Chapter 8:
Clearing Setup Information or Resetting Devices
It may be necessary during the installation process to
clear portions of the setup and start over. The following
section will take the user through the steps needed
change the setup or restore the individual parts back to
their original factory settings.
Controller
Note
When removing the link between devices
(e.g., thermostats and Relay Module), Uponor
recommends performing the unpairing process
on both pieces of hardware.
Refer to the two options below to remove setup
parameters on Controllers that were done incorrectly.
Unpairing a Channel
Use this process when a channel is incorrectly assigned to
a thermostat.
• Enter the registration mode by pressing the
OK
button on
the Controller for three (3) seconds. The first unassigned
channel will begin to flash red.
• LEDs that are solid green are available to be unassigned.
• Using the
<
or
>
buttons, move the flashing red LED to
the channel you wish to remove. The LED will alternate
between green and red.
• Press and hold the
<
and
>
buttons for five (5) seconds.
• When the channel is unregistered, the LED will flash red.
• Press and hold the
OK
button on the Controller until the
LEDs turn off. The Controller has returned to normal run
mode.
• If unpairing a thermostat, Uponor recommends resetting
this device as well.
Clearing All Setup Information
Refer to this procedure to clear all setup information and
return the Controller to its factory, or default, state. This will
remove links to all devices in the system: Controllers, Relay
Modules, thermostats, etc.
Caution!
Resetting the Controller removes all registration
information and settings. Registration of
thermostats and system devices are once again
required.
Caution!
If resetting a sub-Controller, all remaining sub-
Controllers must be unregistered from the Primary
Controller (system device Channel 1). Register
the remaining sub-Controllers to the Primary
Controller again when finished.
• Make sure the Controller is in run mode (green LED in
upper-right hand corner of the Controller).
• Press and hold the
<
,
OK
, and
>
buttons for approximately
10 seconds until the power LED flashes and all channel
LEDs turn off.
• All parameters and settings are erased, and the
Controller will return to run mode.
Removing a Paired Relay Module
• Press and hold the
OK
button on the Controller until the
LED for the first available channel begins to flash red to
enter the pairing mode on the Controller and the power
LED will change from green (normal operation) to red
(linking mode).
• Using the
<
or
>
buttons, move the flashing LED from the
channels to the power LED on the Controller, and it will
begin to flash red.
• Press the
OK
button.
• If done correctly, the LED for Channel 1 will begin to flash
red and the power LED will start flashing in a pattern
(long flash, short flash, long flash, etc.).
• Press the
>
button to move to Channel 2 and this LED will
begin to flash green.
• Press and hold the
<
,
OK
, and
>
buttons for approximately
10 seconds until the power LED flashes and Channel 2 LED
will turn off.
• Press and hold the
OK
button on the Controller until the
power LED returns to green. The controller has returned to
normal run mode.
Summary of Contents for Smatrix Base PULSE
Page 1: ...Smatrix Pulse Installation and Operation Manual...
Page 8: ...6 l Smatrix Pulse Installation and Operation Manual...
Page 16: ...14 l Smatrix Pulse Installation and Operation Manual...
Page 22: ...20 l Smatrix Pulse Installation and Operation Manual...
Page 28: ...26 l Smatrix Pulse Installation and Operation Manual...
Page 40: ...38 l Smatrix Pulse Installation and Operation Manual...
Page 42: ...40 l Smatrix Pulse Installation and Operation Manual...
Page 60: ...Notes 58 l Smatrix Pulse Installation and Operation Manual...
Page 61: ...Notes uponor com l 59...