3. Installation
12) If it is necessary to connect the inductance load such as a monitor or a
laser printer to the UPS, the start-up power should be used for
calculating the capacity of the UPS, as its start-up power consumption
is too big when it is started.
Input and Output Terminal Block wiring diagram of 6K(L)/10K(L)
Input and Output Terminal Block wiring diagram of
31 10KL/31 12KL/31 15KL/31 20KL
3.3 Operating procedure for connecting the long backup
time
model UPS with the external battery
3.3.1 The nominal DC voltage of external battery pack is 192VDC. Each
battery pack consists of 16 pieces of 12V “maintenance-free” batteries in
series. To achieve longer backup time, it is possible to connect
multi-battery packs, but the principle of “same voltage, same type” should
be strictly followed.
3.3.2 For 6KL/10KL/31 10KL/31 12KL/31 15KL/31 20KL, the procedure
of installing battery bank should be complied with strictly. Otherwise you
may encounter the hazardous of electric shock.