METHOD A -

 12” (304.8 mm) Clearance to Combustible Wall 

Member:  Using  a  minimum  thickness  3.5”  (89  mm)  brick 

and  a  5/8”  (15.9  mm)  minimum  wall  thickness  clay  liner, 

construct a wall pass-through. The clay liner must conform 

to ASTM C315 (Standard Specification for Clay Fire Linings) 

or its equivalent. Keep a minimum of 12” (304.8 mm) of brick 

masonry between the clay liner and wall combustibles. The 

clay liner shall run from the brick masonry outer surface to 

the inner surface of the chimney flue liner but not past the 

inner surface. Firmly grout or cement the clay liner in place 

to the chimney flue liner.

METHOD B - 

9” (228.6 mm) Clearance to Combustible Wall 

Member:  Using  a  6”  (152.4  mm)  inside  diameter,  listed, 

factory-built  Solid-Pak  chimney  section  with  insulation 

of  1”  (25.4  mm)  or  more,  build  a  wall  pass-through  with  a 

minimum 9” (228.6 mm) air space between the outer wall of 

the chimney length and wall combustibles. Use sheet metal 

supports  fastened  securely  to  wall  surfaces  on  all  sides, 

to  maintain  the  9”  (228.6  mm)  air  space.  When  fastening 

supports to chimney length, do not penetrate the chimney 

liner (the inside wall of the Solid-Pak chimney). The inner end 

of the Solid-Pak chimney section shall be flush with the inside 

of the masonry chimney flue, and sealed with a non-water 

soluble refractory cement. Use this cement to also seal to 

the brick masonry penetration.

METHOD C - 

6” (152.4 mm) Clearance to Combustible Wall 

Member: Starting with a minimum 24 gage (.024” [.61 mm]) 

6” (152.4 mm) metal chimney connector, and a minimum 

24 gage ventilated wall thimble which has two air channels 

of  1”  (25.4  mm)  each,  construct  a  wall  pass-through. 

There  shall  be  a  minimum  6”  (152.4  mm)  separation  area 

containing fiberglass insulation, from the outer surface of the 

wall thimble to wall combustibles. Support the wall thimble, 

and cover its opening with a 24-gage minimum sheet metal 

support.  Maintain  the  6”  (152.4  mm)  space.  There  should 

also be a support sized to fit and hold the metal chimney 

connector. See that the supports are fastened securely to 

wall surfaces on all sides. Make sure fasteners used to secure 

the  metal  chimney  connector  do  not  penetrate  chimney 

flue liner.

METHOD D - 

2” (50.8 mm) Clearance to Combustible Wall 

Member: Start with a solid-pak listed factory built chimney 

section at least 12” (304 mm) long, with insulation of 1” (25.4 

mm) or more, and an inside diameter of 8” (2 inches [51 mm] 

larger than the 6” [152.4 mm] chimney connector). Use this 

as a pass-through for a minimum 24-gauge single wall steel 

chimney connector. Keep solid-pak section concentric with 

and  spaced  1”  (25.4  mm)  off  the  chimney  connector  by 

way of sheet metal support plates at both ends of chimney 

section. Cover opening with and support chimney section 

on both sides with 24 gage minimum sheet metal supports. 

See that the supports are fastened securely to wall surfaces 

on all sides. Make sure fasteners used to secure chimney flue line do not penetrate the inner liner.

NOTES:

1.  Connectors to a masonry chimney, excepting method B, shall extend in one continuous section through the 

wall pass-through system and the chimney wall, to but not past the inner flue liner face.

2.  A chimney connector shall not pass through an attic or roof space, closet or similar concealed space, or a 

floor, or ceiling.

COMBUSTIBLE WALL CHIMNEY CONNECTOR PASS-THROUGHS

Summary of Contents for US2000E-L

Page 1: ...ve These Instructions This manual will help you to obtain efficient dependable service from the heater and enable you to order repair parts correctly Keep in a safe place for future reference This man...

Page 2: ...Type Standard Single Wall or Double Wall Black or Blued Steel 2100 F 650 C Minimum Chimney Height 12 3 7 m Maximum Log Length 21 533 5 mm Dimensions MODEL DEPTH WIDTH HEIGHT Overall Depth x Width x H...

