Page 1: ...P N 06 237214 002 June 2012 A UTC Fire Security Company ARIES NETLink BACnet Interface Module User s Guide ...

Page 2: ......

Page 3: ...r assumes no responsibility for the application of any systems other than those addressed in this manual The technical data contained herein is limited strictly for informational purposes only The manufacturer believes this data to be accurate but it is published and presented without any guarantee or warranty whatsoever The manufacturer disclaims any liability for any use that may be made of the ...

Page 4: ...ule 1 10 1 6 2 Systems With 5 to 8 SLCs Two BACnet Interface Modules 1 11 1 7 Specifications 1 12 CHAPTER 2 BACNET IP 2 1 Introduction 2 1 2 2 Downloading Third Party Remote User Interface Utility 2 1 2 3 Connecting to The Remote User Interface 2 2 2 4 Using The Remote User Interface To Set IP Address 2 2 2 5 Connecting to the WEB Graphical User Interface GUI 2 3 2 6 Using the WEB GUI To Set IP Ad...

Page 5: ...ACnet Interface Module 1 5 1 5 BACnet Interface Module DIP Switches 1 6 1 6 LEDs on BACnet Interface Module ProtoCessor Board 1 7 1 7 LEDs on BACnet Interface Module Main Board 1 8 2 1 Use the following IP address Screen 2 1 2 2 RUInet Main Menu 2 2 2 3 WEB GUI Home Page 2 3 2 4 Web GUI Edit IP Address Settings Screen 2 4 4 1 Use the following IP address Screen 4 2 4 2 Selecting IP Address 4 3 4 3...

Page 6: ...1 8 1 5 Default Communication Settings 1 9 1 6 BACnet Event State Mapping for ARIES NETLink 1 10 1 7 BACnet Multi State Input Mapping for ARIES NETLink Systems With 4 or Fewer SLCs 1 10 1 8 BACnet Multi State Input Mapping for ARIES NETLink Systems With 5 to 8 SLCs 1 11 1 9 BACnet Interface Module Specifications 1 12 3 1 A Bank Switch Settings for BACnet Interface Module Addresses 3 2 LIST OF TABL...

Page 7: ...i protocol gateway that has been pre programmed for the ARIES NETLinkTM control unit to support both BACnet MS TP and BACnet IP protocols Configuration of the BACnet Interface Module is programmed to support Modbus RTU signal output from the ARIES NETLink Figure 1 1 BACnet Interface Module P N 76 800300 007 a BACnet Interface Module Shown with Optional Add On Module P N 76 800300 017 b a b ...

Page 8: ...r from control unit to BACnet Interface Module Verifying grounding to Earth Ground stud Connecting RS232 communications from control unit to BACnet Interface Module Connecting BACnet Interface Module to either a BACnet IP or BACnet MS TP network Setting B Bank DIP switches on BACnet Interface Module to match baud rate of MS TP network Installing an Add On Module if required Connecting power ground...

Page 9: ...General Information P N 06 237214 002 1 3 June 2012 Figure 1 2 Wiring Diagram for BACnet Interface Module ...

Page 10: ...General Information June 2012 1 4 P N 06 237214 002 Figure 1 3 Wiring Diagram for BACnet Interface Module with Add On Module ...

Page 11: ...wire s from one of the BACnet Interface Module mounting screws to one of the Earth Ground studs located inside the enclosure Refer to the wiring diagrams provided in Figure 1 1 and Figure 1 2 A Bank DIP Switches B Bank DIP Switches S Bank DIP Switches 3 Pin Connector for BACnet MS TP network End Of Line Switch ProtoCessor Board Main Board Ethernet port for BACnet IP network Phoenix Connector RS232...

Page 12: ...elow This value is set at the factory and should only be changed if an Add On BACnet Interface Module is installed Switch S0 only Note A single BACnet Interface Module supports systems with up to 4 Signaling Line Circuits SLCs For systems including more than 4 SLCs an Add On BACnet Interface Module is required Table 1 2 S Bank DIP Switch Settings Switches S0 through S3 S0 should be set to OFF on t...

Page 13: ... go on solid 15 seconds after power up It will turn off after 5 seconds A steady red light will indicate a communication error has occurred Toestablish the cause of the error gototheerrorscreenof the RUI interface Config ERR ConfigERR LEDwillgoonsolid15seconds afterpower up Itwill turnoff after 5 seconds Asteady amberlight willindicatea configurationerror exists inthe activeconfiguration Seethe Er...

Page 14: ... LED will go on solid 15 seconds after power up It will turn off after 5 seconds A steady red light will indicate there is a system error on the module If this occurs immediately report the related system error shown in the error screen of the RUI interface to Fenwal Protection Systems Technical Support for evaluation RX The RX LED will flash when a message is received on the RS232 port TX The TX ...

Page 15: ... Modbus 2 Add On BACnet In terface Module 3 Use either the keypad menus on the ARIES NETLink control unit or use the ARIES NETLink Configuration Tool ACT8000 to set the port Modbus ID to 2 Note The RS232 port Modbus ID should always be set to 2 for all BACnet Interface Modules included in your system If using the keypad menus of the control unit After 4 MODBUS RTU is selected a prompt will ask for...

Page 16: ... Circuits SLCs the control unit data is mapped to BACnet Multi State Inputs as shown in Table 1 7 below Table 1 7 BACnet Multi State Input Mapping for ARIES NETLink Systems With 4 or Fewer SLCs Control Unit Status BACnet Object Event State Supervisory 0x1 fault Trouble 0x1 fault Pre Alarm 0x1 fault Alarm 0x2 in_alarm Normal 0 Control Unit Data Multi_State_Input System Status 0 SLC Loop 1 Device 0 ...

Page 17: ...mum Signaling Line Circuits SLCs the control unit data is mapped to BACnet Multi State Inputs as shown in Table 1 8 below Table 1 8 BACnet Multi State Input Mapping for ARIES NETLink Systems With 5 to 8 SLCs Control Unit Data Multi_State_Input System Status 0 SLC Loop 5 Device 0 1 1 2 255 256 SLC Loop 6 0 257 255 512 SLC Loop 7 0 513 255 768 SLC Loop 8 0 769 255 1024 ...

Page 18: ... Ethernet port Approvals BACnet Testing Laboratory BTL Marked Power Requirements 9 30VDCor 12 24VAC Physical Dimensions 4 5 in L x 3 2in W x 1 6 in H 11 5 cmL x 8 2 cmWx 4 0 cm H Weight 0 4 lbs 0 2 kg Operating Temperature 40 F to167 F 40 C to 75 C Surge Suppression EN61000 4 2ESD EN61000 4 3 EMCEN61000 4 4 EFT Humidity 5 90 RH non condensing Default BACnet IPAddress 192 168 1 24 Default BACnet MS...

Page 19: ...et port of the BACnet Interface Module Refer to Section 1 3 Components Overview for location of the Ethernet port 4 The Default IP Address of the BACnet Interface Module is 192 168 1 24 Subnet Mask is 255 255 255 0 If the PC and the module are on different IP Networks assign a static IP Address to the PC on the 192 168 1 xxx network by doing the following For Windows XP Go to Windows Start Control...

Page 20: ...Set tings menu 2 Press 1 to modify the IP address of the Ethernet adapter 3 Type in a new IP address in the format 192 168 2 X and press Enter 4 If necessary press 2 to and change the Subnet mask 5 Type in a new Subnet Mask and press Enter 6 If necessary press 3 to and change the IP Gateway 7 Type in a new IP Gateway and press Enter Note If the BACnet Interface Module is connected to a router the ...

Page 21: ... new IP address in the format 192 168 2 X 3 If necessary change the Netmask N1 Netmask field 4 Type in a new Subnet Mask 5 If necessary change the IP Gateway Default Gateway field 6 Type in a new IP Gateway Note If the BACnet Interface Module is connected to a router the IP Gateway of the mod ule should be set to the IP address of the router that it is connected to 7 Select Update IP Settings to s...

Page 22: ...BACnet IP June 2012 2 4 P N 06 237214 002 Figure 2 4 Web GUI Edit IP Address Settings Screen ...

Page 23: ...Note that all BACnet Interface Modules are factory set to the address of 8 when shipped The default value is shown in a yellow highlighted row in Table 3 1 3 1 2 Changing Address Value To change the module s address from its default setting move the A Bank dip switches to the corresponding ON OFF positions for the desired address value Refer to Table 3 1 for a list of available addresses and how t...

Page 24: ... Off Off On Off Off On On 19 Off Off Off On Off On Off Off 20 Off Off Off On Off On Off On 21 Off Off Off On Off On On Off 22 Off Off Off On Off On On On 23 Off Off Off On On Off Off Off 24 Off Off Off On On Off Off On 25 Off Off Off On On Off On Off 26 Off Off Off On On Off On On 27 Off Off Off On On On Off Off 28 Off Off Off On On On Off On 29 Off Off Off On On On On Off 30 Off Off Off On On On ...

Page 25: ... Off On 65 Off On Off Off Off Off On Off 66 Off On Off Off Off Off On On 67 Off On Off Off Off On Off Off 68 Off On Off Off Off On Off On 69 Off On Off Off Off On On Off 70 Off On Off Off Off On On On 71 Off On Off Off On Off Off Off 72 Off On Off Off On Off Off On 73 Off On Off Off On Off On Off 74 Off On Off Off On Off On On 75 Off On Off Off On On Off Off 76 Off On Off Off On On Off On 77 Off O...

Page 26: ...Off 110 Off On On Off On On On On 111 Off On On On Off Off Off Off 112 Off On On On Off Off Off On 113 Off On On On Off Off On Off 114 Off On On On Off Off On On 115 Off On On On Off On Off Off 116 Off On On On Off On Off On 117 Off On On On Off On On Off 118 Off On On On Off On On On 119 Off On On On On Off Off Off 120 Off On On On On Off Off On 121 Off On On On On Off On Off 122 Off On On On On ...

Page 27: ...On On Off Off 156 On Off Off On On On Off On 157 On Off Off On On On On Off 158 On Off Off On On On On On 159 On Off On Off Off Off Off Off 160 On Off On Off Off Off Off On 161 On Off On Off Off Off On Off 162 On Off On Off Off Off On On 163 On Off On Off Off On Off Off 164 On Off On Off Off On Off On 165 On Off On Off Off On On Off 166 On Off On Off Off On On On 167 On Off On Off On Off Off Off 1...

Page 28: ... On Off On Off 202 On On Off Off On Off On On 203 On On Off Off On On Off Off 204 On On Off Off On On Off On 205 On On Off Off On On On Off 206 On On Off Off On On On On 207 On On Off On Off Off Off Off 208 On On Off On Off Off Off On 209 On On Off On Off Off On Off 210 On On Off On Off Off On On 211 On On Off On Off On Off Off 212 On On Off On Off On Off On 213 On On Off On Off On On Off 214 On O...

Page 29: ...n Off On On On Off 238 On On On Off On On On On 239 On On On On Off Off Off Off 240 On On On On Off Off Off On 241 On On On On Off Off On Off 242 On On On On Off Off On On 243 On On On On Off On Off Off 244 On On On On Off On Off On 245 On On On On Off On On Off 246 On On On On Off On On On 247 On On On On On Off Off Off 248 On On On On On Off Off On 249 On On On On On Off On Off 250 On On On On O...

Page 30: ...BACnet MS TP June 2012 3 8 P N 06 237214 002 THIS PAGE INTENTIONALLY LEFT BLANK ...

Page 31: ...n a Static IP Address to the PC on the 192 168 1 0 network using the Remote User Interface Utility If Using Windows XP ensure that the firewall is disabled Ensure that all other Ethernet cards active on the PC especially wireless adapters are dis abled Ensure that the BACnet Interface Module address is set correctly Ensure that DIP switch positions are set correctly Refer to Section 1 3 2 DIP Swit...

Page 32: ...f the Ethernet port 4 The Default IP Address of the BACnet Interface Module is 192 168 1 24 Subnet Mask is 255 255 255 0 If the PC and the module are on different IP Networks assign a static IP Address to the PC on the 192 168 1 xxx network For Windows XP Go to Windows Start Control Panel Network Connections Right click on Local Area Connection Properties Highlight Internet Protocol TCP IP Propert...

Page 33: ... DOS prompts will flash across the monitor Do not click or type anything in response to these DOS prompts This step may take a few minutes depending on whether Short Log or Long Log has been selected and the speed of the PC laptop When the utility is finished you will be presented with a log of events that have occurred Figure 4 3 Taking a Log Type in the BACnet Interface Module IP address Default...

Page 34: ...files is C Program Files FieldServer FST_Diag upload zip Select Locate Folder to launch Windows Explorer and have it point directly at the correct folder Note Do not send log files to Field Server Technologies Contact Kidde Technical Support at 866 287 2531 for instructions on how to send the upload zip file for diagnos tic purposes and request technical assistance 9 Close the utility program by s...

Page 35: ......

Page 36: ...ce All specifications subject to change without notice Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser s purposes the matter should be referred to KIDDE FENWAL INC Ashland Masssachusetts 06 237214 002 Rev AA 2012 Kidde Fenwal Inc All rights reserved Kidde is a registered trademark of Kidde Fenwal Inc ARIES NETLink is a ...