NEVER use an open flame of any kind to test this smoke alarm. You might accidentally damage
or set fire to the smoke alarm or to your home. The built-in test switch accurately tests the
smoke alarm's operation as required by Underwriters Laboratories Inc. (UL).
(UTHA) Sensitivity Indicating Means

The sensitivity indicating means for this Smoke and Fire Alarm is the use of the analyzer for Smoke
Detectors Model 501-A or 501-A/Bat Aerosol Generator Manufactured by Gemini Scientific Corp.,
1122-B Aster Ave., Sunnyvale, CA 94086.
The Equivalent UL 268 Light obscuration %/Ft as measured by this instrument must be within the
obscuration listed on the back of this alarm.

(UTHA) Go/No-Go Field Test

The Go/No-Go test for this smoke and fire alarm is to use one of the following UL listed can-type aerosol
smoke alarm testers. The instructions for use are printed on the canister. Home Safeguard, Model 25S.

If you choose to use an aerosol smoke product to test the smoke alarm, be certain to use one
that has been Listed to Underwriters Laboratories, Inc. Safety Standards and use it only as
directed. Use of non-UL Listed products or improper use of UL Listed products may affect
the smoke alarm's sensitivity.
(UTHA) MAINTENANCE:

The alarm is virtually maintenance free. However, under dusty conditions, a vacuum hose may be
used to clear the sensing chamber of dust.

Clean the alarm at least once a month

 to remove dust, dirt, insects or debris. Always turn off power to

alarm before cleaning. Using a soft brush or wand attachment to a vacuum cleaner, vacuum all sides and
cover of the alarm. Be sure all the vents are free of debris.
If the alarm is false alarming and cannot be restored to normal operation, the alarm should be replaced.

WEEKLY TESTING

NEVER use an open flame of any kind to test this unit. You might accidentally damage or set fire
to the alarm or to your home. The built-in test switch accurately tests the unit's operation as
required by the UL 217, UL 2034 and UL 1484 Standards. NEVER use vehicle exhaust! Exhaust
may cause permanent damage and voids your warranty.

DO NOT stand close to the alarm when the horn is sounding. Exposure at close range may be
harmful to your hearing. When testing, step away when the horn starts sounding.

It is important to test this alarm every week to make sure it is working properly.

USING THE TEST FEATURE:

Press and release the TEST button on the alarm cover.

During testing, you will hear: 3 beeps (red LED on), 2 second pause, 3 beeps (red LED on), 6
second pause, 4 beeps (red LED on), 5 second pause, 1 beep (blue LED on).

If the alarm does not sound properly:

1. Make sure the AC power is applied and the battery is fresh and installed correctly.

2. Test the alarm again.

REGULAR MAINTENANCE

CLEANING YOUR ALARM:

Page 12

DO NOT use spray cleaning chemicals or insect sprays directly on or near the alarm. DO NOT paint
over the alarm. Doing so may permanently damage the alarm.
The outside can be wiped with a damp cloth. Do not use any household cleaning agents, ammonia-
based cleaners, paints, varnishes or any other chemical on or near your alarm. 

AFTER CLEANING,

REINSTALL YOUR ALARM. TEST YOUR ALARM BY USING THE TEST BUTTON.

END-OF-SERVICE LIFE NOTIFICATION:

 A majority of home fire deaths are a result of no smoke alarms

or no 

working

 smoke alarms. In addition to the "replace by date" stamped on the back of your alarm, your

alarm contains a unique audible end-of-service life notification feature. When it is time to replace your alarm,
which is after approx. 7 years of operation from initial power up, the alarm will sound 2 chirps approx. every
20 seconds. The green LED stays on. The alarm should be replaced immediately.The  product end-of-
service life notification can be temporarily silenced for a 10 hour period for up to 20 days. After 20 days,
the warning cannot be silenced. The alarm should be replaced immediately.

Summary of Contents for MICN102

Page 1: ...C 60 Hz 100 mAMax SECURITY INSTRUMENTS INC Table of Contents Page Alarm Limitations and Functions 2 What You Should Know About CO 3 What You Should Know About Natural Gas 3 Basic Safety Information 5...

Page 2: ...SIONS ESCAPING GAS IMPROPER STORAGE OF FLAMMABLE MATERIALS OVERLOADED ELECTRICAL CIRCUITS CHILDREN PLAYING WITH MATCHES NATURAL CAUSES SUCH AS LIGHTNING OR ARSON FIRE PREVENTION IS YOUR BEST SAFEGUARD...

Page 3: ...ical problems may consider using warning devices which provide audible and visual warnings for carbon monoxide concentrations under 30 ppm IMPORTANT CONSIDERATIONS YOUR COMBINATION SMOKE CO AND NATURA...

Page 4: ...ceiling shall be located within 36 in 914 mm horizontally of the peak but not closer than 4 in 102 mm vertically to the peak Sloped Ceilings Shed Ceilings Smoke alarms or combination alarms mounted on...

Page 5: ...to detect any other gas Carbon monoxide and natural gas may be present in other areas The Smoke CO and Natural Gas Alarm will only indicate the presence of CO or natural gas which reaches the sensor D...

Page 6: ...nted alarms can occur if an alarm is placed directly next to a fuel burning source Ventilate these areas as much as possible If you must install the alarm near a cooking or heating appliance install a...

Page 7: ...e alarm in the direction indicated by the TWIST TO REMOVE arrow on the side of the alarm base OPTIONAL TAMPER RESISTANT FEATURES There are two separate tamper resistant locking features provided for t...

Page 8: ...sing models within an interconnected system The following alarms cannot reset units on an interconnected system USI 7795 CD 9795 USI 7385 USI 7390 USI 7485 USI 7490 CD 9385 CD 9390 CD 9485 CD 9490 The...

Page 9: ...rm utilizes battery backup power the natural gas sensor will operate the alarm and will sample less frequently to extend battery life Natural gas could be present during this period between samples wi...

Page 10: ...ach alarm event TESTING Test by pushing the Test button on the alarm cover until the alarm sounds then release The alarm will sound 3 beeps approx 2 second pause 3 beeps approx 6 second pause 4 beeps...

Page 11: ...etected If CO levels drop below alarm levels the alarm will remain silent and return to normal operation If CO levels remain constant or increase this indicates a potentially dangerous situation and t...

Page 12: ...y damage or set fire to the alarm or to your home The built in test switch accurately tests the unit s operation as required by the UL 217 UL 2034 and UL 1484 Standards NEVER use vehicle exhaust Exhau...

Page 13: ...self diagnostic test reveals a malfunction immediately have the unit replaced see last page for warranty information Smoke CO and Natural Gas alarms can only sense CO which reaches the alarm s sensor...

Page 14: ...nsumer is exempt from any licensing or requirements Simultaneous operation of several fuel burning appliances competing for limited internal air Vent pipe connections vibrating loose from clothes drye...

Page 15: ...sleeping area within 6 4 m 21 ft of any door to a sleeping room the distance measured along a path of travel 3 On every level of a dwelling unit including basements 4 On every level of a residential...

Page 16: ...ff Blinks On in sync with the 1 beep Condition Originating GAS Alarm Recommendation If hazard is identified take all precautions if an alarm sounds by calling an Emergency Service and getting out of t...

Page 17: ...enced for a 10 hour period for up to 20 days After 20 days the warning cannot be silenced The alarm should be replaced immediately Silent alarmed previously Off and Blinks On approx every 5 seconds un...

Page 18: ...ECIFICALLY DISCLAIMS ANY WARRANTY WHETHER EXPRESS OR IMPLIED OF FITNESS FOR A PARTICULAR PURPOSE OTHER THAN THE WARRANTY CONTAINED HEREIN NO IMPLIED WARRANTY ON THIS PRODUCT CREATED BY STATE LAW SHALL...

Reviews: