Unitronics UniStream UAG-XK Series Installation Manual Download Page 8

Local Expansion Adapter Kits Installation Guide  

 

 

Unitronics 

 

 

 

Wiring the Power Supply (UAG-XKPxxx, UAG-CX-XKPxxx, UAG-CX-XKPLxxxx, 
or UAG-XKPLxxxx)

 

These end units require an external 12 or 24VDC power supply. 

 

 

 

The 0V of these end units must be connected to the controller's 0V. Ignoring this 

directive may damage the device. 

 

In the event of voltage fluctuations or non-conformity to voltage power supply 
specifications, connect the device to a regulated power supply. 

Connect the +V and 0V terminals as shown in the 

accompanying figure. 

 

 
 
 

Removing the Expansion Adapter  

1. Turn off the system power. 
2. Remove the Power/Earth terminal block from the bottom of the End unit. 
3.  Disconnect the cable: 

 

Short-Range: Unplug the cable from the RJ45 port on the Base Unit. 

 

Long-Range: Unplug the blue cable from the RJ45 ports of the Base and the End 

units. 

4.  To remove the Base unit: 

 

UAG-XKPxxx, UAG-XKxxx, UAG-XKPLxxxx 

Pull the top clip up and the bottom clip down, and pull the unit slowly away until 

the plug disengages. 

 

UAG-CX-XKPxxx, UAG-CX-XKPLxxxx, UAG-CX-XKPLxxxx 

Pull the unit slowly away until the plug disengages. 

5.  To remove the End unit:  

 

Locate the Bus connector lock of the Uni-I/O™ module connected to the End Unit 

and slide it to the right. 

 

Pull the End Unit’s top DIN-rail clip up and the bottom clip down. 

 

Pull the End Unit out of its place (away from the DIN rail). 

         

         

 

 

 
 
 

The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole 

discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or 

temporarily withdraw any of the forgoing from the market. 
All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of 
merchantability, fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in 

this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising 

out of or in connection with the use or performance of this information. 
The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other 

third parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them

 

 

DOC20001-F7   07/19 

Summary of Contents for UniStream UAG-XK Series

Page 1: ...the Base and End units of these adapters have DIN rail clips You can Snap the base onto the DIN rail type structure on the back of UniStream Modular HMI Snap the base directly onto a UniStream PLC UAG CX The base unit of these adapters has a plug the end unit has DIN rail clips You can plug the base unit only into the I O Expansion Jack offered by the UniStream Built in series Note that the maximu...

Page 2: ... should be installed only by qualified personnel Failure to comply with appropriate safety guidelines can cause severe injury or property damage Do not attempt to use this device with parameters that exceed permissible levels Do not connect disconnect the device when power is on Environmental Considerations Ventilation 10mm 0 4 of space is required between the device top bottom edges and the enclo...

Page 3: ...AG CX XKPLxxx Assembly Diagram Short range Adapters UAG XKxxx and UAG XKPxxx UniStream Modular UniStream PLC 1 Bus connector 2 Base Unit plug 3 Clips 4 Base Unit s cable port 5 Cable with RJ45 connector 6 End Unit LED indicators 7 DIN rail clips top and bottom 8 End Unit I O bus connector 9 I O Bus Left side connector 10 Model dependent UAG XKxxx earth point connector UAG XKPxxx power supply conne...

Page 4: ...or 8 I O Bus Left side connector 9 Power supply connector Assembly Diagram Long range Adapters UAG XKPLxxxx UniStream Modular UniStream PLC 1 Bus connector 2 Base Unit plug 3 Clips 4 Base Unit s cable port blue RJ45 5 Cable with RJ45 connectors 6 End Unit LED indicators 7 DIN rail clips top and bottom 8 End Unit I O bus connector 9 I O Bus Left side connector 10 Power supply connector Caution Plea...

Page 5: ...proper precautions to prevent Electro Static Discharge ESD This kit enables you to connect a UniStream controller to a row of Uni I O modules located on a DIN rail To do this you must Connect the Base Unit to the controller Connect the End Unit to the first module in a row of Uni I O modules Link the End Unit into the Base Unit via the connecting cable If you are using a UAG XKPxxx UAG CX XKPxxx U...

Page 6: ...ing figure and plug it into the I O Expansion Jack in the rear of the device Connecting the Adapter End Unit 1 Push the End Unit onto the DIN rail until the clips located at the top and bottom of the unit have snapped onto the DIN rail 2 Install Uni I O modules to the right of the End unit Please refer to the specific Installation Guide of each Uni I O module 3 Slide the Bus Connector Lock of the ...

Page 7: ...distance from high voltage cables and power equipment Wiring Procedure Use crimp terminals for wiring use 26 12 AWG wire 0 13 mm2 3 31 mm2 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inches 2 Unscrew the terminal to its widest position before inserting a wire 3 Insert the wire completely into the terminal to ensure a proper connection 4 Tighten enough to keep the wire from pulling free Wir...

Page 8: ...t and slide it to the right Pull the End Unit s top DIN rail clip up and the bottom clip down Pull the End Unit out of its place away from the DIN rail The information in this document reflects products at the date of printing Unitronics reserves the right subject to all applicable laws at any time at its sole discretion and without notice to discontinue or change the features designs materials an...