3. Mount charger on the wall
mounting bracket and lock it with the
pin
4. Follow applicable accessibility
requirements for the mounting
position. The unit shall be mounted at
a sufficient height from ground such
that the height of the storage means
for the coupling device is located
between 24 inches (0.6 m) and 48
inches (1.2 m) from the ground.
5. For Plug-in (NEMA 6-50 or 14-50)
models, Plug in the power cord to
the NEMA 6-50 or 14-50 Wall Outlet/
Receptacle. The NEMA outlet should
be located no less than 20~26”
from the ground or as defined by
applicable, local electrical safety codes
and standards.
Figure 2-10. Plug in the power cord
Figure 2-9. Security pin
17
Figure 2-11. Conduit.
Figure 2-12. Copper terminal, heat shrink tube and copper wire
2.4 Input Wiring Connection
(Optional Hardwire Connection Only)
1. Choose the appropriate conduit in accordance with all applicable, local and electrical
safety codes and standards.
2. Using the appropriate tool, clamp the wire terminal to the copper wire. For non-insulated
terminals, use heat shrink tube to cover the non-insulated portion of the terminal