Error 3

When a Start command is given and the gate does not open and 
the display shows 

Err3

It means that the photocell test failed.

1.

  Be sure that no obstacle interrupted the photocell beam when 

the Start command was given.

2.

  Be sure that photocells, as enabled by their relevant menus, 

have been installed actually.

3.

  If you have photocells 2, be sure that Fot2 menu item is on 

CF.Ch

.

4.

  Be sure that photocells are powered and working; when you 

interrupt their beam, you should hear the relay tripping.

5.

  Ensure the photocells are connected correctly, as shown in the 

chapter 5.5

Error 4

When a Start command is given and the gate does not open (or 
does a partial opening) and the display shows 

Err4

It means that the end of stroke is damaged or that the wiring that 
connects the sensor to the control unit is broken.

•  Change the end of stroke sensor or the broken wiring. If the 

error persists send the control unit to V2 S.p.A. for repair.

•  If limit switches have not been connected, check that the 

FC.En 

function is set to no.

Error 5

Once given a start control, the gate does not open and the display 
shows 

Err5

It means that the test of the safety edges failed.
Check that the menu of the test of safety edges (

Co.tE

) have 

been set correctly.
Check that the safety edges enabled from the menu are installed.

Error 7

The display shows 

Err7

This indicates an error in the encoders’ operation.
There are three possible causes:

1.

  With the encoders connected, even if they are not enabled, for 

a few instants after movement of a gate panel. This means that 
the connection to the encoder for that gate panel is reversed. 
Exchange terminal K1 with K2, or K3 with K4

2.

  With the encoders enabled, once a START command is 

received: This means that the encoders have not been 
initialized. For the encoders to operate correctly, the  
self-learning procedure must be performed. 

3.

  With the encoders enabled and initialized, a few seconds after 

movement begins: This means that an encoder is NOT correctly 
operating. Encoder malfunction or broken connection.

PLEASE NOTE

: Check the connection is in line with the motor 

instructions

Error 8

When executing a self-learning function the control is refused and 
the display shows 

Err8

It means that the setting of the control unit is not compatible with 
the requested function. 
In order to carry out self-learning, the Start inputs must be 
enabled in standard mode (

Strt

 menu set to 

StAn

) and the 

ADI interface must be disabled (

i.Adi

 menu set to 

no

). 

To survey the currents of the motor it is also necessary that the 
length of the opening and closure are at least of 7,5 second. 

Error 9

When you are trying to change the control unit setups and the the 
display shows 

Err9

It means that programming was locked by means of the 
programming lock key CL1+ (code 161213).
To change the settings it is necessary to insert in the connector of 
the ADI interface the same key used to activate the programming 
lock, and unlock the device.

Error 10

When a start command is given, the gate does not open and the 
display shows the message 

Er 10

This means that the ADI module function test failed.

Summary of Contents for CITY2+

Page 1: ...TALE PER CANCELLI AD ANTA E SCORREVOLI DIGITAL CONTROL UNIT 24V FOR LEAF SWING AND SLIDING GATES ARMOIRE DE COMMANDE NUM RIQUE 24V POUR PORTAILS VANTAILS ET COULISSANTS CUADRO DE MANIOBRAS DIGITAL 24V...

Page 2: ......

Page 3: ...SHING LIGHT 5 9 LOCK 5 10 LIMIT SWITCH AND ENCODER 5 11 EXTERNAL AERIAL 5 12 PLUG IN RECEIVER 5 13 ADI INTERFACE 5 14 ELECTRIC CONNECTIONS 6 CONTROL PANEL 6 1 USE OF THE DOWN MENU AND UP KEYS FOR PROG...

Page 4: ...e plastic case has an IP55 insulation to connect flexible or rigid pipes use pipefittings having the same insulation level Installation requires mechanical and electrical skills therefore it shall be...

Page 5: ...can be used for a signal light or a 24 V flashing light Auxiliary relay with programmable logic for courtesy light flashing light or other use ENERGY SAVING FUNCTION 5 INSTALLATION Installation of co...