Page 3: ...1 1 2 bolts 3 washers and 3 weld tabs provided in the parts box FIREBRICK CONFIGURATION Replace the Firebrick as shown in the illustration 5 16 18 x 1 1 2 BOLT WASHER HEATER TOP GASKET WELD TAB TOOLS...

Page 4: ...me is spent and in the most spacious room possible Recall that wood stoves produce radiating heat the heat we feel when we are close to a wood stove A wood stove also functions by convection that is t...

Page 5: ...12 305 305 F 22 22 559 559 D B A C E F E D B A C E F E OUTSIDE COMBUSTION AIR Your wood stove is approved to be installed with an outside air intake 4FAK which is necessary for a mobile home This type...

Page 6: ...MUST BE ATTACHED TO THE STRUCTURE OF THE MOBILE HOME SECURING APPLIANCE S ON A PEDESTAL TO THE FLOOR Use the designated holes to secure the unit to the floor SECURING APPLIANCE S WITH LEGS TO THE FLOO...

Page 7: ...o the room through appliance and chimney connector joints An uncontrollable burn or excessive temperature indicates an excessive draft CHIMNEY Your wood stove may be hooked up with a 6 factory built o...

Page 8: ...as recommended by the manufacturer The chimney must be the required height above the roof or other obstructions for safety and proper draft operation MASONRY CHIMNEY Ensure that a masonry chimney meet...

Page 9: ...h has two air channels of 1 25 4 mm each construct a wall pass through There shall be a minimum 6 152 4 mm separation area containing fiberglass insulation from the outer surface of the wall thimble t...

Page 10: ...ns Under extreme conditions it may rot instead of drying This point cannot be over stressed the vast majority of the problems related to the operation of a wood stove is caused by the fact that the wo...

Page 11: ...g tires 4 Materials containing plastic 5 Waste petroleum products paints or paint thinners or asphalt products 6 Materials containing asbestos 7 Construction or demolition debris 8 Railroad ties or pr...

Page 12: ...TED WITH A SPECIAL HIGH TEMP PAINT WHICH REQUIRES A SERIES OF LOW TO MEDIUM BURNS TO FULLY CURE FOR DURABILITY AND A LIFETIME OF SERVICE Proper curing of the high temp paint requires a series of three...

Page 13: ...so open the air controls to maximum a few seconds before opening the stove s door 2 Open the door very slowly open it one or two inches for 5 to 10 seconds before opening it completely to increase the...

Page 14: ...n Make sure the blades do not have build up CAUTION Do not overfire appliance You are overfiring if any part of the appliance glows red Close the door and shut damper immediately to reduce the air sup...

Page 15: ...GLASS CARE Inspect and clean the glass regularly to detect any cracks If you spot one turn the stove off immediately Do not abuse the glass door by striking or slamming shut Do not use the stove if th...

Page 16: ...Qty 1 40292A 6 Flue Collar 1 2 88042 Rope Gasket 1 4 1 3 25845 Air Deflector 1 4 891492 Blower Assembly B36 1 5 26060 Rear Shield 1 6 610926 Rear Ashpan US2000E BP 1 7 29068 Pedestal US2000E BP 1 8 2...

Page 17: ...ir Tube 1 8 2 4 86952 Secondary Air Tube 11 64 1 5 29039 Brick Retainer left 1 6 29040 Brick Retainer right 1 7 40561 Ash Plug 1 8 24103A Half Pumice Firebrick 4 1 2 X 4 1 2 2 9 891414A Half Firebrick...

Page 18: ...07 Date _____________________ Engineer Name ________________________________ License No ____________________________________ Company _____________________________________ Telephone No _______________...

Page 19: ...RECHANGE VEUILLEZ CONSERVER CE GUIDE DANS UN ENDROIT S R DES FINS DE R F RENCE LORSQUE VOUS NOUS CRIVEZ VEUILLEZ INDIQUER LE NUM RO COMPLET DU MOD LE QUI FIGURE SUR LA PLAQUE SIGNAL TIQUE DE L APPARE...

