UTC. All Rights Reserved.
2
P/N 0000000 – Rev. A – 06 Nov 12
o
Do not install near vents, flues, chimneys, or any
forced/unforced air ventilation openings.
o
Do not install on metal surfaces.
o
Avoid mounting in areas with a large quantity of metal or
electrical wires.
o
Do not install near ceiling fans, doors, windows, or areas
directly exposed to the weather.
o
Do not install in dead air spaces, such as peaks of vaulted
ceilings or gabled roofs, where CO may not reach the sensor in
time to provide early warning.
o
Do not install near deep-cell large batteries. Large batteries
have emissions that can cause the alarm to perform at less
than optimum performance.
o
Do not obstruct the vents located on the alarm. Do not place the
alarm where drapes, furniture, or other objects block the flow of
air to the vents.
3.
Mounting the Sensor
Note:
Add the product to the Control Panel before physically mounting
the product in the desired location. This verifies RF performance prior to
permanently mounting the alarm. See “RF communication test”.
The CO Alarm can be wall mounted or ceiling mounted.
To mount the alarm:
A.
Slide the product body off of the mounting plate. Place the
mounting plate in the desired location, and mark the location of
the two mounting holes. Orient the mounting plate vertically or
horizontally as shown in the following figures.
Note:
The product can also be directly mounted to a single gang box.
Vertical Mounting
Horizontal Mounting
B.
Insert the two screws provided and secure the mounting plate
to the wall or ceiling surface. (If mounting in plasterboard or
drywall, drill a 3/16 in. hole and use the plastic anchors
provided.)
C.
After the mounting plate is secured, slide the alarm over the
mounting plate (see Figure 4 on page 2).
Important labels provided
Two labels have been provided that have important information on
what to do in case of an alarm. Add the phone number of your
emergency service provider in the space provided. Place one label next
to the alarm after it is mounted, and one label near a fresh air source
such as a door or window.
4.
Basic Operations
This product is equipped with an intuitive normal mode operation.
Since the batteries are pre-installed, remove the battery pull tab to turn
ON power. The product shall search for a networked control panel to
pair with. During this time, Search Mode, the RF wireless module
transmits every ~ 5-seconds. Not pairing or enrolling into a control
panel within minutes of initial power up, places a large drain the
batteries. Failure to complete pairing results in dead batteries after 2-3
days time passes.
Normal Mode Operation
o
In normal operation, the green Power LED flashes once every 30
seconds.
o
In alarm mode, the red Alarm LED flashes with four quick
beeps, 5-seconds silence and repeat.
o
In trouble or maintenance mode, the red Alarm LED flashes
once every 30 seconds with one audible chirp.
o
In low battery mode, the red Alarm LED flashes once every 60
seconds with one quick beep until the batteries are replaced.
Press the Test/Hush button to silence the audible chirp for
between 8-11 hours.
Note:
the modes can be viewed from the Control Panel.
Silence the Alarm
Press the Test/Hush button to silence the sounder during an alarm.
After a few minutes, the sounder and alarm resume if dangerous CO
gas levels are still present.
5.
Installing / Replacing Battery
This product comes with three battery preinstalled. When you need to
replace the battery, use the following procedure.
Note:
Place the control panel into sensor test mode prior to replacing
the batteries. If the control panel is not in sensor test mode during
battery replacement, an alarm/tamper condition may be indicated.
A.
Slide the product body off of the mounting plate.
B.
If replacing batteries, remove the old batteries and properly
dispose of them as recommended by the battery manufacturer.
C.
Install the new batteries. Note the polarity illustration in the
battery compartment (see Figure 3 below).