Uplink 202132UP455012 Installation & User Manual Download Page 34

33

®

4550-CB

UL COMPLIANCE SECTION –   

INSTALLATION REQUIREMENTS 

(cont.)

  5.  The Model 4550-CB unit must be located within the same room as the alarm 

panel and a maximum of 20 feet of the alarm panel. The 4550-CB must be 
installed at the protected premises. 

  6.  The wiring between the Model 4550-CB unit and the alarm panel must be in 

conduit.

  7.  All power-limited wiring must be secured a minimum of 1/4 inch away from all 

non-power-limited high voltage wiring, and all non-power-limited high voltage 
wiring must be routed through a different conduit than any of the power-limited 
wiring or cable. The only non-power limited wiring is between a battery and 
the 4550-CB DC terminals.

  8.  Both the alarm panel’s DACT and the Model 4550-CB unit must be used for 

alarm communications to the central monitoring station’s UL Listed digital 
alarm receiver.

  9.  The telephone line connected to the RJ31X jack cannot be connected to a 

PBX system.

10.  The Model 4550-CB unit must be programmed to send a Test signal to the 

central station a minimum of once every 24 hours.

11.  The following troubles are to be programmed to output #1 or output #3 – 

Loss of AC, low battery, telco loss, Cellular loss, and catastrophic failure 
simultaneously. In addition, outputs 1 and 3 shall be connected to a reporting 
zone on the alarm panel, and the zone must be set up as closed in the normal 
state and open in the off-normal state. Activation of this zone must annunciate 
locally at the keypad which shall be programmed to display the message “For 
trouble see panel” or similar. 

                                      (UL COMPLIANCE SECTION continued next page)

Summary of Contents for 202132UP455012

Page 1: ...INSTALLATION USER S GUIDE PRODUCT ID 202132UP455012 4G CELLULAR ALARM COMMUNICATOR WIRELESS COMMERCIAL SECURITY APPLICATIONS PRIMARY OR BACKUP COMMUNICATIONS 4550 CB...

Page 2: ...or information storage and retrieval systems The material in this manual is subject to change without notice Uplink reserves the right to make changes to any software or product to improve reliabilit...

Page 3: ...15 32 A General Considerations 15 B DIP Switch Settings 15 C LEDs 16 18 D Locating and Installing the 4550 CB 19 22 E Connecting the 4550 CB to the Alarm Panel Telephone Jack 23 25 F Activating the 4...

Page 4: ...nt the 4550 CB will intercept the alarm panel s digital dialer output when the panel has an event to report and communicate with the panel as if it were a central station alarm receiver Once the 4550...

Page 5: ...er output and substitute the GSM cellular network for the Public Switched Telephone Network as the communications path for sending event information C Panel to 4550 CB Cable Supervision Monitors conti...

Page 6: ...y Restoral at 11 4 VDC It can also be programmed to report Loss of AC power to the central station This occurs at 102 VAC and restores at 107 VAC G Automated Testing Sends an automated test signal to...

Page 7: ...ent transmissions c initiation of a test report d the ability to query the unit and receive a real time radio report status including a Received Signal Strength reading e programming inputs and other...

Page 8: ...because of a defect in materials or workmanship within the 12 month warranty period Uplink will at its sole option and at no charge repair or replace it or arrange for its repair or replacement Uplin...

Page 9: ...THE FORESEEABILITY OF SUCH DAMAGES NEITHER UPLINK NOR ITS SERVICE PROVIDERS SHALL BE LIABLE FOR ANY CLAIM RESULTING FROM OR RELATING TO A THIRD PARTY CRIMINAL ACTIVITY OR FRAUD B ACTS OR OMISSIONS OF...

Page 10: ...LITY WAIVER cont MORE RELATED OR UNRELATED CLAIMS EXCEED AN AMOUNT EQUAL TO THE AGGREGATE AMOUNT PAID BY THE CLAIMANT FOR UPLINK SERVICE DURING THE 12 MONTH PERIOD PRECEDING THE DATE OF THE EARLIEST E...

Page 11: ...uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that...

Page 12: ...number of devices that may be connected to a telephone line Excessive RENs on a telephone line may result in the devices not ringing in response to an incoming call In most but not all areas the sum o...

Page 13: ...network the telephone company may request that you disconnect the equipment until the problem is resolved The 4550 CB is not designed to be repaired in the field by an Installer Repairs to this unit...

Page 14: ...d international standards bodies The design of this module complies with the FCC guidelines and these international standards The FCC ID of this unit is TWV192513384X For more information about RF exp...

Page 15: ...echnical support please ensure to have read the installation guide completely Technical support requires the caller to provide Login name Password Serial number of the 4550 CB UPLINK Technical Support...

Page 16: ...d Proximity to the RJ31X Telco jack from the telephone system B DIP Switch Settings The 4550 CB has a four position dipswitch The dipswitches function as follows SWITCH NO SETTING FUNCTION S1 Default...

Page 17: ...on for approximately 1 minute Then power must be removed and S1 restored to its OFF position All website configurations will be erased by using S1 C LEDs Normal Mode Upon initial power up the 5 LEDs...

Page 18: ...on Line is off hook RED On Phone line Trouble Condition Trouble LED 3 GREEN On All 3 Output Relays Normal RED On One or more Output Relay Off Normal GSM Comm LED 4 GREEN On Unit registered on the netw...

Page 19: ...solid 4 green solid 5 green solid 60 dBm lllll 1 off 2 green solid 3 green solid 4 green solid 5 green solid 70 dBm lllll 1 off 2 off 3 green solid 4 green solid 5 green solid 80 dBm lllll 1 off 2 of...

Page 20: ...re as a template to mark where to drill holes for the screws and anchors that will hold the enclosure in place on the wall 2 Connect the supplied antenna with the 4550 CB The Antenna supplied may diff...

Page 21: ...le To RJ31X House Phone Line To Alarm Panel To AC Transformer To Battery Note All Circuits are power limited except for battery connections A inch spacing is required between power limited circuits an...

Page 22: ...n Figure 2 5 Place the backup battery into its location in the bottom of the enclosure Secure the battery in place using the metal battery bracket and nuts provided 6 Connect the positive and negative...

Page 23: ...e that the RSSI is still showing a good signal strength level 9 Connect the unit s tamper switches For a single tamper switch connect the switch plug to the top of the left most column of JP13 For a d...

Page 24: ...le On the 4550 CB s side the cable should use an RJ45 plug and be connected into Jack JP3 the Jack closer to the Terminal Strip 3 Inputs The 4550 CB has two EOLR supervised inputs that report to the c...

Page 25: ...tputs that can be used to activate inputs on the alarm panel or for other local purposes Decide on how to use these outputs then wire them to terminal strip JP10 as follows Output 1 Out 1 and Out 1 Ou...

Page 26: ...NG REQUIREMENTS AND INSTALLATION NOTES ALARM PANEL TO RJ31X Orange Wire 2 Blue Wire 7 Note To supervise the Telco cable connection to the Model 4550 CB unit short wires 2 and 7 together Model 4550 CB...

Page 27: ...at 1 888 987 5465 Click OK e A confirmation box will appear saying Congratulations your new Uplink Account was successfully created Press OK f Select the UPLINK DEALERS new existing dealer button at t...

Page 28: ...on I have read and I accept the terms of the Activation Agreement d Enter the device serial number and select Activate e Enter all appropriate customer information f From the Central Station Notificat...

Page 29: ...arm states e What event codes should be sent for Low Battery and Low Battery Restoral f Whether alarm events should also be sent to an email account and the email account s address The following param...

Page 30: ...ealer Web Site as Normally Open Normally Closed and whether the unit will send Alarms and Troubles or Alarms only 6 Definition of Output Relay Default 1 Loss of Cellular Service 2 Central Station ACK...

Page 31: ...H Default Event Email Messages Email and Text Messaging will only be available for Status events e g Low Battery Test etc and state transitions on the 2 Inputs of the 4550 CB INSTALLATION continued ne...

Page 32: ...ive c With the Telco Line still disconnected trip an alarm on the alarm panel Check that the 4550 CB has correctly intercepted the panel s digital dialer output and reported the event to the central m...

Page 33: ...red to communicate via Contact ID protocol 2 Installation of the UL Listed alarm panel must be in accordance with the manufacturer s written UL Compliance rules for the type of UL certificate to be ac...

Page 34: ...m panel s DACT and the Model 4550 CB unit must be used for alarm communications to the central monitoring station s UL Listed digital alarm receiver 9 The telephone line connected to the RJ31X jack ca...

Page 35: ...n to the requirements for additional backup battery power i e 80 hours and shock or vibration sensors In this application the required backup battery is a UL Listed 12VDC 12 0 AH battery Recommended B...

Page 36: ...no more than 10 attempts 20 Low battery trouble shall be annunciated at the central station 21 The status of each device must be checked every 90 seconds or less 22 Refer to LED Table and wiring diag...

Page 37: ...d non power limited circuits and all non power limited high voltage wiring must be secured a minimum of 1 4 inch away from all power limited wiring 27 The 4550 CB has two EOLR supervised inputs that r...

Page 38: ...Ringer Equivalence 0 3 REN Mode Loop start 26 mA typical Phone Line Monitor On Hook voltage 8 50 VDC Off Hook current 10 0 mA Power 400 mW AC Transformer 16 5 V 45VA AC Supply 120VAC 60Hz 430mA Norma...

Page 39: ...Ripple 20mV Radio Frequencies 850 1900 MHz Avg Current 290 mA Peak Current 2A DC Voltage 3 3 4 2 V D C Sensitivity 109 dB typical Environmental Temperature Range 0 to 49 C Humidity 0 to 85 non conden...

Page 40: ...49 Zs 000 Alarm generic E140 UA 10 Za BL Burglary Alarm E130 BA 10 Za BU Burglary Restoral R130 BR 12 Zr BU Burglary Tamper E137 TA 10 Zs 011 Burglary Tamper Restoral R137 TR 12 Zs 003 Closing R400 CL...

Page 41: ...Zr A1 Medical Alarm E100 MA 10 Za EM Medical Restoral R100 MR 12 Zr EM Opening E400 OP 2F Zq OP Panic Alarm E120 PA 10 Za PN Panic Restoral R120 PR 12 Zr PN Phone Fail E350 LT 44 Zs 028 Phone Restora...

Page 42: ...T DESCRIPTION CONTACT ID EVENT CODE SIA DC 03 EVENT CODE MODEM lle llla lllla2 DMP EVENT CODE Test E602 TX 33 Zs 007 Trouble generic E300 UT 11 Zt BL Trouble Restoral generic R300 UR 12 Zr BL Trouble...

Page 43: ...DC 03 EVENT CODE MODEM lle llla llla2 ZONE NO REPORTED AC Loss E301 AT 48 239 AC Restoral R301 AR 49 239 Low Battery E302 YT 4B 240 Low Battery Restoral R302 YR 4C 240 Telco Trouble E351 LT 44 241 Te...

Page 44: ...EVENT CODE SIA DC 03 EVENT CODE MODEM lle llla llla2 ZONE NO REPORTED Watchdog Circuit Trouble E616 YX 11 246 Watchdog Circuit Restoral R616 YZ 12 246 Input 1 Alarm E140 UA 10 247 Input 1 Normal R140...

Page 45: ...OMMUNICATOR INSTALLATION OPERATION AND PROGRAMMING GUIDE 2013 Uplink Security LLC All rights reserved Uplink is a trademark of Uplink Security LLC GUIDE 00 25580 876 REV A 3330 CUMBERLAND BLVD SUITE 7...

Page 46: ...1 FOR SALES PRODUCT INFORMATION Uplink 3330 Cumberland Blvd Suite 700 Atlanta GA 30339 1 888 9 UPLINK sales uplink com www uplink com FOR TECHNICAL SUPPORT Please visit our website at www uplink com...

Reviews: