REGENERATIVE DC COMMON BUS SUPPLY 2
SPECIFICATIONS AND FEATURES
Electrical Specifications:
Rated Input Voltage:
200-250Vac, 380-500Vac, 500-600Vac
-10% of minimum, +10% of maximum.
Frequency Tolerance:
47-63 Hz
Number of Phases:
3
Efficiency:
99% or greater
Max. Short Circuit Current Rating:
200,000A rms symmetrical, 600 volts (when used with AC input line fuses
specified in tables 1 to 3).
Noise Immunity:
IEEE C62.41-1991 Category B (Formerly known as IEEE 587) - 6000V tests
EN50082-1, 2 Generic Immunity Standards
IEC 1000-4-2 ( IEC 801-2 )
IEC 1000-4-3 ( IEC 801-3 )
IEC 1000-4-4 ( IEC 801-4 )
IEC 1000-4-5 ( IEC 801-5 )
IEC 1000-4-6 ( IEC 801-6 )
IEC 1000-4-8 ( IEC 801-8 )
Environmental Specifications:
Ambient Temperature:
-10
C to 55
C (14
F to 131
F) Nema type 1 enclosed.
Storage Temperature:
-40
C to 70
C (-40
F to 158
F) Nema type 1 enclosed.
Altitude:
Sea level to 3000 Feet [1000m] without derating.
Humidity:
95% relative humidity non-condensing.
Vibration:
9.8m/sec
2
(1.0G) peak.
Physical attributes:
Mounting:
Though hole or panel mount.
Nema Rating:
Type 1 (IP20) as standard, Type 12 (IP54) optional.
Construction:
Steel construction (reduces E.M.I.)
Control I/O:
2 Digital Inputs:
Regen Enable & Regen Reset
2 Digital Outputs:
Form C dry contacts rated 115Vac @ 5A; 30Vdc @ 3.5A.
1 meter output:
Use with 100
A movement analog meter.
24Vdc source:
Use to power operator pushbuttons and US Drives option boards: 24Vdc @ 100 mA
max.
Protective Features:
Peak output current monitoring to protect against line-to-line shorts and line-to-ground shorts.
Ground fault monitoring.
Heatsink over-temperature monitoring.
AC line & DC bus over-voltage protection.
AC line & DC bus under-voltage protection.
Control power supply power ride-thru.
Internal power supply monitoring.
AC phase loss detection.
Standard Regen Features
Latest generation IBGT.
Nema type 1 (IP20) as standard for all models.
55
C ambient with standard Nema type 1 (IP20) enclosure.
High voltage ratings: 10% , 10% models, and 10% models
Input line suppression: Metal oxide varistors for line-to-line and line-to-ground voltage surge protection.
No programming or hardware jumper for all voltages.