Time menu setup

Time menus allow setting a function duration. When you enter
into a time menu, the current setup value will be viewed; the
display mode depends on the current value:

• times being lower than one minute will be viewed as follows: 

each time you press UP key, current time value increases of 
half a second; vice versa, each time you press the DOWN 
key, current time value decreases of half a second.

• Times between 1 and 10 minutes will be viewed as follows:

each time you press UP key, current time value increases of 5 
seconds; vice versa, each time you press the DOWN key, 
current time value decreases of 5 seconds.

• Times being more than 10 minutes will be viewed as follows:

each time you press UP key, current time value increases of 
half a minute; vice versa, each time you press the DOWN key, 
current time value decreases of half a minute.

By holding down the UP key, you can quickly increase the time
value, up to reach the max. value allowed for this item. Vice
versa, by holding down the DOWN key, you can quickly decrease
the time value down to reach 

0.0”

.

In some circumstances, setting the value to 0 means that the
relevant function is disabled, in this case, ‘

no

’ will appear instead

of 

0.0”

.

By pressing on MENU you will confirm the displayed value and
you will return to the configuration menu.

Value menu setup

Value menus are similar to time menus; however, the setup value
can be any number. 
By holding down UP or DOWN keys, the value will increase or
decrease slowly.

Please refer to the paragraph “Control unit configuration” for
the item position inside the menu, as well as for the available
options for each item.

1.

Call up a default configuration (item 

dEF.

). 

Select 

AntE

for a door-gate, select 

Scor

for other 

configurations (sliding, rolling, sectional, etc.).

2.

If you have a door gate with only one motor, set 

t.AP2

opening time to zero.

3.

In case there is no electric lock on the gate, set 

t.SEr

t.ASE

and 

t.CvE

values to zero.

4.

Set items 

StoP

Fot1

Fot2

CoS1

CoS2

FC.En

according 

to the safety devices installed on the gate.

5.

Start the self-learning cycle (item 

APPr

).

This last operation will close the configuration menu and store
set up parameters.

Self-learning procedure if there are two motors:

• In case the ends of stroke, the encoder or the obstacle 

sensor have been enabled, the doors will be activated in 
closing direction until the stop end or the closing end of 
stroke is reached. Be sure that the leaves do not overlap.

• In case NEITHER the ends of stroke NOR the obstacle 

sensor have been enabled, be sure that the doors are 
completely closed when the procedure starts.

• The doors will be activated in opening direction until the 

stop end or the opening end of stroke is reached.

• In case the sensors have not been enabled, or if you realize 

that they do not signal the position to the control unit, you 
must send a first START command when leaf 1 reaches its 
max. opening position and then a second START command 
when leaf 2 completes its opening phase.

• The doors will be activated in closing direction until the 

stop end or the closing end of stroke is reached 

• In case the sensors have not been enabled, or if you realize 

that they do not signal the position to the control unit, you 
must send a first START command when  leaf 1 reaches its 
fully closed position and then a second START command 
when leaf 2 completes its closing phase.

Self-learning procedure if there is one motor:

• In case the end of stroke, the encoder or the obstacle 

sensor has been enabled, the door will be activated in 
closing direction until the stop end or the closing end of 
stroke is reached.

• In case NEITHER the ends of stroke OR the obstacle sensor 

have been enabled, be sure that the door is completely 
closed when the procedure is started up.

• The door will be activated in opening direction until the 

stop end or the opening end of stroke is reached.

• In case the sensors have not been enabled, or if you realize 

that they do not signal the position to the control unit, you 
must send a START command when the door reaches its 
max. opening position.

• The door will be activated in closing direction until the stop 

end or the closing end of stroke is reached.

• In case the sensors have not been enabled, or if you realize 

that they do not signal the position to the control unit, you 
must send a START command must be sent when the door 
reaches its fully closed position.

QUICK CONFIGURATION

This paragraph concerns a quick procedure to set the control
unit and set it at work immediately. 

We recommend following these instructions, in order to check
quickly the correct operation of control unit, motor and
accessories, and then changing the configuration in case of
any non-satisfactory parameter. 

WARNING: The self-learning procedure must be
performed when the encoder (CITY1-ECD) is to be used.

Summary of Contents for CITY1

Page 1: ...IL n 170 1 EDIZ 04 03 2009 V2 S p A Corso Principi di Piemonte 65 67 12035 RACCONIGI CN ITALY tel 39 01 72 81 24 11 fax 39 01 72 84 050 info v2home com www v2home com CITY1 I...

Page 2: ...Y RIBBONS 28 LOCK 28 END OF STROKE 28 ENCODER 28 STOP 28 ACTIVATION INPUTS 29 EXTERNAL AERIAL 29 PLUG IN RECEIVER 29 OPTIONAL MODULES 29 CONTROL PANEL 30 USE OF DOWN MENU AND UP KEYS FOR PROGRAMMING 3...

Page 3: ...N 12453 allows We recommend to make use of an emergency button to be installed by the automation connected to the control unit STOP input so that the gate may be immediately stopped in case of danger...

Page 4: ...d in case of disabled obstacle sensor is described WARNING In case it has not yet fitted a start capacitor for each motor is required connect the start capacitor for motor 1 between terminals 27 and 2...

Page 5: ...good closing of doors Make use of a 12V lock Connect lock cables to terminals 20 and 21 of the control unit END OF STROKE CITY1 control unit supports the two following kinds of end of stroke end of s...

Page 6: ...f device controlling the first input between terminals 3 and 6 of the control unit Connect cables of device controlling the second input between terminals 4 and 6 of the control unit The first input f...

Page 7: ...nto its closing phase If it blinks it means that the closing has been caused by a safety device border or obstacle detector USE OF DOWN MENU AND UP KEYS FOR PROGRAMMING Control unit time and function...

Page 8: ...the doors will be activated in closing direction until the stop end or the closing end of stroke is reached Be sure that the leaves do not overlap In case NEITHER the ends of stroke NOR the obstacle s...

Page 9: ...ning phase before the relevant time expires WARNING if motor 2 is not connected this time must be set to zero in this circumstance the control unit will not consider all configurations of motor 2 and...

Page 10: ...mmand it will use this time to close the gate Max allowed time to be setup is t CH1 To avoid that the door does not close completely we recommend to setup a longer time than t APP opening time Leaf 2...

Page 11: ...motors to help the electric lock release The control unit controls the motors in reduced power in closing direction for the setup time The backlash precedes the electric lock release It is possible t...

Page 12: ...down function in order to measure both opening and closing times and to enable it again once the setup has been carried out The control unit will automatically consider the working time delay caused b...

Page 13: ...the step by step operation logic Select option APEr to set up the always open operation logic Start command during the pause This menu allows fixing the control unit conduct in case it receives a Sta...

Page 14: ...n is disabled by setting the value to zero no will be displayed the gate can be closed through the start command only in this case St PA menu setup will be ignored If the control unit receives a Stop...

Page 15: ...ns associated to the command of STOP no The input STOP is not available ProS The input STOP stops the gate pressing the command START the gate continues the motion invE The command STOP stops the gate...

Page 16: ...In some installations it may occur that the gate door passes before the photocells so breaking their beam In this case the gate cannot complete its closing cycle Through this function photocells can...

Page 17: ...eached its position of complete opening or closing no End of stroke inputs are disabled Si End of stroke inputs are enabled Motor Release on Mechanical Stop When the gate halts against the mechanical...

Page 18: ...exactly to the starting position it is possible to set an anti skid time that is added to the time calculated by the control unit in order to recover the inertia WARNING If function ASM is disabled t...

Page 19: ...d the learning cycle starts WARNING The procedure of the operation time automatic learning can be starter only if the Start inputs are set up on the STANDARD mode StAn End of Programming This menu all...

Page 20: ...cles after which the next service will be requested In case no new value is setup that is to say that the counter value is left at zero the signalling function for the service request will be disabled...

Page 21: ...0 no Pre flashing disabled it corresponds to 0 Pot1 30 100 Motor 1 power 60 60 Pot2 30 100 Motor 2 power 60 SPUn no Si Start off no Si t P So 0 5 3 0 Slowed down starting time 1 5 no no Slowed down s...

Page 22: ...no no no Function disabled F ShA FOTO2 disabling higher time i ShA FOTO2 disabling lower time CoS1 no Si Border 1 input fixed border no no CoS2 no Si Border 2 input mobile border no no FC En no Si En...

Page 23: ...ing phase N C contact 16 Common 17 18 Power output 24 VAC for photocells and other accessories 18 19 Photocell TX power supply for functional test 20 21 Electric lock 12VAC 22 23 Flashing light 230VAC...

Page 24: ...K 2 x 1 5 mm2 PG9 For cables with external from 5 to 8 mm OTHER WIRINGS MULTIPOLAR n x 0 25 0 5 mm2 n depending on the number of wirings to be made PG9 For cables with external from 5 to 8 mm PG11 For...

Page 25: ...sure that photocells are powered and working when you interrupt their beam you should hear the relay tripping Error 4 After few centimeters during the opening phase the gate stops and the display show...