Unitronics UniStream UAG-XK Series Installation Manual Download Page 6

Local Expansion Adapter Kits Installation Guide  

 

 

Unitronics 

 

UAG-XKxxx, UAG-XKPxxx and UAG-XKPLxxxx 

1.  Hold the Base Unit as shown in the accompanying 

figure, and plug it into the last device installed on 

the back of the HMI panel. 

Verify first that its Bus Connector is not covered. 

 

2.  Click the top and bottom clips into the Guide 

Tunnel of the last device.  

  

Connecting the Adapter’s Base Unit: UniStream PLC 

 

UAG-XKxxx, UAG-XKPxxx and UAG-XKPLxxxx 

1.  Hold the Base Unit as shown in the accompanying 

figure, and plug it into the Bus Connector on the 
right side of the UniStream PLC. 

Verify first that the connection point is not covered. 

 

2.  Click the top and bottom clips down onto the PLC.  

 

Connecting the Adapter’s Base Unit: UniStream Built-in  

  

UAG-CX-XKPxxx, UAG-CX-XKPLxxxx and UAG-CX-XKPxxx, 

UAG-CX-XKPLxxxxx  

1.  Hold the Base Unit as shown in the accompanying 

figure, and plug it into the I/O Expansion Jack in the 

rear of the device. 

 

 

Connecting the Adapter End Unit 

1.  Push the End Unit onto the DIN-rail until the clips located at the top and bottom of the 

unit have snapped onto the DIN-rail. 

2.  Install Uni-I/O™ modules to the right of the End unit. Please refer to the specific 

Installation Guide of each Uni-I/O™ module. 

3.  Slide the Bus Connector Lock of the first module all the way to the left. 

Connecting the Cable 

Short-range kit

: Link the adapter’s units by 

plugging the RJ45 of the End Unit’s cable into the 
port at the bottom of the Base Unit.  

Long-range kit

: Connect both sides of the blue 

cable to the RJ45 ports of the adapter’s Base and 

End units. Please refer to the Long Range 

Adapter Assembly Diagram, page 5 

 

Connecting the Power Supply and Earth 

If you are using a UAG-XKxxx, only earth it. 
All other models: connect it to a power source

 

as

 

described on page 8. 

 

 

 

 

Do not connect the cable to any device other than the Base Unit. 

 

Do not connect the Base Unit’s cable port to any other cable or device. 

Summary of Contents for UniStream UAG-XK Series

Page 1: ...the Base and End units of these adapters have DIN rail clips You can Snap the base onto the DIN rail type structure on the back of UniStream Modular HMI Snap the base directly onto a UniStream PLC UAG CX The base unit of these adapters has a plug the end unit has DIN rail clips You can plug the base unit only into the I O Expansion Jack offered by the UniStream Built in series Note that the maximu...

Page 2: ... should be installed only by qualified personnel Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters that exceed permissible levels Do not connect disconnect the device when power is on Environmental Considerations Ventilation 10mm 0 4 of space is required between the device top bottom edges and the enclo...

Page 3: ...AG CX XKPLxxx Assembly Diagram Short range Adapters UAG XKxxx and UAG XKPxxx UniStream Modular UniStream PLC 1 Bus connector 2 Base Unit plug 3 Clips 4 Base Unit s cable port 5 Cable with RJ45 connector 6 End Unit LED indicators 7 DIN rail clips top and bottom 8 End Unit I O bus connector 9 I O Bus Left side connector 10 Model dependent UAG XKxxx earth point connector UAG XKPxxx power supply conne...

Page 4: ...or 8 I O Bus Left side connector 9 Power supply connector Assembly Diagram Long range Adapters UAG XKPLxxxx UniStream Modular UniStream PLC 1 Bus connector 2 Base Unit plug 3 Clips 4 Base Unit s cable port blue RJ45 5 Cable with RJ45 connectors 6 End Unit LED indicators 7 DIN rail clips top and bottom 8 End Unit I O bus connector 9 I O Bus Left side connector 10 Power supply connector Caution Plea...

Page 5: ...proper precautions to prevent Electro Static Discharge ESD This kit enables you to connect a UniStream controller to a row of Uni I O modules located on a DIN rail To do this you must Connect the Base Unit to the controller Connect the End Unit to the first module in a row of Uni I O modules Link the End Unit into the Base Unit via the connecting cable If you are using a UAG XKPxxx UAG CX XKPxxx U...

Page 6: ...ing figure and plug it into the I O Expansion Jack in the rear of the device Connecting the Adapter End Unit 1 Push the End Unit onto the DIN rail until the clips located at the top and bottom of the unit have snapped onto the DIN rail 2 Install Uni I O modules to the right of the End unit Please refer to the specific Installation Guide of each Uni I O module 3 Slide the Bus Connector Lock of the ...

Page 7: ...distance from high voltage cables and power equipment Wiring Procedure Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm2 3 31 mm2 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire completely into the terminal to ensure a proper connection 4 Tighten enough to keep the wire from pulling free Wir...

Page 8: ...t and slide it to the right Pull the End Unit s top DIN rail clip up and the bottom clip down Pull the End Unit out of its place away from the DIN rail The information in this document reflects products at the date of printing Unitronics reserves the right subject to all applicable laws at any time at its sole discretion and without notice to discontinue or change the features designs materials an...

Reviews: