CITY1 FUNCTION TABLE

DISPLAY DATA

DESCRIPTION

DEFAULT

SCor

DEFAULT

AntE

MEMO

DATA

dEF.

no

It does not load the V2 standard data

no

no

SCor

Predefined programming for a typical sliding gate. 

AntE

Predefined programming for a typical two-door gate 

t.AP1

0.0" ÷ 2.0'

Gate 1 opening time

22.5"

22.5"

t.AP2

0.0" ÷ 2.0'

Gate 2 opening time

0.0"

22.5"

t.APP

0.0" ÷ t.AP1

Opening time of pedestrian gate

6.0"

6.0"

t.Ch1

0.0" ÷ 2.0'

Gate 1 closing time

23.5"

23.5"

t.Ch2

0.0" ÷ 2.0'

Gate 2 closing time

0.0"

23.5"

t.ChP

0.0" ÷ t.Ch1

Closing time of pedestrian gate

7.0"

7.0"

t.C2P

0.5" ÷ 2.0'

Leaf 2 closing time during pedestrian cycle

no

2.0"

no

- Function disabled

r.AP

0.0"÷ 2.0'

Gate delay during opening

1.0"

1.0"

r.Ch

0.0" ÷ 2.0'

Gate delay during closing

3.0"

3.0"

t.SEr

0.5" ÷ 2.0'

Electrical lock operation time 

no

2.0"

no

- Lock is not energized (it corresponds to 0)

t.ASE

0.0" ÷ 2.0'

Lock advance time

0.0"

1.0"

t.inv

0.5" ÷ 3.0"

Backlash time

no

no

no

- Backlash disabled (it corresponds to 0)

t.PrE

0.5" ÷ 2.0'

Pre-flashing time

1.0"

1.0"

no

- Pre-flashing disabled (it corresponds to 0)

Pot1

30 ÷ 100%

Motor 1 power

60

60

Pot2

30 ÷ 100%

Motor 2 power

-

60

SPUn

no/Si

Start off

no

Si

t.P.So

0.5" ÷ 3.0"

Slowed down starting time

1.5"

no

no

- Slowed down starting disabled

t.raL

0.5"÷22.5"

Slow down time

2.0"

2.0"

no

- Slow down disabled

t.CVE

0.0" ÷ 3.0"

Fast closing time after slowing down during closing

0.0"

1.0"

St.AP

Start in opening

PAUS

PAUS

no

- Start command is not available

ChiU

- Command close gate

PAUS

- Stop the gate and goes in pause

St.Ch

Start in closing

StoP

StoP

Stop

- Start command stop the gate

APEr

- Start command open the gate

St.PA

Start in pause

ChiU

ChiU

no

- Start command is not available

ChiU

- Start command closes the gate

SPAP

Pedestrian in opening

PAUS

PAUS

no

- Pedestrian start command is not available

ChiU

- Pedestrian start command closes the gate

PAUS

- Gate goes in pause

Ch.AU 

Automatic closing 

no

no 

no

- The automatic closing is not active (it corresponds to 0)

0.5"÷ 20.0'

- The gate closes after the setup time

Ch.tr

Closing after passage

no

no

no

- Closing after passage disabled

0.5"÷ 20.0'

- Gate stop for a time to be set between 0.5" to 20'

PA.tr

no/Si

Pausa dopo il transito

no

no

LP.PA

no/Si

Flashlight in pause

no

no

Summary of Contents for CITY1

Page 1: ...IL n 170 1 EDIZ 04 03 2009 V2 S p A Corso Principi di Piemonte 65 67 12035 RACCONIGI CN ITALY tel 39 01 72 81 24 11 fax 39 01 72 84 050 info v2home com www v2home com CITY1 I...

Page 2: ...Y RIBBONS 28 LOCK 28 END OF STROKE 28 ENCODER 28 STOP 28 ACTIVATION INPUTS 29 EXTERNAL AERIAL 29 PLUG IN RECEIVER 29 OPTIONAL MODULES 29 CONTROL PANEL 30 USE OF DOWN MENU AND UP KEYS FOR PROGRAMMING 3...

Page 3: ...N 12453 allows We recommend to make use of an emergency button to be installed by the automation connected to the control unit STOP input so that the gate may be immediately stopped in case of danger...

