IMT120 15
5
Part III - Dimensions
(Dimensional drawings for all models may be found at www.ueonline.com)
Dimension A
Model
Inches
mm
Sensor
120
9.12
231,4
Immersion
stem
121
8.97
227,4
Immersion
stem
1BS-8BS
8.47
214,8
Bulb &
capillary
A
2.25
(57.2 mm)
4.69
(119.1 mm)
3/4 NPT
E/C
COVER-LOCK
SCREW
4.28
(108.7 mm)
1.29
(32.9 mm)
3.63
(92.2 mm)
5.31
(134.9 mm)
3
(76.2 mm)
3/4 NPT E/C
CLEARANCE FOR 1/4
SCREW
4 MOUNTING HOLES
Internal Set Point Adjustment, Type C120, F120
External Set Point Adjustment, Type B121, B122, E121, E122
A
3
(76.2 mm)
5.19
(131.8 mm)
2.09
(53.1 mm)
3.63
(92.2 mm)
5.13
(130.3 mm)
3
(76.2 mm)
COVER-LOCK
SCREW
3/4 NPT
E/C
Dimension A
Model
Inches
mm
Sensor
120, 121
(B121)
10.0
254,0
Immersion
stem
120
(B122)
10.0
254,0
Immersion
stem
121
(B122)
9.84
250,0
Immersion
stem
2BS-8BS
9.31
236,6
Bulb &
capillary
13242,
13322
10.0
254,0
Immersion
stem (Freeze
protection)
13273,
13321
9.31
236,6
Bulb &
capillary
(Heat tracing)
Model Number Range
Cap Length / Division
[1]
1
-180 to 120°F
2 ft
2
-125 to 350°F
1 1/2 ft
3
-125 to 500°F
1 ft
4
-40 to 120°F
4 ft
5
-40 to 180°F
3 ft
6
0 to 250°F
2 1/2 ft
7
0 to 400°F
2 ft
8
50 to 650°F
2 ft
[1]
Added to or taken away from the process
Recommended Practices
• A redundant device is necessary for applications
where damage to the primary device could
endanger life, limb or property. A high or low
limit switch is necessary for applications where
a dangerous runaway condition could result.
• Monitor operation to observe warning signs of
possible damage to device, such as drift in set
point. Check device immediately.
• Preventative maintenance and periodic testing
is necessary for critical applications where damage
could endanger property or personnel.