6 - HYDRONIC PIPING
6.1 General
• Primary/Secondary piping required.
• Install piping in accordance with authority having
jurisdiction.
• Support system piping and safety relief valve discharge
piping. Boiler's internal piping and wall mount bracket can
be damaged if subjected to excessive weight.
NOTICE
The intended use of the internal heat exchanger pump
is a boiler loop. Do not use as a primary system pump.
• Size central heating pump (and domestic hot water pump,
if used) for system requirements only. Internal heat
exchanger pump compensates for pressure drop through
boiler internal piping and heat exchanger.
•
Thoroughly clean and flush system before connecting to
boiler.
• If oil is present in system water, use approved detergent
to wash system.
• It is necessary to semi-annually check the water quality of
central heating systems.
• Manufacturer recommends installation of magnetic dirt
separator in the hydronic system where there are cast
iron or steel components, or where the previous boiler
was a cast iron heat exchanger. The abrasive, extremely
fine sediment is difficult to remove and can deposit onto
heat exchange surfaces and accumulate in pump cavities
causing reduced efficiency and premature wear.
• Flush system to remove any solid objects such as metal
chips, fibers, or Teflon tape, etc.
• Flush system until water runs clean and piping is free of
sediment.
•
Use purge valve to flush zoned systems, each zone
separately. If purge valves and isolation valves are not
installed, install them to properly clean the system.
• When purging installations that include standing iron
radiators and systems with manual vents at high points,
start with nearest manual air vent. Open the vent until
water flows out, then close vent. Repeat this procedure,
working toward furthest air vent.
• Install a basket strainer if large amounts of sediment is
present. Keep basket clear of sediment build up.
• Manufacturer recommends a water treatment product be
used for sediment removal.
• Ensure piping in the heating system has an oxygen
barrier.
FIGURE 6-1 Safety Relief Valve
Note
Boiler rated at 50 psig (345 kPa) maximum
allowable working pressure. Boiler provided with
30 psig (206 kPa) safety relief valve.
WARNING
• Poison hazard. Ethylene glycol is toxic. Do not use
ethylene glycol.
• Never use automotive or standard glycol antifreeze,
even ethylene glycol made for hydronic systems.
• Ethylene glycol can attack gaskets and seals used in
hydronic systems.
• Do not use petroleum based cleaning or sealing
compounds boiler system.
•
Do not fill boiler or boiler system with softened
water.
• Use only inhibited propylene glycol solutions
certified by fluid manufacturer as acceptable for use
with closed water heating system.
•
Thoroughly clean and flush any system that used
glycol before installing new Boiler.
• Provide user with Material Safety Data Sheet
(MSDS) on fluid used.
!
Safety Relief
Safety Relief
Valve
Valve
Note
When installing safety relief valve it must be
installed in a vertical position with spindle at
top.
TP Gauge
TP Gauge
System Supply
System Supply
System Return
System Return
Note
System pressure above 43 psi [2.96 bar]
WILL
result in boiler shutting down.
240013354 REV B [09/15/2021]
Summary of Contents for MAC-115
Page 2: ...MAC 205 ...
Page 4: ...MAH 165 ...
Page 77: ...73 APPENDIX A WIRING DIAGRAMS A 2 MODEL 125 Heat Only 240013354 REV B 09 15 2021 ...
Page 78: ...74 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013354 REV B 09 15 2021 ...
Page 79: ...75 APPENDIX A WIRING DIAGRAMS A 1 MODEL 115 Combi 240013354 REV B 09 15 2021 ...
Page 80: ...76 APPENDIX A WIRING DIAGRAMS A 4 MODEL 150 Combi 240013354 REV B 09 15 2021 ...
Page 81: ...77 APPENDIX A WIRING DIAGRAMS A 5 MODEL 205 Combi 240013354 REV B 09 15 2021 ...
Page 82: ...78 NOTES 240013354 REV B 09 15 2021 ...
Page 118: ...34 MODEL 125 Heat Only 125 HEAT ONLY WIRING DIAGRAM PN 240011430 REV P 09 15 2021 ...
Page 119: ...35 MODEL 165 Heat Only 165 HEAT ONLY WIRING DIAGRAM PN 240011430 REV P 09 15 2021 ...
Page 120: ...36 115 COMBI WIRING DIAGRAM MODEL 115 Combi PN 240011430 REV P 09 15 2021 ...
Page 121: ...37 MODEL 150 Combi 150 COMBI WIRING DIAGRAM PN 240011430 REV P 09 15 2021 ...
Page 122: ...38 MODEL 205 Combi 205 COMBI WIRING DIAGRAM PN 240011430 REV P 09 15 2021 ...
Page 127: ...43 Low Water Cutoff Detail LOW WATER CUTOFF NO NO YES PN 240011430 REV P 09 15 2021 ...
Page 132: ...48 3 FAULT SOLUTION SECTIONS PN 240011430 REV P 09 15 2021 ...