KEY FEATURES
A. FULL DATA Reporting.
Compatible with most alarm panels using Contact ID (SIA
DC-05 Standard), SIA FSK Level 1 (SIA DC-03 Standard), Pulse 4+2, DMP or
Modem IIe/IIIa/IIIa
2
digital dialer formats. All information sent by the alarm panel
in these formats (account number, zone information, user IDs, etc.) will be sent to
the central station using the telephone line or the GSM network.
B. Telephone Line Supervision.
Features a built-in telephone line monitoring circuit
designed to detect voltage (in the On-Hook state) or voltage and current (in the
Off-Hook state). If insufficient voltage or current is detected, a relay is activated
causing the unit to “intercept” (or “capture”) the alarm panel’s digital dialer output
and substitute the GSM cellular network for the Public Switched Telephone
Network as the communications path for sending event information.
C. Panel to 4550-CB Cable Supervision.
Monitors continuity of the cable connecting
the panel’s telephone dialer to the 4550-CB. This feature is activated through the
web site
www.uplink.com
or by calling Uplink Customer Service at
1-888-9-UPLINK
(1-888-987-5465).
D. Zone Inputs.
Reports programmed events to the central station.
Note: One suggested use for this feature is to allow a summary alarm output from
the alarm panel to be connected to one of the inputs and report a summary alarm
event to the central station. This prevents circumventing the TELCO supervision
circuit, assuming that a compromised PSTN line is operational. This is a unique
feature not found in many other dialer capture products on the market today.
(KEY FEATURES continued next page)
4