13 - OPERATION DEFECTS

This paragraph shows some possible operation defects, along
with their cause and applicable remedy.

MAINS led does not switch on

It means that there is no voltage on PD19 control unit card.

1.

  Before acting on the control unit, disconnect through the 

disconnecting switch on the power line and remove the power 
supply terminal.

2.

  Be sure that there is no voltage break upstream the control 

unit.

3.

  Check whether the fuse is burnt-out, if so replace it with same 

value.

OVERLOAD led is on

It means that there is an overload on accessory power supply.

1.

  Remove the extractable part containing terminals M1 to M12. 

OVERLOAD led will switch off.

2.

  Remove the overload cause.

3.

  Reinsert the terminal board extractable part and check that this 

led is not on again.

Too long pre-blinking

When a Start command is given and the blinker switches on
immediately but the gate is late in opening, it means that the
setup cycle count down expired and the control unit shows that
service is required.

Slow movement of the gate while closing

This condition can occur when the motor encoder must be 
realigned: the gate is closed at slow speed until the closed range 
limit and after resumes normal operation.
This anomaly can occur due to power failure with the gate open 
or due to other factors related to the malfunctioning of the gate.

Error 1

The following writing appears on display when you exit from
programming 

Err1

It means that changed data could not be stored.
This kind of defect has no remedy and the control unit must be 
sent to V2 S.p.A. for repair.

Error 2

When a Start command is given and the gate does not open and
the following writing appears on display 

Err2

It means that triac test failed.
Before sending the control unit to V2 S.p.A. for repair, be sure 
that motors have been properly connected.

Error 3

When a Start command is given and the gate does not open and
the following writing appears on display 

Err3

It means that the photocell test failed.

1.

  Be sure that no obstacle interrupted the photocell beam when 

the Start command was given.

2.

  Be sure that photocells, as enabled by their relevant menus, 

have been installed actually.

3.

  If you have photocells 2, be sure that 

Fot2 

menu item is on 

CF.Ch

.

4.

  Be sure that photocells are powered and working; when you 

interrupt their beam, you should hear the relay tripping.

Error 4

When a Start command is given and the gate does not open (or 
does a partial opening) and the following writing appears on 
display 

Err4

This anomaly can occur when in one of the following conditions:

1.

  If a START command is sent with the motor released. 

2.

  During the self-learning cycle if there are any problems with 

the range limits. 
Check the direction of the magnets, if they are backwards, 
they should be removed and inverted. 
If the magnets are installed correctly, it means that the limit 
switch sensor is damaged or the cabling connecting the sensor 
to the central control unit is broken/damaged. 
Change the end of stroke sensor or the broken wiring.

3.

  During normal operation. If the error persists send the control 

unit to V2 S.p.A. for repair. 

Error 5

Once given a start control, the gate does not open and the
display shows 

Err5

It means that the test of the safety edges failed.
Check that the menu of the test of safety edges (Co.tE) have been 
set correctly.
Check that the safety edges enabled from the menu are installed.

Error 6

During the manoeuvre the motor stops and the display shows

Err6

It means that the triac verification system does not work.
If the problem persists, the control unit must be sent to V2 SpA 
for repair.

Error 7

When given a start control the gate does not open and the display 
shows 

Err7

This indicates an error in the encoders’ operation.
Encoder malfunction or broken connection.

Error 8

When executing a self-learning function, one of the following
conditions occurs:

1.

  the control is refused and the display shows 

Err8

 

It means that the setting of the control unit is not compatible 
with the requested function. 
In order to carry out self-learning, the Start inputs must be 
enabled in standard mode (

Strt

 menu set to 

StAn

) and the 

ADI interface must be disabled (

i.Adi

 menu set to 

no

).

2.

  The procedure stops and the displays shows 

Err8

 

It means that a safety device has tripped.

Error 9

When you are trying to change the control unit setups and the 
following writing appears on display 

Err9

It means that programming was locked by means of the 
programming lock key CL1+ (code 161213).
To change the settings it is necessary to insert in the connector of 
the ADI interface the same key used to activate the programming 
lock, and unlock the device.

Error 10

When a start command is given, the gate does not open and the
display shows the message 

Er 10

This means that the ADI module function test failed

Summary of Contents for AYROS series

Page 1: ...PESO GB 230V 120V ELECTRO MECHANICAL IRREVERSIBLE RACK ACTUATOR FOR SLIDING GATES UP TO 1200 KG F OPERATEUR ELECTROMECANIQUE 230V 120V IRREVERSIBLE A CREMAILLERE POUR PORTAILS COULISSANTS JUSQU A 120...

Page 2: ...200 mm 343 mm 178 mm 226 mm 334 mm 3 mm 328 mm 200 mm 343 mm 160 mm 74 mm 50 mm 100 mm 128 mm 206 mm 283 mm...

Page 3: ...ITALIANO 26...

Page 4: ...4 6 PHOTOCELLS 4 7 SAFETY RIBBONS 4 8 EXTERNAL AERIAL 4 9 ELECTRICAL CONNECTION 4 10 PLUG IN RECEIVER 4 11 ADI INTERFACE 5 CONTROL PANEL 5 1 DISPLAY 5 2 USE OF THE KEYS FOR PROGRAMMING 6 ACCESSING TH...

