Following these instructions, you can easily and fast set up your Modbus for use:
1
Choose control place.
A. Press LOC/REM button on keypad to select
Remote Control Place
B.
Select
Fieldbus
as remote control place:
Main Menu
>
Quick Setup (M1)
>
Rem. Ctrl. Place (P1.15) > FieldbusCTRL
2
Make these settings in the master software
A. Set Control Word to '0' by writing the data 0000h to the register 2001
d
.
B. Set Control Word to '1' by writing the data 0001h to the register 2001
d
.
C. AC drive status is RUN
D. Set Speed Reference value to '5000' (=50.00%) by writing the data 1388h to the
register 2003
d
.
E.
Actual speed
is 5000 (25.00 Hz if MinFreq is 0.00 Hz and MaxFreq is 50.00 Hz)
F. Set Control Word to '0' by writing the data 0000h to the register 2001
d
.
G. AC drive status is STOP.
Summary of Contents for 100 INDUSTRIAL