Menu 05: High Floor Temperature Limitation

Default: 78°F (26°C) 

Setting range: 38 – 95°F (20 – 35°C), 1°F (0.5°C) increments

Note

This parameter cannot be set lower than the set 

value in settings 

Menu 06

 (low floor temperature 

limitation).

In this menu, a limit on the highest allowable floor 

temperature is set. This menu is only visible if control 

mode RFT is activated in 

Menu 04

. For systems with a 

Communication Module, this menu only shows the set 

value. Changes are done in the Smatrix Pulse App.

Menu 06: Low Floor Temperature Limitation

Default: 68°F (20°C) 

Setting range: 50 - 86°F (10 – 30°C), 1°F (0.5°C) increments

Note

This parameter cannot be set higher than the set 

value in settings

 Menu 05

 High floor temperature 

limitation.

In this menu a limit on the lowest allowable floor 

temperature is set. This menu is only visible if control 

mode RFT is activated in 

Menu 04

. For systems with a 

Communication Module, this menu only shows the set 

value. Changes are done in the Smatrix Pulse App.

Menu 07: Cooling Allowed

This menu sets whether a room will receive cooling or not. 

This menu is not visible if a Communication Module is 

connected to the system. The setting is then available in 

the Smatrix Pulse App.

Menu 08: Display Units

This menu sets the temperature information in °F or °C.

Menu 09: Relay Module Integration

Use this menu to link a thermostat to a Relay Module for 

controlling a forced-air heating and cooling system or fan 

coil unit.

Menu 11: Room Temperature Calibration

Default: 0.0  

Setting range: -6.0 – 6.0, 0.1 increments
This menu adjusts the temperature in the display if there 

is a difference between the displayed versus the actual 

temperature.

Menu 12: Invert Screen 

This menu inverts the color in the display. The background 

is black, and the numbers and icons are white.

Relative Humidity 

The Digital Thermostat (T-169) also displays the relative 

humidity level in the room or space. Pressing the 

OK

 button 

three (3) times will display the following information:

Reference

Description

A

Relative humidity

B

Relative humidity reading

Table 9-10: Relative humidity displays

Mini Sensor (T-161) Operation

During normal operation, the thermostat settings and 

control is performed via the Uponor Smatrix App (requires 

the Communication Module).

Reference

Description

A

Status LED

B

Registration button

C

Battery CR 

D

2032V terminals for external sensor

Table 9-11: Mini Sensor (T-161) components

Figure 9-7: Relative Humidity

Figure 9-8: Mini Sensor (T-161) operation

Summary of Contents for Smatrix Base PULSE

Page 1: ...Smatrix Pulse Installation and Operation Manual...

Page 2: ...148th Street West Apple Valley MN 55124 USA T 800 321 4739 F 952 891 2008 Uponor Ltd 6510 Kennedy Road Mississauga ON L5T 2X4 CANADA T 888 594 7726 F 800 638 9517 uponor com 2022 Uponor All rights res...

Page 3: ...ter 5 Hardware Installation 15 Installation Procedure 15 A380265C A380265A Controllers 16 A3801263 Expansion Module M 262 17 Communication Module R 208 17 Antenna A 265 18 A3801263 Relay Module M 263...

Page 4: ...without notice Note that Uponor is not liable for installation practices that deviate from this manual or are not acceptable practices within the mechanical trades codes or standards of practices If...

Page 5: ...t connected to or used with non Uponor products parts or components except for those approved or specified by Uponor and Does not show evidence of tampering mishandling insufficient maintenance improp...

Page 6: ...adio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or...

Page 7: ...annot accept any responsibility for damage or breakdown that can result from ignoring these instructions Power Warning The Uponor system uses 115V 60 Hz AC power In case of emergency immediately disco...

Page 8: ...6 l Smatrix Pulse Installation and Operation Manual...

Page 9: ...fferent types of Smatrix Pulse thermostats in the same installation Wireless relays provide installation flexibility when needing to control other heating and cooling devices when running additional w...

Page 10: ...y requires Communication Module Invert display color Communication distances up to 98 ft 30 m away from the controller Included Components Digital Thermostat T 169 Wall bracket Adhesive tape Battery C...

Page 11: ...O mode ECO mode activates in all rooms at once using a dry contact or Smatrix Pulse App requires Communication Module 115V plug in power cord 42 Options App connectivity via Communication Module remot...

Page 12: ...om the controller when used as a sub Controller 115V plug in power cord 42 Options Increase Controller functionality by adding an Expansion Module that adds six 6 additional thermostats and six 6 addi...

