COURTESY LIGHT

This output has a normally-open clean contact relay which closes 
for approx. 1 second at the start of an opening phase. 
This switch may be used to activate a courtesy light timer (max. 
load: 230V - 4 A).

PLEASE NOTE

: If there is no timer, the courtesy light can be 

controlled using channel 4 of receiver MR: bistable or timer 
programmable channel (read the instructions for the receiver MR 
thoroughly).

The switch is on terminals 

K1

 and 

K2

.

BLINKER

The control unit provides for the use of a 230V - 40W or  
120V - 40W blinker with built-in intermittence. 

Connect the cables to terminals 

K9

 and 

K10

.

ELECTRIC LOCK

A 12V electric lock can be mounted on the gate to ensure a good 
closure of the shutters.
The electric lock is activated for a fixed time of 1.5 seconds.
The lock advance time is adjustable from 0.2 to 0.5 seconds  
(dip-switch 1)

Connect the cables of the electric lock between terminals 

L10 

and 

L11

 of the control unit.

START INPUT

The START input is preset for connecting devices with the switch 
normally open. 
Function depends on the mode of operation set by means of dip-
switch 4.

Step mode

Subsequent Start command cause, in order: 
opening 

g

 stop 

g

 closure 

g

 stop 

“Inversion” mode

Start during opening causes closure.
Start during closure causes opening.
Start with the gate open always results in closure; the only case 
where this does not occur immediately is when automatic closure 
is enabled and start while opening is not accepted: in this specific 
case, start makes the pause time count start from zero, after 
which the gate will be re-closed. 

In both modes it is possible to disable the Start command during 
gate opening by means of 
dip-switch 3.

Connect the start input control device cables between terminals 

L1 

and 

L6

 on the control unit.

PEDESTRIAN START 

With the gate closed, the pedestrian start command causes partial 
opening (approx. half way) of the gate leaf connected to motor 1. 
Subsequent pedestrian start commands will function according to 
step logic.

During a pedestrian cycle, the start command results in the 
complete opening of both gate leaves.

Connect the pedestrian start input control device cables between 
terminals 

L2

 and 

L6

 on the control unit.

STOP

The STOP input is intended for devices with the switch normally 
closed. 
The STOP command causes the immediate stop of the gate. 
A subsequent START command activates the gate in the opposite 
direction of movement.
If the STOP command is given during opening or pause, then 
there will be no subsequent automatic re-closure.

Connect the stop input control device cables between terminals 

L3

 and 

L6

 on the control unit.

EXTERNAL ANTENNA

It is recommended the external antenna be used in order to 
guarantee maximum radio capacity.

Connect the antenna hot pole to terminal 

A1

 of the control unit 

and the braiding to terminal 

A2

PLUG-IN RECEIVER

The control unit is suitable for plugging-in an MR series receiver.

m

 

PLEASE NOTE: Pay the utmost attention to the 

direction of insertion of plug-in modules.

The MR receiver module has 4 channels, each with an associated 
command of the control unit:
•  CHANNEL 1 

g

 START

•  CHANNEL 2 

g

 PEDESTRIAN START

•  CHANNEL 3 

g

 STOP

•  CHANNEL 4 

g

 COURTESY LIGHTS

m

 

PLEASE NOTE: Read the instructions supplied with the 

MR receiver thoroughly for details on programming the 4 
channels and the operational logic

Summary of Contents for CITY11

Page 1: ...not come into contact with safety low voltage ones The plastic case has an IP55 insulation to connect flexible or rigid pipes use pipefittings having the same insulation level Installation requires m...

Page 2: ...an be used with two settings 1 Photocell always active Intervention of the photocell during opening or closing causes the gate to stop When the photocell restores the gate re opens completely 2 Photoc...

Page 3: ...closed In both modes it is possible to disable the Start command during gate opening by means of dip switch 3 Connect the start input control device cables between terminals L1 and L6 on the control...

Page 4: ...an opening command for a standard connection device with switch normally open L3 STOP command N C switch L4 Photocell N C switch L5 Edge Switch N C or resistive rubber edge L6 Commands common line L7...

Page 5: ...h the slow down function disabled DIP 5 OFF mWARNING the adjustment of times has to be made when the gate is still POWER MIN MAX WORK 50 18 2 2 45 PAUSE 150 30 2 2 90 DELAY 90 15 0 0 45 POWER motor po...

Page 6: ...upplemental time in order to compensate for the inertia of the gate 8 Photocell ON Always active Intervention of the photocell during opening or closing causes the gate to stop When the photocell rest...

Page 7: ...cas de d tachement d un conducteur on vite que les partie en tension puissent aller en contact avec les parties faible tension de s curit Pour la connexion de tubes rigides ou flexibles utiliser des...

Reviews: