![United CoolAir 4CA1901 Installation Manual Download Page 5](http://html.mh-extra.com/html/united-coolair/4ca1901/4ca1901_installation-manual_844867005.webp)
5
FORM CIM 0203
DIMENSIONS
0017CA
FIGURE 3:
Water-Cooled Water Connections
FIGURE 4:
Approximate Net Weights
CONDENSING
TOTAL UNITS
SECTION ONLY
AIR
WATER
AIR
WATER
COOLED
COOLED
COOLED
COOLED
1 TON
415 lbs.
395 lbs.
250 lbs.
230 lbs.
1-1/2 TON
430 lbs.
410 lbs.
290 lbs.
270 lbs.
2 TON
665 lbs.
605 lbs.
395 lbs.
335 lbs.
3 TON
685 lbs.
625 lbs.
390 lbs.
330 lbs.
4 TON
700 lbs.
640 lbs.
415 lbs.
355 lbs.
SINGLE COMP.
4 TON
950 lbs.
905 lbs.
570 lbs.
525 lbs.
DUAL COMP.
5 TON
720 lbs.
660 lbs.
425 lbs.
365 lbs.
SINGLE COMP
5 TON
970 lbs.
925 lbs.
585 lbs.
540 lbs.
DUAL COMP.
6 TON
970 lbs.
925 lbs.
585 lbs.
540 lbs.
DUAL COMP.
8 TON
995 lbs.
945 lbs.
600 lbs.
550 lbs.
DUAL COMP
10 TON.
1340 lbs.
1205 lbs.
800 lbs.
665 lbs.
DUAL COMP.
12 TON
1520 lbs.
1375 lbs.
915 lbs.
770 lbs.
TRIPLE COMP.
15 TON
1580 lbs.
1450 lbs.
950 lbs.
820 lbs.
TRIPLE COMP.
NOTE:
CONDENSATE DRAIN MUST BE PIPED IN
BOTH EVAPORATOR AND CONDENSING
SECTIONS.
NOMINAL
A
B
C
D-WATER CONNECTIONS
TONS
1 and 1-1/2
Ton Single
6-3/8" 10"
4"
7/8" O.D. on left side
Circuit
2 thru 4
Ton Single
8-3/8" 12" 5-7/8"
7/8" O.D. on left side
Circuit
5 Ton
Single
8-3/8" 12" 5-7/8"
1-1/8" O.D. on left side
Circuit
4 thru 8
Ton Dual
—
—
—
1-1/8" O.D. on right side
Circuit
10 thru 15
Ton Multi
—
—
—
1-3/8" O.D. on right side
Circuit