I
NSTALLATION
VACON
•
25
24-hour support (0)201 212 575 • Email: [email protected]
3
Frame
Type
Fuse
[A]
Mains
cable
Cu
[mm
2
]
Motor
cable
Cu
[mm
2
]
Terminal cable size (min/max)
Main
terminal
[mm
2
]
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
Relay
terminal
[mm
2
]
MI2
0001-0004
20
2*2.5+2.5 3*1.5+1.5
1.5-4
1.5-4
0.5-1.5
0.5-1.5
MI3
0005
32
2*6+6
3*1.5+1.5
1.5-4
1.5-4
0.5-1.5
0.5-1.5
Table 3.9: Cable and fuse sizes for Vacon 10, 115 V, 1~
Frame
Type
Fuse
[A]
Mains
cable
Cu
[mm
2
]
Motor
cable
Cu
[mm
2
]
Terminal cable size (min/max)
Main
terminal
[mm
2
]
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
Relay
terminal
[mm
2
]
MI1
0001-0003
10
2*1.5+1.5 3*1.5+1.5
1.5-4
1.5-4
0.5-1.5
0.5-1.5
MI2
0004-0007
20
2*2.5+2.5 3*1.5+1.5
1.5-4
1.5-4
0.5-1.5
0.5-1.5
MI3
0009
32
2*6+6
3*1.5+1.5
1.5-6
1.5-6
0.5-1.5
0.5-1.5
Table 3.10: Cable and fuse sizes for Vacon 10, 208 - 240 V, 1~
Frame
Type
Fuse
[A]
Mains
cable
Cu
[mm
2
]
Motor
cable
Cu
[mm
2
]
Terminal cable size (min/max)
Main
terminal
[mm
2
]
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
Relay
terminal
[mm
2
]
MI1
0001-0003
6
3*1.5+1.5 3*1.5+1.5
1.5-4
1.5-4
0.5-1.5
0.5-1.5
MI2
0004-0007
10
3*1.5+1.5 3*1.5+1.5
1.5-4
1.5-4
0.5-1.5
0.5-1.5
MI3
0011
20
3*2.5+2.5 3*2.5+2.5
1.5-6
1.5-6
0.5-1.5
0.5-1.5
Table 3.11: Cable and fuse sizes for Vacon 10, 208 - 240 V, 3~
Frame
Type
Fuse
[A]
Mains
cable
Cu
[mm
2
]
Motor
cable
Cu
[mm
2
]
Terminal cable size (min/max)
Main
terminal
[mm
2
]
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
Relay
terminal
[mm
2
]
MI1
0001-0003
6
3*1.5+1.5 3*1.5+1.5
1.5-4
1.5-4
0.5-1.5
0.5-1.5
MI2
0004-0006
10
3*1.5+1.5 3*1.5+1.5
1.5-4
1.5-4
0.5-1.5
0.5-1.5
MI3
0008-0012
20
3*2.5+2.5 3*2.5+2.5
1.5-6
1.5-6
0.5-1.5
0.5-1.5
Table 3.12: Cable and fuse sizes for Vacon 10, 380 - 480 V, 3~