Electrical installation
Q3 240-840A
16
Co
nn
ec
tio
n a
dv
ic
e
4.4
Connection advice
Attention:
The order of the connections to the connector numbers or screw terminals is obligatory. All
further advice is non-obligatory.
The input and output conductors may be altered or supplemented in accordance with the
electrical standards.
Note:
- Connection and operating instructions
- Local regulations
- EU guideline 89/392/EWG
- VDE and TÜV regulations and Trade body guidelines
Switch on the auxiliary voltage and the supply voltage simultaneously.
Switch off the supply voltage after the auxiliary voltage
Input filter
see CE advice, page 14
Short conductor length to be used between the input filter and the device
Auxiliary voltage connection
Connection
terminal X5:17, X5:18
Power supply
400V~ ±15%
Special voltages
24V~, 110V~, 230V~, 500V~
Input current
max. 300mA
Phase position
regardless
Internal fuses
FE1, FE2
0.8AT
Min. line cross-section 0.5mm²
External fuse
Min. line protection 6A
Q3-Hilfsspannung1-V647
Note:
Observe the respective type plate. Control voltage XXX