PROBE BUDDY – USER MANUAL
Page 14 of 27
UPC_MAN013_R7
Copyright © United Process Controls.
All rights to copy, reproduce and transmit are reserved.
Press t
he ◄ or ► keys
to move the display across the main categories of the setup menu. The
Enter key selects the category and then moves the display vertically down the selected menu.
Menu or parameter lists loop back at the end of any menu or category.
Display
Selects the process for calculation and display: carbon, dew point, and oxygen.
The Sleep Mode Shutdown parameter allows for different shut down times.
Display Menu
Parameter Name
Units or Options
Range
Review
PROCESS
Carbon, Dewpt, O2
Display range:
Carbon: 0-2.55%
Dewpt: -99.9 to
212.0°F (-73 to
100°C)
O2: 0.01%-20.9%
(ppm below 0.01%,
9999ppm to
100ppm)
Selects the process value that is
displayed with the temperature and
mV values.
TEMP SCALE
F OR C
Sets temperature scale for
temperature display and dewpt
calculation.
SLEEP MODE
1, 5, 10, 30,
ALWAYS ON
Select number
values (mins) or
ALWAYS ON to
disable the sleep
mode.
Sets the time the PROBE BUDDY
will stay on after the last key
press. If there is no key press
after the selected period of time,
the PROBE BUDDY goes into
standby mode.
BACKLIGHT TIME ALWAYS ON, 1
sec, 5 sec, 10 sec,
30 sec, 1 min, 5
min
Select number
values or ALWAYS
ON (Default)
Sets the time the backlight will
stay on after the last key press. If
there is no key press after the
selected period of time, the
backlight turns off but the display
is still active. Backlight returns on
next key press.
Inputs
Selects TC type (B, K, R, S), temperature scale (C or F), and averaging for TC and
mV inputs.
Input Menu
Parameter Name
Units or Options
Range
Description
TC TYPE
K, R, S, B
See TC reference
table
See Input calibration for
thermocouple ranges.
APPLY CJ COMP
YES or NO
Applies the cold junction
correction or not when a
thermocouple type is selected.
Default is YES.
TC FILTER
0 – 450
Temperature filter setting in
seconds. Filters the temperature