Page 5: ...make any modifications to any part of the automation device or the accessories connected to it unless described in this manual Any other modifications will void the warranty on the product The instal...

Page 6: ...are authorised for use and closure is not in a public area Examples of this type are gates inside business premises where the sole users are employees or a part of them who have been suitably informed...

Page 7: ...tended to be installed on sliding gates to create a machine according to the provisions of the Directive 2006 42 EC The machinery must not be put into service until the final machinery into which it h...

Page 8: ...1 7 A 2 A 2 6 A 4 3 A Running capacitor 8 F 10 F 12 F 36 F Start off capacitor 18 F 18 F 25 F 75 F Gate maximum speed 0 16 m s 0 16 m s 0 16 m s 0 18 m s Maximum thrust 400 N 670 N 950 N 950 N Duty ci...

Page 9: ...ace and parallel to the gate 5 Wait for the complete setting of the concrete 6 Unscrew the bolts fixing the base to the clamps and put the motor on the plate 7 Adjust the 4 grains to make the motor be...

Page 10: ...TOR Check the following points 1 the motor must be on a levelled surface and perfectly parallel to the gate 2 the distance between pinion and rack must be 1 or 2 mm If needed adjust the 4 grains 3 the...

Page 11: ...it positions the magnet be positioned next to the magnetic sensor behind the hood as near as possible to the hood The supplied magnets have been colored differently in order to be distinguished from e...

Page 12: ...nticlockwise closing the hatch of the lock then draw it out 4 Close the lock with the hatch J 3 6 INSTALLATION LAYOUT 1 3 E 5 4 A B F D 2 C LENGTH OF THE CABLE 10 metres from 10 to 20 metres from 20 t...

Page 13: ...es see Strt item of programming menu mWARNING If you use maintained command devices magnetic loop detectors timers presence detectors etc clock mode must be used parameter Strt oroL Standard mode STAR...

Page 14: ...on photocells power supply must be connected to terminals M11 and M12 of the control unit to carry out the operation test 4 7 SAFETY RIBBONS The control unit considers two kinds of safety ribbons depe...

Page 15: ...M10 M11 M12 RECEIVER FUSE MAINS OVERLOAD L LINE N NEUTRAL LAMP 230V MAX 40W COURTESY LIGHT CONTACT START START P STOP COM PHOTO 1 PHOTO 2 EDGE 1 EDGE 2 COM 24V 10W 24V Photo Edge Test GND ANT A1 A2 mC...

Page 16: ...uitable for a command of PD19 control unit CHANNEL 1 g START CHANNEL 2 g PEDESTRIAN START CHANNEL 3 g STOP CHANNEL 4 g COURTESY LIGHT NOTE Before programming 4 channels and function logics read carefu...

Page 17: ...the START command pressing the i key activates the PEDESTRIAN START command There are the following three kinds of menu items Function menu Time menu Value menu Function menu setup Function menus all...

Page 18: ...ot2 CoS1 CoS2 according to the safety devices installed on the gate For the position of the item menus inside the main menu and for the options related to each item menu refer to the chapter 12 3 Star...

Page 19: ...o store the precise position of the range limit it is recommended to activate the slow speed near to the limit The position at which the slow speed is activated is stored as the starting point for slo...

Page 20: ...to read the totalizing counter how to read the number of cycles before the next service is required as well as how to program the number of cycles before the next request for service as for the exampl...

Page 21: ...e gate opens leftwards P APP Partial opening 25 0 1 00 The percentage of the path the gate performs in the case of opening using the Pedestrian Start command t PrE Pre blinking time 1 0 0 5 1 00 Befor...

Page 22: ...pening phase This menu allows fixing the control unit conduct in case it receives a Start command during the opening phase PAUS PAUS The gate stops and goes to pause ChiU The gate immediately starts c...

Page 23: ...ime adjustable time from 0 5 to 20 0 PA t r Pause after transit no Si In order to let the gate open for the shortest possible time it is possible to stop the gate once the passage before the photocell...

Page 24: ...cells active both during the opening and closing phase no no Input disabled ignored by the control unit AP Ch Input enabled Fot2 Photocell 2 input This menu allows enabling the input for type 2 photoc...

Page 25: ...sed rate below the set threshold indicates the presence of an obstacle If set to 0 the obstacle is only detected when the gate is stopped When the sensor intervenes the gate stops and is operated in t...

Page 26: ...interrupt their beam you should hear the relay tripping Error 4 When a Start command is given and the gate does not open or does a partial opening and the following writing appears on display Err4 Th...

Page 27: ...iciency of all warning devices the perfect efficiency of all safety devices measurement of the gate operating forces the lubrication of mechanical parts on the automation device where necessary the st...

Page 28: ...ay vary depending on the intensity of use Any inspection maintenance or repairs should only be performed by qualified personnel Even if you think you know how do not modify the system and the automati...

Page 29: ...V2 S p A Corso Principi di Piemonte 65 67 12035 RACCONIGI CN ITALY Tel 39 0172 812411 Fax 39 0172 84050 info v2home com www v2home com...

Reviews: