Installation Guide 

10/06

Unitronics  

Mounting 

Dimensions

Panel mounting

Before you begin, note that the 
mounting panel cannot be more 
than 5 mm thick. 

1. Make 

panel 

cut-out 

measuring 92 x 92 mm 
(3.622” x 3.622”). 

 
2.  Slide the controller into the 

cut-out, ensuring that the 
rubber seal is in place. 

 
3.  Push the 2 mounting brackets 

into their slots on the sides of 
the controller as shown in the 
figure to the right. 

 
4. Tighten 

the 

bracket 

screws 

against the panel. Hold the 
bracket securely against the 
unit while tightening the 
screw. 

 
5. When 

properly 

mounted, 

the 

controller is squarely situated 
in the panel cut-out as shown 
in the figure to the right. 

Summary of Contents for Vision120

Page 1: ...high speed and analog I Os I O Expansion Modules Via I O expansion port adapter connect up to 128 additional I Os per controller Programming Write both the HMI and Ladder control application using VisiLogic freeware The Vision120 User Guide and the product s technical specification sheet contain additional information These documents are located on the Unitronics Setup CD They may also be download...

Page 2: ...alified service personnel should open this device or carry out repairs Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters that exceed permissible levels To avoid damaging the system do not connect disconnect the device when power is on Environmental Considerations Do not install in areas with excessive o...

Page 3: ...e controller into the cut out ensuring that the rubber seal is in place 3 Push the 2 mounting brackets into their slots on the sides of the controller as shown in the figure to the right 4 Tighten the bracket screws against the panel Hold the bracket securely against the unit while tightening the screw 5 When properly mounted the controller is squarely situated in the panel cut out as shown in the...

Page 4: ...ules Wiring General Do not touch live wires Unused pins should not be connected Ignoring this directive may damage the device Caution To avoid damaging the wire do not exceed a maximum torque of 0 5 N m 5 kgf cm Do not use tin solder or any substance on stripped wire that might cause the wire strand to break Use crimp terminals for wiring use 26 14 AWG wire 0 13 mm 2 2 08 mm2 1 Strip the wire to a...

Page 5: ...2 or RS485 Certain models also comprise CANbus ports Check your controller s technical specifications Turn off power before making communications connections Caution Signals are related to the controller s 0V the same 0V is used by the power supply Always use the appropriate port adapters Serial Communications The serial ports are type RJ 11 and may be set to either RS232 or RS485 via jumper as de...

Page 6: ...nd wiring Before performing these actions touch a grounded object to discharge any electrostatic charge Avoid touching the PCB board directly Hold the PCB board by its connectors 1 Turn power off before opening the controller 2 Locate the 4 slots on the sides of the controller 3 Using the blade of a flat bladed screwdriver gently pry off the back of the controller 4 Gently remove the top PCB board...

Page 7: ...oard into place doing so may damage the controller 7 Close the controller by snapping the plastic cover back in its place If the card is placed correctly the cover will snap on easily RS232 RS485 Jumper Settings Jumper Settings RS485 Termination Jumper RS232 RS485 Jumper ON OFF 1 A B 3 A B COM 1 2 A B 4 A B 5 A B 7 A B COM 2 6 A B 8 A B Default factory setting ...

Page 8: ...ll applicable laws at any time at its sole discretion and without notice to discontinue or change the features designs materials and other specifications of its products and to either permanently or temporarily withdraw any of the forgoing from the market All information in this document is provided as is without warranty of any kind either expressed or implied including but not limited to any imp...