Page 13: ...tes the actual energy need of single rooms or zones and adapts the output power of each loop to its length This means a short loop might get 20 on time while a long loop might get about 60 The autobal...

Page 14: ...in the floor Air cooling delivered via conventional air conditioning or fan coil units connected to a relay module registered to a room thermostat Note If selecting air cooling as the primary method t...

Page 15: ...e optional When using the relay module to control a pump the mode of the pump control is set through in the Smatrix Pulse App Caution Changing operation of the pump control and or cooling allowed in t...

Page 16: ...14 l Smatrix Pulse Installation and Operation Manual...

Page 17: ...for Installation Verify the contents of the package with the packing list Check whether an external temperature sensor e g floor sensor is to be installed with a thermostat Review the wiring diagram...

Page 18: ...mal operation The timer is reset when a button has been pressed If programmed schedules exist individual rooms may operate without following a schedule Setting up a system for remote access and connec...

Page 19: ...extend the tab Angle the Expansion Module away from the wall Remove the Expansion Module from the DIN rail Communication Module R 208 The Communication Module contains both an antenna for internal con...

Page 20: ...Install the Antenna outside a manifold cabinet Caution Install the Antenna vertically to ensure the best communication Mounting the Antenna Attach the Antenna to the wall using the adhesive strips inc...

Page 21: ...erence or location for the specific Controller This will help once it is time to begin the registration process of linking the thermostats to the correct devices Note Remove the breakout tab on the th...

Page 22: ...20 l Smatrix Pulse Installation and Operation Manual...

Page 23: ...screwdriver from the quick connector 7 Repeat for the second wire and for the additional actuators General Purpose Input GPI Switch The controller includes a set of terminals that can be used to chan...

Page 24: ...bles 6 1 and 6 2 1 H C Switch and Chiller is only available when cooling is activated 2 Function only available when Pump management is set to Individual otherwise Not used is shown in the Smatrix Pul...

Page 25: ...relay closes when ECO mode is activated and open when the system returns to Comfort mode Ventilation The relay is closed when the system is set to ECO The ventilation unit must be setup to lower its...

Page 26: ...3 8 8 9 5 mm Insert the wires into the terminal blocks and tighten Replace the cover Apply 24V power supply to the Relay Module The Relay Module can be wired to a furnace air conditioning system or f...

Page 27: ...push buttons on the connection terminals While pressing the push buttons insert the two wires from the sensor cable non polarized into the connection terminal Powering Up the Thermostats Remove the pl...

Page 28: ...26 l Smatrix Pulse Installation and Operation Manual...

Page 29: ...green to solid red The Controller is in registration mode when the LED for Channel 1 flashes red If a thermostat has already been linked the first channel available will flash red A previously linked...

Page 30: ...into pairing mode or to clear a link or registration to a thermostat 2 This will show the status of the Relay Module based on the various modes of operation During power up this LED will flash red an...

Page 31: ...Controller can only have one Relay Module linked to it to mirror or duplicate the pump and boiler outputs This can be useful in installations when getting wiring back to the mechanical room for a zon...

Page 32: ...em device Channel 01 or register to another Primary Controller To link a sub Controller to a Primary Controller use the following steps Enter the pairing mode on the Primary Controller one connected t...

Page 33: ...ll remove links to all devices in the system Controllers Relay Modules thermostats etc Caution Resetting the Controller removes all registration information and settings Registration of thermostats an...

Page 34: ...at while re inserting the battery Release the button after 10 seconds when the LED begins to flash Finishing the Installation Prior to making the system operational perform a complete review of the in...

Page 35: ...chedules When the system is running in normal mode In Heating mode the actuators are open when room temperatures are lower than the temperatures set on the thermostats In Cooling mode the actuators ar...

Page 36: ...Green Red Selector is pointed at a channel that is already registered to a thermostat Table 9 1 Controller LED mode of operation Communication Module Like the Controller s the Communication Module inc...

Page 37: ...tting Table 9 4 Digital Thermostat T 169 button functions Display Mode Figure 9 5 shows the different symbol and characters that can be displayed when the thermostat is in the run mode Reference Descr...

Page 38: ...rt screen Table 9 8 Digital Thermostat T 169 menu descriptions Menu 02 Heating Cooling Changeover This menu is not visible if the thermostat is registered to a Controller Heating cooling changeover wi...

Page 39: ...ected to the system The setting is then available in the Smatrix Pulse App Menu 08 Display Units This menu sets the temperature information in F or C Menu 09 Relay Module Integration Use this menu to...

Page 40: ...38 l Smatrix Pulse Installation and Operation Manual...

Page 41: ...f technical support calls could have been averted if the updates were accepted and installed This only applies to systems that are connected to the Uponor Cloud have internet access and have an accoun...

Page 42: ...40 l Smatrix Pulse Installation and Operation Manual...

Page 43: ...or PC Router Requirements DHCP IP address assignment is activated in the router Wi Fi protected access is setup as WPA2 Personal or WPA WPA2 Personal Wi Fi connectivity is set at 802 11 b g n 2 4Ghz...

Page 44: ...Fi router E connect using either Wi Fi or Ethernet The sub Controller D communicates via the Primary Controller C Remote Connection outside local Wi Fi network During normal operation outside the loca...

Page 45: ...or the Antenna or if possible move the shielding object The transmitter in the thermostat is faulty Force the thermostat to transmit by changing the temperature setpoint Replace the thermostat Relativ...

Page 46: ...s login and add the new installation Verify the smartphone or tablet is connected to the same network as the Communication Module Verify the network has internet access Communication error connecting...

Page 47: ...ielding radio signals for example a metal door safe Try to find a new position for the thermostat and or the Antenna or if possible move the shielding object Low radio signal detected sporadic communi...

Page 48: ...LED is fixed green Make sure the Communication Module is connected to an internet connected router via either Wi Fi or Ethernet Make sure the Communication Module is connected to the Controller Restar...

Page 49: ...s not correctly positioned Check the placement of the thermostat so the signal is not shielded by another object The Antenna is not correctly installed or positioned Check the wiring and Antenna conne...

Page 50: ...rong room The room is too cold or too warm in cooling mode Thermostat setpoint is too low Change the temperature setpoint Use maximum and minimum settings in the Smatrix Pulse App to protect the syste...

Page 51: ...the supply line or a malfunctioning circulation pump Contact the installer if the problem persists Loop is warm even after an extended period without heat call The actuator s are not closing Contact...

Page 52: ...lations in building shield radio signals for example a metal door safe Try to find a new position for the thermostat and or the Antenna or if possible move the shielding object The transmitter is work...

Page 53: ...e tests EN 60730 1 and EN 60730 2 9 EMC electromagnetic compatibility requirements tests EN 60730 1 and EN 301 489 3 ERM electromagnetic compatibility and radio spectrum matters tests EN 300 220 3 Pow...

Page 54: ...ly 24VAC 10 15 50 Hz or 60 Hz Pollution degree 2 Software class A Operating temperature 32 F to 122 F 0 C to 50 C Storage temperature 4 F to 158 F 20 C to 70 C Radio frequency 912 0 MHz Transmitter du...

Page 55: ...lity to active parts of the product and degree of water Maximum ambient RH relative humidity 85 at 68 F 20 C Low voltage tests EN 60730 1 and EN 60730 2 9 EMC electromagnetic compatibility requirement...

Page 56: ...A A Operating temperature 0 C to 45 C 32 F to 113 F 0 C to 45 C Storage temperature 20 C to 70 C 4 F to 158 F 20 C to 70 C Maximum consumption 45 W Pump and boiler relay outputs 24 VAC 10 15 8 A maxi...

Page 57: ...from Controller to actuator 65 20 m 18 24 AWG External sensor cable to thermostat 16 4 5 m 18 24 AWG Floor sensor cable to thermostat 16 4 5 m 18 24 AWG Outdoor sensor cable to thermostat 16 4 5 m 18...

Page 58: ...56 l Smatrix Pulse Installation and Operation Manual Digital Thermostat T 169 Mini Sensor T 161 Figure 13 3 Digital Thermostat T 169 Figure 13 4 Mini Sensor T 161...

Page 59: ...6 40 4 26 099 45 7 22 763 50 10 19 900 55 13 17 436 60 16 15 311 65 18 13 474 70 21 11 883 75 24 10 501 80 27 9 299 85 29 8 250 Temperature Resistance F C 90 32 7 334 95 35 6 532 100 36 5 828 105 41 5...

Page 60: ...Notes 58 l Smatrix Pulse Installation and Operation Manual...

Page 61: ...Notes uponor com l 59...

Page 62: ...t 2022 Uponor Printed in the United States Uponor Inc 5925 148th Street West Apple Valley MN 55124 USA T 800 321 4739 F 952 891 2008 uponor com Uponor Ltd 6510 Kennedy Road Mississauga ON L5T 2X4 CANA...

Reviews: