background image

IMT120 15 

1

GENERAL

MISUSE OF THIS PRODUCT MAY CAUSE EXPLOSION 

AND PERSONAL INJURY. THESE INSTRUCTIONS MUST 

BE THOROUGHLY READ AND UNDERSTOOD BEFORE 

DEVICE IS INSTALLED.

Cert number

20160531-E43374

Applicable Area

North America

Markings

Class I, Groups B, C and D; Class II, 

Groups E, F and G; Class III

Applicable Standards

UL 1203; 

CAN/CSA C22.2 No. 25

CAN/CSA C22.2 No. 30

Cert number

DEMKO 09 ATEX 0815573X 

Applicable Area

Europe (EU)

Markings

II 2 G Ex db IIC T6 Gb; II 2 D Ex tb IIIC 

T85°C Db IP66

Applicable Standards

EN IEC 60079-0; EN 60079-1; EN 60079-31

Cert number

IECEx UL 03.0001X 

Applicable Area

International

Markings

Ex db IIC T6 Gb

Ex tb IIIC T85°C Db IP66

-40°C to +75°C

Applicable Standards

IEC 60079-0; IEC 60079-1; IEC 60079-31

Cert number

DEMKO 11 ATEX 1105261X

Applicable Area

Europe (EU)

Markings

II 1 G Ex ia IIC T6 Ga

Applicable Standards

EN IEC 60079-0; EN 60079-11 

Cert number

IECEx UL 14.0075X

Applicable Area

International

Markings

Ex ia IIC T6 Ga

-50°C ≤ Tamb ≤ +60°C

Applicable Standards

IEC 60079-0; IEC 60079-11

120 SERIES FOR USE IN CLASS I, DIV. 1, GROUPS B, C & D; 

CLASS II, DIV. 1, GROUPS E, F & G; CLASS III HAZARDOUS 

LOCATIONS. ENCLOSURE TYPE 4X, IP66. AMBIENT 

TEMPERATURE RANGE -50°C (-58°F) TO 71°C (160°F).

TO PREVENT IGNITION OF HAZARDOUS 

ATMOSPHERES, DISCONNECT SUPPLY CIRCUITS 

BEFORE OPENING. KEEP COVER TIGHT WHILE 

CIRCUITS ARE ENERGIZED.

ATEX AND IEC SPECIFIC CONDITIONS OF USE: 

DIMENSIONS OF THE FLAMEPROOF JOINTS ARE 

OTHER THAN THE RELEVANT MINIMUM OR MAXIMUM 

SPECIFIED IN TABLES 1 THROUGH 2 OF EN 60079-1/IEC 

60079-1. TEMPERATURE OPERATED SWITCHES ARE TO 

BE MARKED WITH AN “X” AND THE DIMENSIONS OF THE 

FLAMEPROOF JOINTS ARE AS FOLLOWS:

120’s

•  Activation Plunger to adjustment screw hole

gap joints:

 1.140 in/28.96 mm min length by 

0.0039 in/0.099 mm max annular gap

•  Plunger Guide to enclosure through threaded 

joints:

 minimum 8 ½ fully engaged threads

•  Cover to enclosure through threaded joints:

minimum 7 ½ fully engaged threads

121’s & 122’s 

•  Activation Plunger to enclosure through hole 

gap joints: 

1.00 in/25.40 mm min length by 

0.0030 in/0.076 mm max annular gap

•  Adjustment shaft to shaft through hole gap 

joints:

 1.050 in/26.67 mm min. length by 0.0035 

in/0.089 mm max. annular gap

•  Cover to enclosure through threaded joints: 

minimum 7 ½ fully engaged threads

ATEX AND IEC SPECIFIC CONDITIONS OF USE: 

ENCLOSURE CONTAINS ALUMINUM. CARE MUST BE 

TAKEN TO AVOID IGNITION HAZARD DUE TO IMPACT 

OR FRICTION. 

MAX. TEMPERATURE* LIMITS LISTED ON NAMEPLATE 

MUST NEVER BE EXCEEDED, EVEN BY SURGES IN THE 

SYSTEM. OCCASIONAL OPERATION OF UNIT UP TO 

MAX. TEMPERATURE IS ACCEPTABLE, E.G., START-UP 

AND TESTING. EXCESSIVE CYCLING AT MAXIMUM 

TEMPERATURE LIMIT COULD REDUCE SENSOR LIFE. 

CONTINUOUS OPERATION SHOULD NOT EXCEED THE 

DESIGNATED ADJUSTABLE TEMPERATURE RANGE. 

* Maximum Temperature - the highest temperature to which a 

sensing element may be occasionally operated without adversely 

aff ecting set point calibration and repeatability.

THIS PRODUCT DOES NOT HAVE ANY FIELD 

REPLACEABLE PARTS. ANY SUBSTITUTION OF 

COMPONENTS WILL INVALIDATE THIRD-PARTY ISSUED 

APPROVALS AND CERTIFICATIONS, AND MAY IMPAIR 

SUITABILITY FOR CLASS I, DIVISION 1 LOCATION.

120 Series

Explosion-Proof Temperature and Indicating Temperature Switches 

and Controls

Local Mount Types B121, B122, C120

Remote Mount Types E121, E122, F120; 820E, 822E 

Installation and Operation Instructions

Please read all instructional literature carefully and thoroughly before starting. 

Refer to the final page for the Warranty.

Summary of Contents for 120 Series

Page 1: ...ARE AS FOLLOWS 120 s Activation Plunger to adjustment screw hole gap joints 1 140 in 28 96 mm min length by 0 0039 in 0 099 mm max annular gap Plunger Guide to enclosure through threaded joints minim...

Page 2: ...ION STEM HEX SEE DIMENSIONAL DRAWINGS DO NOT TIGHTEN BY TURNING THE ENCLOSURE AS THIS WILL DAMAGE THE SENSOR AND WEAKEN WELDED JOINTS The conduit connection must be properly sealed potted for horizont...

Page 3: ...d turning the calibrating screw with another 3 16 open end wrench see figure 3 Turn clockwise to increase setting or counter clockwise to decrease setting Types B121 and E121 Remove adjustment cover A...

Page 4: ...then re tighten screw A see Figure 5 NOTE Indicating Pointer Deflection 820E 822E The indicating pointers will read slightly low when the bulb temperature is 15 F above the controller setting This de...

Page 5: ...B122 9 84 250 0 Immersion stem 2BS 8BS 9 31 236 6 Bulb capillary 13242 13322 10 0 254 0 Immersion stem Freeze protection 13273 13321 9 31 236 6 Bulb capillary Heat tracing Model Number Range Cap Lengt...

Page 6: ...ELL INSTALLATIONS ii Except model 13273 13321 bulb OD is 1 4 6 35 mm 6 3 8 161 9 mm 3 3 16 81 0 mm 3 3 16 81 0 mm 7 177 8 mm 6 3 8 161 9 mm 14 11 16 373 1 mm 9 228 6 mm 7 8 22 2 mm 1 3 16 30 2 mm 3 4...

Page 7: ...Y INSTALLED Il est imp ratif d utiliser des raccords d tanch it antid flagrants pour les fils lectriques Les types C120 F120 820E et 822E poss dent deux ouvertures de conduits lectriques de 3 4 NPT l...

Page 8: ...disassembled by anyone other than authorized Seller s representatives EXCEPT FOR THE LIMITED WARRANTY OF REPAIR AND REPLACEMENT STATED ABOVE SELLER DISCLAIMS ALL WARRANTIES WHATSOEVER WITH RESPECT TO...

Reviews: