background image

Vision™ OPLC™ V570-57-C30B, V570-57-T40B 

Installation Guide

6

Unitronics 

Communication Ports 

This series comprises 2 RS232/RS485 serial ports and a CANbus port.  

Turn off power before making communications connections. 

Caution

 

Always use the appropriate port adapters. 

Serial Communications

The serial ports are type RJ-11 and may be set to 

either

RS232 or RS485 via DIP switches, in 

accordance with the table shown on page 6.  
Use RS232 to download programs from a PC, and to communicate with serial devices and 
applications, such as SCADA.   
Use RS485 to create a multi-drop network containing up to 32 devices. 

Pinouts 

The pinouts below show the signals between the adapter and port. 
To connect a PC to a port that is set to RS485, remove the RS485 connector, and connect the PC 
to the PLC via the programming cable. Note that this is possible only if flow control signals are not 
used (which is the standard case). 

RS232  

RS485** 

Controller 

Port 

Pin # 

Description 

 

Pin # 

Description 

1* DTR 

signal 

 

1

A signal (+) 

2

0V reference 

 

2

(RS232 signal) 

3

TXD signal 

 

3

(RS232 signal) 

4

RXD signal 

 

4

(RS232 signal) 

5

0V reference 

 

5

(RS232 signal) 

6* DSR 

signal 

 

6

B signal (-) 

 

Pin #1

*Standard programming cables do not provide connection points for pins 1 and 6. 
**When a port is adapted to RS485, Pin 1 (DTR) is used for signal A,  
  and Pin 6 (DSR) signal is used for signal B. 

RS232 to RS485: Changing DIP Switch Settings

The ports are set to RS232 by factory default. 
To change the settings, first remove the Snap-in I/O Module, if one is installed, and then set the 
switches according to the following table. 

 

RS232/RS485: DIP Switch Settings

The settings below are for each COM port. 

 Switch 

Settings 

1

2

3

4

5

6

RS232* ON 

ON 

ON 

OFF 

ON 

OFF 

RS485 

OFF OFF OFF 

ON 

OFF 

ON 

RS485 with 
termination** 

ON ON 

OFF 

ON 

OFF 

ON 

*Default factory setting

 

**Causes the unit to function as an end unit in an RS485 network

 

Summary of Contents for Vision OPLC V570-57-C30B

Page 1: ... Via adaptor local or remote I Os may be added via expansion port or CANbus Installation instructions and other data may be found in the module s technical specification sheet Information Mode This mode enables you to Calibrate the touchscreen View Edit operand values COM port settings RTC and screen contrast brightness settings Stop initialize and reset the PLC To enter Information Mode press the...

Page 2: ...physical and property damage Warning The identified danger could cause physical and property damage Caution Caution Use caution Before using this product the user must read and understand this document All examples and diagrams are intended to aid understanding and do not guarantee operation Unitronics accepts no responsibility for actual use of this product based on these examples Please dispose ...

Page 3: ...he battery The battery is supplied taped to the battery cover on the rear of the controller 1 Remove the battery cover shown on page 6 The polarity is marked on the battery holder and on the battery 2 Insert the battery ensuring that the polarity symbol on the battery is facing up aligned with the symbol on the holder 3 Replace the battery cover Dimensions ...

Page 4: ...Cut out Dimensions 2 Slide the controller into the cut out ensuring that the rubber seal is in place 3 Push the 4 mounting brackets into their slots on the sides of the controller as shown in the figure to the right 4 Tighten the bracket screws against the panel Hold the bracket securely against the unit while tightening the screw 5 When properly mounted the controller is squarely situated in the ...

Page 5: ...he permissible input voltage range is 20 4 28 8VDC with less than 10 ripple A non isolated power supply can be used if a 0V signal is connected to the chassis You must use an external circuit protection device Install an external circuit breaker Guard against short circuiting in external wiring Double check all wiring before turning on the power supply Do not connect either the Neutral or Line sig...

Page 6: ...this is possible only if flow control signals are not used which is the standard case RS232 RS485 Controller Port Pin Description Pin Description 1 DTR signal 1 A signal 2 0V reference 2 RS232 signal 3 TXD signal 3 RS232 signal 4 RXD signal 4 RS232 signal 5 0V reference 5 RS232 signal 6 DSR signal 6 B signal Pin 1 Standard programming cables do not provide connection points for pins 1 and 6 When a...

Page 7: ...n to open the locking mechanism 3 Gently rock the module from side to side easing the module from the controller Re installing a Snap in I O Module 1 Line the circular guidelines on the controller up with the guidelines on the Snap in I O Module as shown below 2 Apply even pressure on all 4 corners until you hear a distinct click The module is now installed Check that all sides and corners are cor...

Page 8: ...nnect ground signal to the earth at only one point near the power supply The network power supply need not be at the end of the network CANbus Connector 121 terminating resistor 121 terminating resistor Circuit protection device 24V Power Supply V L H V PE V L H V PE V L H V PE Samara tel 7 846 273 95 85 samara klinkmann spb ru Yekaterinburg tel 7 343 287 19 19 yekaterinburg klinkmann spb ru St Pe...

Reviews: