ENGLISH

- 12 -

DIP

FUNCTION

SETTING

DESCRIPTION

1

Pre-flashing,
backlash,
electric lock 
advance

ON

Enabled
functions

The flashing light lights up for 3 sec. before the motors are started in opening. 
After 1 second of pre-flash, the backlash is activated for 2 seconds. 
After 0.5 seconds of backlash the electric lock is activated

OFF

-

Preflashing disabled. Water hammer disabled.
0.3 seconds of electric lock advance

2

Automatic closure

ON

Enabled

The gate is closed automatically after the period of time set by the PAUSE 
trimmer

OFF

Disabled

On completion of the opening step, the gate remains open. It is necessary to 
instruct closure with another START command

3

Start during 
opening

ON

Not accepted

Any START command issued during opening is ignored

OFF

Accepted

Any START command issued during opening is accepted

4

Operational logic

ON

Inversion

Start during opening causes closure. 
Start during closure causes opening.

OFF

Step

Commands subsequent to starting cause, in order: 
open 

g

 stop 

g

 close 

g

 stop...

5

Slow down and 
final push

ON

Enabled

At the end of each opening and closing phase the motors slow down  
for 2 seconds. The final push lasts for 1 second

OFF

Disabled

6

Start off

ON

Disabled

At the start of each opening and closing step, the motors are started at 
maximum power 

OFF

Enabled

7

Anti-slip

ON

Disabled

The time used for opening or closure will always be the value set by the WORK 
trimmer, even if the previous operation has been interrupted before the expiry 
of such time.

OFF

Enabled

When an opening (or closing) operation is interrupted before expiry of the 
set time (for example due to the intervention of one of the safety devices or 
due to a start command), the duration of the subsequent closing (or opening) 
operation will not be that set by the WORK trimmer, but will be equal to the 
time effectively elapsed, plus a short supplemental time in order to compensate 
for the inertia of the gate.

8

Photocell

ON

Always active

Intervention of the photocell during opening or closing causes the gate to 
stop. When the photocell restores, the gate re-opens completely.

OFF

NOT active during 
opening

Intervention of the photocell during opening is ignored. Intervention of the 
photocell during closing causes the gate to re-open completely.

9

Photocell test

ON

Enabled

The control unit performs a photocell operational test before starting each 
opening or closing operation. If the photocells are not operating correctly, the 
gate does not begin to move and the light flashes for approx. 8 seconds.

PLEASE NOTE:  connect the photocell TX correctly

OFF

Disabled

10

Safety edge type

ON

Conductive rubber 
edge

Select this option if using conductive rubber edges with nominal resistance of 
8K2.

OFF

Standard or optical 
edge

Select this option if using standard edges with switch normally closed or 
optical edges.

11

Safety edge

ON

Always active

Intervention of the edge during opening or closing causes inversion of the 
direction of movement in order to free the body that caused the edge to 
intervene. The gate will be stopped after approx. 3 seconds.

OFF

NOT active during 
opening

Intervention of the edge during opening is ignored. Intervention of the edge 
during closing causes the gate to be re-opened completely.

12

Safety edge test

ON

Enabled

The control unit performs an operational test on the edges before starting 
each opening or closing operation. If the edges are not operating correctly, the 
gate does not begin to move and the light flashes for approx. 8 seconds. 

DO NOT enable testing if conductive rubber edges are used or standard 
edges are used without a suitable control unit for controlling function.

OFF

Disabled

PROGRAMMING THE OPERATIONAL LOGIC

It is possible for the control unit to use several different operational logic states, by simply moving the dip-switches located on the card.  
The functions associated with each individual dip-switch are listed below.

Summary of Contents for CITY11

Page 1: ...not come into contact with safety low voltage ones The plastic case has an IP55 insulation to connect flexible or rigid pipes use pipefittings having the same insulation level Installation requires m...

Page 2: ...an be used with two settings 1 Photocell always active Intervention of the photocell during opening or closing causes the gate to stop When the photocell restores the gate re opens completely 2 Photoc...

Page 3: ...closed In both modes it is possible to disable the Start command during gate opening by means of dip switch 3 Connect the start input control device cables between terminals L1 and L6 on the control...

Page 4: ...an opening command for a standard connection device with switch normally open L3 STOP command N C switch L4 Photocell N C switch L5 Edge Switch N C or resistive rubber edge L6 Commands common line L7...

Page 5: ...h the slow down function disabled DIP 5 OFF mWARNING the adjustment of times has to be made when the gate is still POWER MIN MAX WORK 50 18 2 2 45 PAUSE 150 30 2 2 90 DELAY 90 15 0 0 45 POWER motor po...

Page 6: ...upplemental time in order to compensate for the inertia of the gate 8 Photocell ON Always active Intervention of the photocell during opening or closing causes the gate to stop When the photocell rest...

Page 7: ...cas de d tachement d un conducteur on vite que les partie en tension puissent aller en contact avec les parties faible tension de s curit Pour la connexion de tubes rigides ou flexibles utiliser des...

Reviews: