ENGLISH
- 24 -
PARAMETER
VALUE
DESCRIPTION
AntE SCor
MEMO
En.SA
ENERGY SAVING function
When the function is active and the LOW ENERGY module is installed,
the control unit deactivates the display, the photocells, and all the
devices powered by a terminal box under determined conditions.
NOTE
: If the LOW ENERGY module is not installed, the control unit
deactivates only the display.
The control unit activates the ENERGY SAVING mode under the
following conditions:
• 30 seconds after completion of an operational cycle
• 30 seconds after an opening (if automatic closure is not enabled)
• 30 seconds after exiting the programming menu
The control unit exits from the ENERGY SAVING mode in these cases:
• If an operational cycle is activated
• If one of the keys on the control unit are pressed
no
no
no
Function deactivated
Si
Function activated
t.AP1
Leaf 1 opening time
20.0” 22.5”
0.0”-5’00
Adjustable time from 0 seconds to 5 minutes
t.AP2
Leaf 2 opening time
20.0” 0.0”
0.0”-5’00
Adjustable time from 0 seconds to 5 minutes.
WARNING
: if motor M2 is not connected, this time must be set to
zero
t.Ch1
Leaf 1 closing time
21.0” 23.5”
0.0”-5’00
Adjustable time from 0 seconds to 5 minutes.
NOTE
: To avoid that the door does not close completely, we
recommend to setup a longer time than
t.AP1
opening time.
t.Ch2
Leaf 2 closing time
21.0” 0.0”
0.0”-5’00
Adjustable time from 0 seconds to 2 minutes
NOTE:
To avoid that the door does not close completely, we
recommend to setup a longer time than
t.AP2
opening time
P.APP
Partial opening (leaf 1 only)
25
25
0 - 100
The percentage of the path the gate performs in the case of opening
using the Pedestrian Start command
r.AP
Opening door delay
1.0”
0.0”
0.0” - 1’00
During the opening phase, leaf 1 must start moving before leaf 2, to
avoid that both doors may collide.
Leaf 2 opening will be delayed for the setup time.
NOTE
: If you set the opening door delay to zero, the control board
does not execute the control of the correct leaves closing order
r.Ch
Closing door delay
3.0” 0.0”
0.0” - 1’00
During the closing phase, leaf 1 must start moving after leaf 2, to
avoid that both doors may collide.
Leaf 1 closing will be delayed for the setup time