Page 4: ...d in case of disabled obstacle sensor is described WARNING In case it has not yet fitted a start capacitor for each motor is required connect the start capacitor for motor 1 between terminals 27 and 2...

Page 5: ...good closing of doors Make use of a 12V lock Connect lock cables to terminals 20 and 21 of the control unit END OF STROKE CITY1 control unit supports the two following kinds of end of stroke end of s...

Page 6: ...f device controlling the first input between terminals 3 and 6 of the control unit Connect cables of device controlling the second input between terminals 4 and 6 of the control unit The first input f...

Page 7: ...nto its closing phase If it blinks it means that the closing has been caused by a safety device border or obstacle detector USE OF DOWN MENU AND UP KEYS FOR PROGRAMMING Control unit time and function...

Page 8: ...the doors will be activated in closing direction until the stop end or the closing end of stroke is reached Be sure that the leaves do not overlap In case NEITHER the ends of stroke NOR the obstacle s...

Page 9: ...ning phase before the relevant time expires WARNING if motor 2 is not connected this time must be set to zero in this circumstance the control unit will not consider all configurations of motor 2 and...

Page 10: ...mmand it will use this time to close the gate Max allowed time to be setup is t CH1 To avoid that the door does not close completely we recommend to setup a longer time than t APP opening time Leaf 2...

Page 11: ...motors to help the electric lock release The control unit controls the motors in reduced power in closing direction for the setup time The backlash precedes the electric lock release It is possible t...

Page 12: ...down function in order to measure both opening and closing times and to enable it again once the setup has been carried out The control unit will automatically consider the working time delay caused b...

Page 13: ...the step by step operation logic Select option APEr to set up the always open operation logic Start command during the pause This menu allows fixing the control unit conduct in case it receives a Sta...

Page 14: ...n is disabled by setting the value to zero no will be displayed the gate can be closed through the start command only in this case St PA menu setup will be ignored If the control unit receives a Stop...

Page 15: ...ns associated to the command of STOP no The input STOP is not available ProS The input STOP stops the gate pressing the command START the gate continues the motion invE The command STOP stops the gate...

Page 16: ...In some installations it may occur that the gate door passes before the photocells so breaking their beam In this case the gate cannot complete its closing cycle Through this function photocells can...

Page 17: ...eached its position of complete opening or closing no End of stroke inputs are disabled Si End of stroke inputs are enabled Motor Release on Mechanical Stop When the gate halts against the mechanical...

Page 18: ...exactly to the starting position it is possible to set an anti skid time that is added to the time calculated by the control unit in order to recover the inertia WARNING If function ASM is disabled t...

Page 19: ...d the learning cycle starts WARNING The procedure of the operation time automatic learning can be starter only if the Start inputs are set up on the STANDARD mode StAn End of Programming This menu all...

Page 20: ...cles after which the next service will be requested In case no new value is setup that is to say that the counter value is left at zero the signalling function for the service request will be disabled...

Page 21: ...0 no Pre flashing disabled it corresponds to 0 Pot1 30 100 Motor 1 power 60 60 Pot2 30 100 Motor 2 power 60 SPUn no Si Start off no Si t P So 0 5 3 0 Slowed down starting time 1 5 no no Slowed down s...

Page 22: ...no no no Function disabled F ShA FOTO2 disabling higher time i ShA FOTO2 disabling lower time CoS1 no Si Border 1 input fixed border no no CoS2 no Si Border 2 input mobile border no no FC En no Si En...

Page 23: ...ing phase N C contact 16 Common 17 18 Power output 24 VAC for photocells and other accessories 18 19 Photocell TX power supply for functional test 20 21 Electric lock 12VAC 22 23 Flashing light 230VAC...

Page 24: ...K 2 x 1 5 mm2 PG9 For cables with external from 5 to 8 mm OTHER WIRINGS MULTIPOLAR n x 0 25 0 5 mm2 n depending on the number of wirings to be made PG9 For cables with external from 5 to 8 mm PG11 For...

Page 25: ...sure that photocells are powered and working when you interrupt their beam you should hear the relay tripping Error 4 After few centimeters during the opening phase the gate stops and the display show...

Page 26: ...V2 S p A Corso Principi di Piemonte 65 67 12035 RACCONIGI CN ITALY tel 39 01 72 81 24 11 fax 39 01 72 84 050 info v2home com www v2home com...

Reviews: