background image

1 1 / 0 0  

IO-AI4-AO2    

I / O   E x p a n s i o n   M o d u l e

 

Unitronics Industrial Automation Systems  

 7 

 

 

Notes: 

 

1.  Note that the range of each I/O is defined both by wiring and within the controller’s software. 
2.  The analog value of an input may also indicate when the input is functioning out of range. If an analog 

input exceeds the permissible range, its value will be 409

6

3.  When an output that is delivering positive output voltage is connected to a load that short-circuits, the 

SHORT CIRCUIT LED lights up on the module.  The short circuit is also identified by the software 
program within the controller connected to the module.   
Within the M90 OPLC, for example, SB 5 turns ON.  SI 5 contains a bitmap indicating the module 
containing the affected output.   
For more information, refer to the on-line help supplied with the programming package of your controller.  

    

    

  

 

Addressing I/Os on M90 Expansion Modules

 

Inputs and outputs located on I/O expansion modules that are connected into an M90 OPLC are assigned 
addresses that comprise a letter and a number.  The letter indicates whether the I/O is an input (I) or an 
output (O).  The number indicates the I/O’s location in the system.  This number relates to both the position 
of the expansion module in the system, and to the position of the I/O on that module. 
Expansion modules are numbered from 0-7 as shown in the figure below. 
 

0

1

2

3

4

5

6

7

Expansion module
identification number

Adapter

 

The formula below is used to assign addresses for I/O modules used in conjunction with the M90 OPLC. 
X is the number representing a specific module’s location (0-7).  Y is the number of the input or output on 
that specific module (0-15).   
The number that represents the I/O’s location is equal to: 

32 + x • 16 + y 

Examples 

 

Input #3, located on expansion module #2 in the system, will be addressed as I 67, 
67 = 32 + 2 • 16 + 3 

 

Output #4, located on expansion module #3 in the system, will be addressed as O 84,  
84 = 32 + 3 • 16 + 4. 

 
EX90-DI8-RO8 is a stand-alone I/O module.  Even if it is the only module in the configuration, the EX90-DI8-
RO8 is always assigned the number 7. 
Its I/Os are addressed accordingly. 
 
Example 

 

Input #5, located on an EX90-DI8-RO8 connected to an M90 OPLC will be addressed  
as I 149, 149 = 32 + 7 • 16 + 5 

 

 

 

Summary of Contents for O-AI4-AO2

Page 1: ...nt as defined by the European directives for machinery low voltage and EMC Only a technician or engineer trained in the local and national electrical standards should perform tasks associated with the electrical wiring of this device Under no circumstances will Unitronics be liable or responsible for any consequential damage that may arise as a result of installation or use of this equipment and i...

Page 2: ...e device and the enclosure walls Do not place in water or let water leak onto the unit Do not allow debris to fall inside the unit during installation DIN rail mounting Snap the device onto the DIN rail as shown below the module will be squarely situated on the DIN rail 60mm 3 5mm 14mm 80mm 93mm 44 5mm OUT OF RANGE SHORT CIRCUIT IO AI4 AO2 AI AO 24 VDC V 0V I V COM AO0 I V COM AO1 I V COM AI3 I V ...

Page 3: ...11 00 IO AI4 AO2 I O Expansion Module Unitronics Industrial Automation Systems 3 4mm 5 8mm 85mm 80mm 68 4mm 93mm 4mm x2 ...

Page 4: ... Note that the COM signals of each I O are internally connected to the module s 0V Do not use tin solder or any other substance on the stripped wire that might cause the wire strand to break We recommend that you use crimp terminals for wiring Install at maximum distance from high voltage cables and power equipment General Wiring Procedures 1 Strip the wire to a length of 7 0 5mm 0 250 0 300 inche...

Page 5: ... Output Wiring Shields should be earthed connected to the earth of the cabinet Do not connect unused outputs An output can be wired to either current or voltage Do not use current and voltage from the same source channel Wiring the Analog Power Supply Wiring DC supply 1 Connect the positive cable to the V terminal and the negative to the 0V terminal A non isolated power supply can be used provided...

Page 6: ...25 Operational error limits 0 4 Status indicators OUT OF RANGE Red LEDs Lit when the corresponding input is receiving current or voltage in excess of the input range See Note 2 Analog Outputs Number of outputs 2 single ended Output range 10V 0 20mA 4 20mA See Note 1 Resolution except at 4 20mA Resolution at 4 20mA 12 bit 4096 units sign 819 to 4095 3277 units Load impedance 1kΩ minimum voltage 500...

Page 7: ...at comprise a letter and a number The letter indicates whether the I O is an input I or an output O The number indicates the I O s location in the system This number relates to both the position of the expansion module in the system and to the position of the I O on that module Expansion modules are numbered from 0 7 as shown in the figure below 0 1 2 3 4 5 6 7 Expansion module identification numb...

Page 8: ...conjunction with the EX A1 adapter 12 bit sign 2 outputs 10V 0 20mA 4 20mA 12 bit 4 inputs 0 10V 0 20mA 4 20mA IO AI4 AO2 Analog I O To order the expansion module that best fits your system contact your local distributor For a list of Unitronics distributors check our website http www unitronic com contact htm 12 bit 4 PT100 50 to 460 C IO PT4 PT 100 8 8 8 8 8 8 8 8 C C C C C C C C o o o o o o o o...

Reviews: