V200 POSITIONER
6
Connection Back III.ep
s
2. INSTALLATION
2.1 Connections
S
– Supply air
V200P: max. 145 PSI / 1 MPa
V200E: 23 - 145 PSI / 0,15 -1 MPa
I
– Input, pressure signal
V200P: 3-15 PSI / 20-100 kPa
V200E: Plugged
I
E
– Input, current signal
V200E: 4-20 mA (Ri max 250 ohm)
V200P: Plugged
C+
- Actuator conn stroke
C-
- Actuator connection - stroke
OUT
- All air from the actuator, IP and posi-
tioner is vented through this port.
Standard equipped with a bug screen/silencer
Air connections for male 1/4” NPT or G 1/4”.
Gauge connections for male 1/8” NPT or G1/8”.
Cable entry for male 1/2” NPT or M20 cable fit-
tings.
G threads are indicated by an engraved G
on the air connection side of the positioner.
Gauge ports I, C+, C- and S are factory plugged.
Remove plugs and replace with gauges.
The IP connection must be plugged in
V200E.
The IE entrys should be plugged in
V200P