Page 6: ...d receiver output of photocells 2 between terminals L8 PHOTO2 and L11 COM of the control unit Use outputs having normally closed contact mWARNING if several couples of same kind photocells are mounted...

Page 7: ...mmediately The direction of the gate at next command of START or PEDESTRIAN START depends upon the parameter STOP it inverts or continues the motion If the input STOP is disabled the command makes the...

Page 8: ...and K5 COM Connect the close limit switch to motor 2 using terminals K4 FCC2 and K5 COM Installation of encoders Connect the negative feeds BLACK cable for both encoders to terminal K5 COM Connect the...

Page 9: ...al Devices Interface interface of the control unit CITY2 allows the connection to V2 optional modules Refer to V2 catalogue or to the technical sheets to see which optional modules with ADI interface...

Page 10: ...1 OPENING Z4 Motor 1 CLOSING Z5 Motor 2 OPENING Z6 Motor 2 CLOSING B1 B2 230VAC courtesy light or flashing light POW 24V power supply POW Power supply BAT pole of the optional battery pack code 161212...

Page 11: ...ENGLISH 31 F1 L N L N F1 MAINS MAINS CITY2 CITY2 L CITY2 CITY2 L CITY2 BC OVERLOAD DOWN MENU UP BAT POW POW BAT RECEIVER...

Page 12: ...as been caused by a safety device border or obstacle detector The central arrow shows that the gate is on pause If it blinks it means that the time countdown for the automatic closing has been activat...

Page 13: ...utomation work properly and if necessary modify the configuration of the desired parameters 8 LOADING OF DEFAULT PARAMETERS If necessary it is possible to restore all the parameters to their standard...

Page 14: ...anel is jammed A START command is given This position is memorized as the close point for gate panel 2 4 3 Gate panel 1 is closed until one of the conditions listed in point 4 2 occur this position is...

Page 15: ...you can alternate the display of thousands or units Area 2 is the reading of the number of cycles before the next request for service its value is rounded down to the hundreds Area 3 is the setup of...

Page 16: ...t NOTE By holding down the UP or DOWN keys configuration menu items will scroll fast until item FinE is viewed In this way you can quickly reach either the top or bottom of the list PARAMETER VALUE DE...

Page 17: ...e to be setup is t Ch1 NOTE To avoid that the door does not close completely we recommend to setup a longer time than t APP opening time t C2P Leaf 2 closing time during pedestrian cycle no 0 5 5 0 Du...

Page 18: ...slow down phase 50 0 70 The displayed value is the percentage of max motor power P bAt Maximum motor power during battery operation During battery operation the controller is powered with a lower vol...

Page 19: ...e last closing stretch t CvE Fast closing time after slowing down 0 0 0 0 3 0 If a slowing time other than 0 is set up it could be likely that the gate speed is not enough for the lock to fasten durin...

Page 20: ...s generally used no no Function deactivated The gate closes after the time set for the function Ch AU 0 5 20 0 The gate closes after the setup time PA tr Pause after transit Per rendere minimo il temp...

Page 21: ...nput STOP stops the gate pressing the command START the gate continues the motion invE The command STOP stops the gate at the next START the gate starts moving in the opposite direction Fot1 Photocell...

Page 22: ...led for optical safety edges rESi Test enabled for conductive rubber safety edges FC En End of Stroke Inputs no no End of stroke inputs are disabled L SW End of stroke equipped with a normally close s...

Page 23: ...ing on the control unit disconnect through the disconnecting switch on the power line and remove the power supply terminal 2 Be sure that there is no voltage break upstream the control unit 3 Check wh...

Page 24: ...nected even if they are not enabled for a few instants after movement of a gate panel This means that the connection to the encoder for that gate panel is reversed Exchange terminal K1 with K2 or K3 w...

Page 25: ...V2 S p A Corso Principi di Piemonte 65 67 12035 RACCONIGI CN ITALY Tel 39 0172 812411 Fax 39 0172 84050 info v2home com www v2home com...

Reviews: