background image

19

Annual Inspection - Before Start of Heating Season

Periodically or at start of heating season inspect boiler, vent 

and vent pipe for accumulation of soot or scale deposits. 

When soot is present on section walls and flueways, 

improper combustion results, causing additional sooting 

and scaling until flueways are completely closed. 

A. 

To remove soot and scale from flueways, remove 

top jacket panel, top clean-out plate and burner. See 

instructions on Removing Oil Boiler. Use wire brush, 

brush soot and scale into combustion chamber where 

it can be removed through burner opening. 

B.  Carefully vacuum debris from combustion chamber. 

Inspect combustion chamber for signs of damage, i.e. 

cracks. 

C.  In event combustion chamber is damaged, contact 

qualified service agent to replace immediately. 

MAINTENANCE PROCEDURES

NOTICE

Do not overtighten bolts.

Periodic inspection

 and tightening of tankless heater/

cover plate bolts reduce the risk of leaks. CAUTION: Do not 

overtighten bolts.

Instructions For Removing Oil Burner

1. 

Turn off power to boiler.

2. 

Allow boiler to cool down.

3. 

Remove three (3) 1/2" nuts from burner flange.

4. 

Close oil valve. See Figure 16 

and Figure 17, page 13

.

5. 

Disconnect oil line from burner. 

Recommend replacing nozzle at start of each heating 

season. 
Lubricate burner motor and circulator motor - if required - 

with few drops of good grade of light motor oil. Do not over 

oil. 

Have qualified service agent service burner and check 

controls and electrodes for carbon or cracks in insulators. 

Adjust burners to produce conditions shown in Start-up and 

Adjustment of Oil Burner procedure.

Instructions For Replacing Oil Burner

1. 

Reconnect oil line.

2. 

Open oil valve. See Figure 16

 and Figure 17, page 13.

3. 

Install and tighten three (3) 1/2" nuts on burner flange.

4. 

Turn on power to boiler.

Regular Maintenance

• Inspect venting system at start of each heating season. 

Check vent pipe from boiler to chimney for signs 

of deterioration by rust or sagging joints. Repair if 

necessary.

• 

Remove vent pipe at base of chimney or flue. Use mirror, 

check for obstruction.

• Verify compliance to the latest revision of the NFPA 211.
• Operate lever of safety relief valve on boiler periodically 

to verify that it is functioning properly. Open pressure 

relief valve before water pressure exceeds 30 psi reading 

on gauge. If pressure is exceeded and pressure relief 

valve leaks water when boiler is operating at normal 

pressures, replace immediately. Corrosion can build at 

valve seat and prevent functioning as safety device.

Summary of Contents for BC3095

Page 1: ...BOILER INSTALLATION OPERATION MAINTENANCE MANUAL An ISO 9001 2008 Certified Company Manufactured by ECR International Inc 2201 Dwyer Avenue Utica NY 13501 web site www ecrinternational com Models BC3...

Page 2: ...other flammable vapors and liquids DO NOT obstruct air openings to the boiler room Modification substitution or elimination of factory equipped supplied or specified components may result in personal...

Page 3: ...NS Table 1 DIMENSIONS Boiler No Length of Flush Jacket Front of Jacket to Center Line of Flue Outlet Flue Outlet Diameter Tankless Coil to Back of Jacket A B C D BC3 19 9 6 8 BC4 23 11 6 12 Figure 1 D...

Page 4: ...n extensive piping 4 For forced hot water heating systems where boiler and all piping are within the area to be heated select boiler on basis of its Heating Capacity 5 Nozzle listed for use with Becke...

Page 5: ...ion system as practical Allow 24 inches in front top and right hand side for servicing and cleaning or removing tankless water heating coil When installed in utility room door should be wide enough to...

Page 6: ...one starting 12 inches from the top and one 12 inches from the bottom of the enclosed space Each opening shall have a minimum free area of 1 square inch per 1 000 BTU per hour of the total input rati...

Page 7: ...d each opening shall have a minimum free area 1 square inch per 2 000 BTU per hour total input rating of all appliances in the enclosed space See Figure 5 D When ducts are used they shall be of the sa...

Page 8: ...as suggested in Figure 6 When the boiler is used in connection with refrigerated systems A Chilled medium MUST BE IN PARALLEL with boiler B Use appropriate valves to prevent chilled medium from enter...

Page 9: ...o fit the system or condition of the installation Although this method of piping is not typically required for baseboard heating systems A This method is used to protect systems using radiant panels a...

Page 10: ...10 CONNECTING SUPPLY AND RETURN PIPING Figure 9 Bypass Piping Option Used to Protect From Converted Systems With High Water Temperature Figure 10 Typical Installation With Circulators...

Page 11: ...11 CONNECTING SUPPLY AND RETURN PIPING Figure 11 Typical Installation With Valves Figure 12 Typical Installation With DHW...

Page 12: ...ety relief valve outlet and downstream of union if used Terminate pipe with plain end not threaded Refer to local codes and appropriate ASME Boiler and Pressure Vessel Code for additional installation...

Page 13: ...sitive pressure in the combustion chamber Horizontal portions of venting system should not exceed 10 ft in length Horizontal lengths over 10 ft will have negative effect on chimney performance Chimney...

Page 14: ...ended E Compression fittings on suction line often allows air to be drawn into fuel pump making it difficult to maintain oil pressure at the nozzle F Do not run overhead fuel lines from tank to oil bu...

Page 15: ...an inside wall about four feet above the floor 2 NEVER install a thermostat on an outside wall 3 Do not install a thermostat where it will be affected by drafts hot or cold pipes sunlight lighting fi...

Page 16: ...16 WIRING DIAGRAMS Figure 18 Wiring Diagram...

Page 17: ...limit literature for additional information B Burner delay by passed for tankless heat call for heat Burner ignition begins immediately Burner and circulator operation continues until thermostat stops...

Page 18: ...limit point Burner should start B Verify Primary Control and Flame Sensor Flame Failure simulate by shutting off oil supply with hand valve while burner is on Sixty seconds after flameout safety swit...

Page 19: ...ure 17 page 13 5 Disconnect oil line from burner Recommend replacing nozzle at start of each heating season Lubricate burner motor and circulator motor if required with few drops of good grade of ligh...

Page 20: ...ERVICE RECORD Date Nozzle Pump Pressure PSI Smoke Draft CO2 or O2 Flue Temp F Size Angle Type O F INF Controls and Safety Devices X Nozzle Size Angle Type Pump Pressure Vacuum Line Voltage Motor Amps...

Reviews: