6
vacon • 42
Communications
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
6.5
Example messages
6.5.1
Example 1 - Write Process Data
Write the process data 42001…42003 with command 16 (Preset Multiple Registers).
Command Master - Slave:
Message frame:
The reply to Preset Multiple Registers message is the echo of 6 first bytes.
Answer Slave - Master:
Table 36.
ADDRESS
01 hex Slave address 1 hex (= 1)
FUNCTION
10 hex
Function 10 hex (= 16)
DATA
Starting address HI 07 hex
Starting address 07D0 hex (= 2000)
Starting address LO D0 hex
No. of registers HI
00 hex
Number of registers 0003 hex (= 3)
No. of registers LO
03 hex
Byte count
06 hex
Byte count 06 hex (= 6)
Data HI
00 hex
Data 1 = 0001 hex (= 1). Setting control word run bit to 1.
Data LO
01 hex
Data HI
00 hex
Data 2 = 0000 hex (= 0).
Data LO
00 hex
Data HI
13 hex
Data 3 = 1388 hex (= 5000), Speed Reference to 50.00%
Data LO
88 hex
ERROR
CHECK
CRC HI
C8 hex
CRC field C8CB hex (= 51403)
CRC LO
CB hex
Table 37.
01 10 07 D0 00 03
06 00 01
00 00 13
88 C8 CB
Table 38.
ADDRESS
01 hex
Slave address 1 hex (= 1)
FUNCTION
10 hex
Function 10 hex (= 16)
DATA
Starting address HI 07 hex
Starting address 07D0 hex (= 2000)
Starting address LO D0 hex
No. of registers HI
00 hex
Number of registers 0003 hex (= 3)
No. of registers LO
03 hex
ERROR
CHECK
CRC HI
80 hex
CRC 8085 hex (= 32901)
CRC LO
85 hex
Summary of Contents for 100 INDUSTRIAL
Page 2: ......