PARAMETER
VALUE
DESCRIPTION
DEFAULT
MEMO
t.inv
Backlash time
no
0.5” - 1’00
It could be useful to give a closing command to motors, to help the
electric lock release. The control unit controls the motors in reduced power
in closing direction for the setup time
no
Function deactivated
t.PrE
Pre-blinking time
1.0”
0.5” - 1’00
Before any gate movement, blinker will be activated for
t.PrE
time, to
warn about the incoming motion
no
Function deactivated
Pot1
Motor 1 power
80
30 - 100
The displayed value is the percentage of max. motor power
Pot2
Motor 2 power
80
30 - 100
The displayed value is the percentage of max. motor power
Po.r1
Power motor 1 during slow-down phase
50
0 - 70
The displayed value is the percentage of max. motor power
Po.r2
Power motor 2 during slow-down phase
50
0 - 70
The displayed value is the percentage of max. motor power
P.bAt
Maximum motor power during battery operation
During battery operation, the controller is powered with a lower voltage
compared to mains power. For this reason, the power of the motors is
reduced compared to normal operation and may not be sufficient to move
the gate panels effectively.
This menu allows you to activate the motors at their maximum power
during battery operation.
Si
Si
Function activated
no
Function deactivated
SPUn
Start off
When the gate is standstill and it begins moving, the initial inertia must be
faced, therefore, if your gate is quite heavy, its doors could not move.
In case the
SPUn
(pickup) function is activated, for the first 2 seconds of
motion of each door, the control unit will ignore both
Pot1
and
Pot2
values and it will give motors the maximum power command in order to
overcome the gate inertia.
Si
Si
Function activated
no
Function deactivated
rAM
Starting ramp
4
0 - 10
In order not to stress too much the motor, when the motion starts the
power is gradually increased, until reached the set value or 100% if the
take-off is enabled.
Higher is the set value, longer the length of time of the ramp, that is the
time necessary to reach the value of nominal power.