4G CELLULAR
ALARM COMMUNICATOR
UL COMPLIANCE SECTION –
INSTALLATION REQUIREMENTS
For installations that are intended to meet UL certification requirements, the
following items must be adhered to during the installation for each stated
certificate category. The Installation and Wiring requirements are in accordance
with the National Electrical Code, NFPA/70.
The 4550-CB has been tested for compliance by UL in an installation where
the POTS line is the primary communication path and the Cellular channel is
secondary.
Commercial Burglary (UL 1610 - Category AMCX, UL 365 – Category APAW)
1. For a UL Certificated Installation, the 4550-CB must be connected to a Listed
panel, sch as a DSC PC1616 panel and a Listed DACR, such as the DSC,
Model SG-System III and configured to communicate via Contact ID protocol.
2. Installation of the UL Listed alarm panel must be in accordance with the
manufacturer’s written UL Compliance rules for the type of UL certificate to
be achieved. This applies to both the physical installation requirements and
the unit’s programming requirements.
3. Power to the 4550-CB must be supplied from an Elk TRG1640 16.5VAC –
45VA UL Listed wall transformer. This transformer must be secured to the
AC outlet with the security screw. The wire rating of this connection must
exceed 16.5VAC. The transformer must be plugged into an un-switched AC
outlet. This Elk transformer is available by calling Uplink Customer Service
at 1-888-9-UPLINK (1-888-987-5465) or by contacting your local UPLINK
distributor.
4. Use a UL-Listed 12VDC 5.0 Ampere hour rated sealed lead-acid rechargeable
battery with the Model 4550-CB unit. (Recommended Battery: Powersonic PS-
1250-F1 or equivalent)
(UL COMPLIANCE SECTION continued next page)