Local Expansion Adapter Kits Installation Guide
6
Unitronics
UAG-XKxxx, UAG-XKPxxx and UAG-XKPLxxxx
1. Hold the Base Unit as shown in the accompanying
figure, and plug it into the last device installed on
the back of the HMI panel.
Verify first that its Bus Connector is not covered.
2. Click the top and bottom clips into the Guide
Tunnel of the last device.
Connecting the Adapter’s Base Unit: UniStream PLC
UAG-XKxxx, UAG-XKPxxx and UAG-XKPLxxxx
1. Hold the Base Unit as shown in the accompanying
figure, and plug it into the Bus Connector on the
right side of the UniStream PLC.
Verify first that the connection point is not covered.
2. Click the top and bottom clips down onto the PLC.
Connecting the Adapter’s Base Unit: UniStream Built-in
UAG-CX-XKPxxx, UAG-CX-XKPLxxxx and UAG-CX-XKPxxx,
UAG-CX-XKPLxxxxx
1. Hold the Base Unit as shown in the accompanying
figure, and plug it into the I/O Expansion Jack in the
rear of the device.
Connecting the Adapter End Unit
1. Push the End Unit onto the DIN-rail until the clips located at the top and bottom of the
unit have snapped onto the DIN-rail.
2. Install Uni-I/O™ modules to the right of the End unit. Please refer to the specific
Installation Guide of each Uni-I/O™ module.
3. Slide the Bus Connector Lock of the first module all the way to the left.
Connecting the Cable
Short-range kit
: Link the adapter’s units by
plugging the RJ45 of the End Unit’s cable into the
port at the bottom of the Base Unit.
Long-range kit
: Connect both sides of the blue
cable to the RJ45 ports of the adapter’s Base and
End units. Please refer to the Long Range
Adapter Assembly Diagram, page 5 .
Connecting the Power Supply and Earth
If you are using a UAG-XKxxx, only earth it.
All other models: connect it to a power source
as
described on page 8.
Do not connect the cable to any device other than the Base Unit.
Do not connect the Base Unit’s cable port to any other cable or device.