Page 20: ...__________________________ Service de 07 Date _____________________ Nom de l ing nieur ____________________________ N de licence _________________________________ Compagnie ___________________________...

Page 21: ...8 2 4 86952 tube d air secondaire 11 64 1 5 29039 retenue de brique gauche 1 6 29040 retenue de brique droite 1 7 40561 bouchon de cendre 1 8 24103A brique r fractaire demi pierre ponce 4 1 2 x 4 1 2...

Page 22: ...610922 socle soud US2000E BP 1 10 610925 cendrier US2000E BL 1 11 40566 pied en fonte US2000E BL 4 12 25826 plaque de foyer 1 13 29216 cendrier 1 14 610927 soudure de glissi re d amortisseur 1 15 610...

Page 23: ...t et qu ils scellent correctement vitant les expositions ind sirables Il est recommand que vous utilisiez des d tecteurs de fum e et de CO dans les zones o se trouve un potentiel de g n ration de CO E...

Page 24: ...Les feux de chemin e br lent extr mement chaud et peuvent enflammer les mat riaux combustibles environnants En cas d incendie de chemin e appelez imm diatement le service d incendie FORMATION DE CR O...

Page 25: ...teau les braises incandescentes l avant du po le Ajoutez du carburant en faisant attention de ne pas surcharger ou surchauffer l appareil Lors de l ajout de carburant veillez ne pas touffer le feu Ne...

Page 26: ...NTURE SP CIALE CON UE POUR LES HAUTES TEMP RATURES ELLE EXIGE UNE S RIE DE FEUX INTENSIT BASSE ET MOYENNE POUR S CHER ENTI REMENT ET AINSI GARANTIR LA DURABILIT ET LA VIE DE SERVICE Le s chage correct...

Page 27: ...que la temp rature ne d passe jamais 246 C 475 F sur un thermom tre magn tique pour une installation sur des tuyaux de po le paroi simple ou 482 C 900 F sur sonde thermom trique pour l installation s...

Page 28: ...m me pourrir au lieu de s cher On ne saurait trop soulign que la vaste majorit des probl mes li s au fonctionnement d un insert bois est caus e par le fait que le bois utilis tait trop humide ou avai...

Page 29: ...stible Commencez avec une partie de chemin e Solid Pak fabriqu e en usine agr e d au moins 12 po 304 mm de diam tre int rieur avec une isolation de 1 po 25 4 mm ou plus et un raccord de chemin e de 8...

Page 30: ...gagement de 2 po Chapeau homologu Mur combustible Consulter D gagement des combustibles Protecteur de plancher Conduit de raccordement de chemin e Solive de toit combustible Chemin e homologu Mitre So...

Page 31: ...in e et votre chemin e doivent avoir le m me diam tre que la sortie du po le 6 po Si ce n est pas le cas nous vous recommandons de contacter votre vendeur afin de vous assurer qu il n y aura aucun pro...

Page 32: ...ement requis dans les maisons tanches et les maisons ayant des probl mes de pression n gative Vous pouvez acheter cette option aupr s de votre vendeur d appareils de chauffage Assurez vous d indiquer...

Page 33: ...le un passage travers un mur ou une partie de construction combustible est souhait e l installation doit tre conforme CAN CSA B365 Un tuyau de carneau traversant une paroi combustible doit avoir un d...

Page 34: ...nce and inspect for any damage Your appliance is packed with the door handle spring not installed Ensure that the bricks are positioned correctly and not broken see illustration for proper brick arran...

Page 35: ...DURANT LE FONCTIONNEMENT MAINTENEZ LES ENFANTS LES V TEMENTS ET LE MOBILIER LOIGN S TOUT CONTACT PEUT ENTRA NER DES BR LURES N UTILISEZ PAS DE PRODUITS CHIMIQUES NI DE FLUIDES POUR D MARRER LE FEU NE...

Page 36: ...SSEMENT CONCERNANT LA PROPOSITION 65 DE L TAT DE LA CALIFORNIE Ce produit peut vous exposer des agents chimiques y compris au monoxyde de carbone lesquels sont reconnus dans l tat de la Californie com...

Reviews: