the Ethernet board case: Parameters. A further press on the
Menu button right
takes you to
Parameter group.
4.2.
Profinet parameters
#
Name
Default Range
Description
1
Comm. Timeout 10
0…255 s
2
IP Part 1
192
1…223
IP Address Part 1
3
IP Part 2
168
0…255
IP Address Part 2
4
IP Part 3
0
0…255
IP Address Part 3
5
IP Part 4
10
0…255
IP Address Part 4
6
SubNet Part 1
255
0…255
Subnet Mask Part 1
7
SubNet Part 2
255
0…255
Subnet Mask Part 2
8
SubNet Part 3
0
0…255
Subnet Mask Part 3
9
SubNet Part 4
0
0…255
Subnet Mask Part 4
10
DefGW Part 1
192
0…255
Default Gateway Part 1
11
DefGW Part 2
168
0…255
Default Gateway Part 2
12
DefGW Part 3
0
0…255
Default Gateway Part 3
13
DefGW Part 4
1
0…255
Default Gateway Part 4
14 InputAssembly
-
-
NOT USED in Profinet
15 OutputAssembly -
-
NOT USED in Profinet
Table 2. Ethernet parameters
4.3.
IP Address
IP is divided into 4 parts. (Part = Octet) Default IP Address is 192.168.0.10.
Communication timeout
Defines how much time can pass from the last received message from the Master Device before
fieldbus fault is generated. Communication timeout is disabled when given the value 0. The commu-
nication timeout value can be changed from the keypad or with NCIPConfig tool (see chapter IP Tool