9 - SELF-LEARNING OF WORKING 
TIMES

This menu allows the automatic learning of the times necessary to 
open and close the gate.
During this phase, the control unit memorizes also the forces 
necessary to open and close the gate: these values will be 
activated by using the obstacle sensor.
The encoder positions are also saved, if enabled.

m

 

CAUTION: Before continuing, make certain that the 

limit switch(es) and encoder(s) have been installed correctly. 
Limit switches and encoders, if installed, must be enabled 
using the specific menu.

m

 

CAUTION: If the limit switches, the obstacle sensor or 

the encoder have NOT been enabled, make sure that when 
the procedure is started the leaves are completely closed.

1.

  Press and hold down the MENU key until the 

-APP 

appears 

on the display

2.

  Release the MENU key: the display will show 

ESC

 (press the 

MENU key only if you want to leave this menu)

3.

  Press the DOWN key: 

t.LAv

 will appear on the display.

4.

  Press the MENU key to start the self-learning cycle for the work 

cycle times:

CAUTION

: This procedure varies based on the number of gate 

panels and travel control devices installed. 
If there is no limit switch or encoder installed, only points 4.4 and 
4.5 are performed. If there is only one motor (

t.AP2

 = 

0

), the 

procedure starts from point 4.3

4.1

  Gate panel 1 is opened for a few seconds

4.2

  Gate panel 2 is closed until one of the following conditions 

occurs:

    -  it reaches the limit switch

    -  The obstacle sensor or the encoder detect that the  

  gate panel is jammed

    -  A START command is given 

    This position is memorized as the close point for gate panel 

2.

4.3

  Gate panel 1 is closed until one of the conditions listed 

in point 4.2 occur: this position is memorized as the close 
point for gate panel 1.

4.4

  Each gate panel is opened. The operation ends when once 

of the conditions indicated in point 4.2 occur (the first 
START stops gate panel 1, the second START stops gate 
panel 2). The time required is memorized as the open time.

4.5

  Each gate panel is closed. The operation ends when one 

of the conditions indicated in point 4.2 occurs or when the 
closed position is reached. The time required is memorized 
as the close time.

5.

  The display shows the value recommended for the obstacle 

sensor of motor 1. If no operations are performed for 20 
seconds, the controller exits the programming phase without 
saving the recommended value.

6.

  The recommended value can be changed using the UP 

and DOWN keys. Press the MENU key to confirm the value 
displayed and the display will show 

SEn1

7.

  Press the DOWN key: The display will show 

SEn2

. Press the 

MENU key to display the recommended value for the obstacle 
sensor for motor 2, which can be changed in a similar manner 
as that for 

SEn1

.

8.

  Hold down the DOWN key until the 

FinE

 appears on the 

display, then press the MENU key, select 

Si

 and press the 

MENU key to exit programming and save the values for the 
sensors.

m

 

CAUTION: If the controller exits programming due 

to time out (1 minute), the obstacle sensors return to the 
values that were set prior to performing self-learning 
(according to the default values, the sensors are disabled).
The open/close times and the encoder positions are always 
saved.

Summary of Contents for CITY2+

Page 1: ...TALE PER CANCELLI AD ANTA E SCORREVOLI DIGITAL CONTROL UNIT 24V FOR LEAF SWING AND SLIDING GATES ARMOIRE DE COMMANDE NUM RIQUE 24V POUR PORTAILS VANTAILS ET COULISSANTS CUADRO DE MANIOBRAS DIGITAL 24V...

Page 2: ......

Page 3: ...SHING LIGHT 5 9 LOCK 5 10 LIMIT SWITCH AND ENCODER 5 11 EXTERNAL AERIAL 5 12 PLUG IN RECEIVER 5 13 ADI INTERFACE 5 14 ELECTRIC CONNECTIONS 6 CONTROL PANEL 6 1 USE OF THE DOWN MENU AND UP KEYS FOR PROG...

Page 4: ...e plastic case has an IP55 insulation to connect flexible or rigid pipes use pipefittings having the same insulation level Installation requires mechanical and electrical skills therefore it shall be...

Page 5: ...can be used for a signal light or a 24 V flashing light Auxiliary relay with programmable logic for courtesy light flashing light or other use ENERGY SAVING FUNCTION 5 INSTALLATION Installation of co...

Page 6: ...d receiver output of photocells 2 between terminals L8 PHOTO2 and L11 COM of the control unit Use outputs having normally closed contact mWARNING if several couples of same kind photocells are mounted...

Page 7: ...mmediately The direction of the gate at next command of START or PEDESTRIAN START depends upon the parameter STOP it inverts or continues the motion If the input STOP is disabled the command makes the...

Page 8: ...and K5 COM Connect the close limit switch to motor 2 using terminals K4 FCC2 and K5 COM Installation of encoders Connect the negative feeds BLACK cable for both encoders to terminal K5 COM Connect the...

Page 9: ...al Devices Interface interface of the control unit CITY2 allows the connection to V2 optional modules Refer to V2 catalogue or to the technical sheets to see which optional modules with ADI interface...

Page 10: ...1 OPENING Z4 Motor 1 CLOSING Z5 Motor 2 OPENING Z6 Motor 2 CLOSING B1 B2 230VAC courtesy light or flashing light POW 24V power supply POW Power supply BAT pole of the optional battery pack code 161212...

Page 11: ...ENGLISH 31 F1 L N L N F1 MAINS MAINS CITY2 CITY2 L CITY2 CITY2 L CITY2 BC OVERLOAD DOWN MENU UP BAT POW POW BAT RECEIVER...

Page 12: ...as been caused by a safety device border or obstacle detector The central arrow shows that the gate is on pause If it blinks it means that the time countdown for the automatic closing has been activat...

Page 13: ...utomation work properly and if necessary modify the configuration of the desired parameters 8 LOADING OF DEFAULT PARAMETERS If necessary it is possible to restore all the parameters to their standard...

Page 14: ...anel is jammed A START command is given This position is memorized as the close point for gate panel 2 4 3 Gate panel 1 is closed until one of the conditions listed in point 4 2 occur this position is...

Page 15: ...you can alternate the display of thousands or units Area 2 is the reading of the number of cycles before the next request for service its value is rounded down to the hundreds Area 3 is the setup of...

Page 16: ...t NOTE By holding down the UP or DOWN keys configuration menu items will scroll fast until item FinE is viewed In this way you can quickly reach either the top or bottom of the list PARAMETER VALUE DE...

Page 17: ...e to be setup is t Ch1 NOTE To avoid that the door does not close completely we recommend to setup a longer time than t APP opening time t C2P Leaf 2 closing time during pedestrian cycle no 0 5 5 0 Du...

Page 18: ...slow down phase 50 0 70 The displayed value is the percentage of max motor power P bAt Maximum motor power during battery operation During battery operation the controller is powered with a lower vol...

Page 19: ...e last closing stretch t CvE Fast closing time after slowing down 0 0 0 0 3 0 If a slowing time other than 0 is set up it could be likely that the gate speed is not enough for the lock to fasten durin...

Page 20: ...s generally used no no Function deactivated The gate closes after the time set for the function Ch AU 0 5 20 0 The gate closes after the setup time PA tr Pause after transit Per rendere minimo il temp...

Page 21: ...nput STOP stops the gate pressing the command START the gate continues the motion invE The command STOP stops the gate at the next START the gate starts moving in the opposite direction Fot1 Photocell...

Page 22: ...led for optical safety edges rESi Test enabled for conductive rubber safety edges FC En End of Stroke Inputs no no End of stroke inputs are disabled L SW End of stroke equipped with a normally close s...

Page 23: ...ing on the control unit disconnect through the disconnecting switch on the power line and remove the power supply terminal 2 Be sure that there is no voltage break upstream the control unit 3 Check wh...

Page 24: ...nected even if they are not enabled for a few instants after movement of a gate panel This means that the connection to the encoder for that gate panel is reversed Exchange terminal K1 with K2 or K3 w...

Page 25: ...V2 S p A Corso Principi di Piemonte 65 67 12035 RACCONIGI CN ITALY Tel 39 0172 812411 Fax 39 0172 84050 info v2home com www v2home com...

Reviews: