Vision™ OPLC™ V570-57-C30B, V570-57-T40B
Installation Guide
CANbus
These controllers comprise a CANbus port. Use
this to create a decentralized control network
using one of the following CAN protocols:
CANopen: 127 controllers or external
devices
Unitronics’ proprietary UniCAN: 60
controllers, (512 data bytes per scan)
The CANbus port is galvanically isolated.
CANbus Wiring
Use twisted-pair cable. DeviceNet® thick
shielded twisted pair cable is recommended.
Network terminators: These are supplied with the
controller. Place terminators at each end of the
CANbus network.
Resistance must be set to 1%, 121
S
, 1/4W.
Connect ground signal to the earth at only one
point, near the power supply.
The network power supply need not be at the
end of the network
CANbus Connector
121
terminating
resistor
121
terminating
resistor
Circuit
protection
device
+
-
24V Power
Supply
-V
L
H
+V
PE
-V
L
H
+V
PE
-V
L
H
+V
PE