![Vacon 10 PFC User Manual Download Page 77](http://html1.mh-extra.com/html/vacon/10-pfc/10-pfc_user-manual_4547274077.webp)
T
ECHNICAL
DATA
VACON
•
75
24-hour support (0)201 212 575 • Email: [email protected]
11
Ambient condi-
tions
Ambient operating
temperature
-10 °C (no frost)…+40 / 50°C (depends on the unit size):
rated loadability IN
Side by side installation for MI1-3 it is always 40°C; For
IP21/Nema1 option in MI1-3 the maximum temparture
is also 40 °C.
Storage temperature -40°C…+70°C
Relative humidity
0…95% RH, non-condensing, non-corrosive, no
dripping water
Air quality:
- chemical vapours
- mech. particles
IEC 721-3-3, unit in operation, class 3C2
IEC 721-3-3, unit in operation, class 3S2
Altitude
100% load capacity (no derating) up to 1000 m. 1%
derating for each 100 m above 1000 m; max. 2000 m
Vibration:
EN60068-2-6
3...150 Hz
Shift range 1(spike) mm at 3...15.8 Hz Max. range of
acceleration 1 G at 15.8...150 Hz
Shock
IEC 68-2-27
UPS Drop Test (for applicable UPS weights)
Storage and shipping: max 15 G, 11 ms (in package)
Enclosure class
IP20 / IP21 / Nema1 for MI1-3
Pollution degree
PD2
EMC
Immunity
Complies with EN50082-1, -2, EN61800-3
Emissions
230V: Complies with EMC category C2; (level H
Vacon); With an internal RFI filter
400V: Complies with EMC category C2; (level H
Vacon): With an internal RFI filter
Both: No EMC emission protection (Vacon level N):
Without RFI filter
Standards
For EMC: EN61800-3
For safety: UL508C, EN61800-5
Certificates
and manufac-
turer’s declara-
tions of
conformity
For safety: CB, CE, UL, cUL,
For EMC: CE, CB, c-tick
(see drive nameplate for more detailed information)
Table 11.1: Vacon 10 technical data