background image

9

In southern climates, often the heating and air

conditioning equipment is turned off if the

residence is to be unoccupied for an extended

period of time. It is recommended that the

dehumidifier be left ON even when the air

conditioning is off. The internal fan in the

dehumidifier will move air throughout the

conditioned space to keep the humidity under

control. Since the dehumidifier adds a small

amount of heat to the space, it is recommended

that the air conditioning and the dehumidifier be

left on during unoccupied periods; however, the

set point of the air conditioning unit should be set

HIGHER than normal. The higher temperature will

lower the relative humidity. This, coupled with the

dehumidifier operation, will ensure a dry

conditioned space.

PROCESS

When the dehumidifier fan (blower) is operating,

moist air from the conditioned space is drawn into

the unit through the inlet duct. The air first passes

through the filter in the unit. Once beyond the

filter, the air passes through the cool evaporator

(cooling) coil. This coil is part of the refrigeration

process and is, therefore, cold. In all probability

the coil is colder than the dew point of the air.

Since it is below the dew point, moisture in the air

will condense on the coil fins. Once condensed

out of the circulating air, the moisture now in the

form of droplets falls to the bottom of the coil and

is collected in the drain pan. This is essentially the

same process that causes water to drip from

beneath an automobile when the air conditioning

is operating.
Once the moisture has been removed from the

air, it is somewhat cooler. However, since the air

is cooler it cannot hold as much moisture and its

relative humidity is high, even though moisture

has been removed. To solve this “problem” the air

next passes through a warm condenser (heating)

coil where it is warmed. Since the air is warmed

without adding any moisture, its relative humidity

decreases sharply. This dry air is drawn through

the fan and then expelled through the discharge

duct back to the conditioned space.
Dehumidifiers take latent heat (heat removed

from water vapor when it condenses) and convert

it to sensible heat (heat you can feel in the form of

temperature increase). This exchange causes the

discharge air temperature to be warmer than the

entering air temperature. The amount of this

temperature increase varies and is dependent

upon the load (how much dehumidification is

being done).
To ensure that the dehumidification process is

maximized, a thermostatic expansion valve is

used as part of the refrigeration system. This

device provides exacting control of the system

over a very wide range of operating temperatures.

This is superior to lower cost refrigerant control

devices such as capillary tubes which limit

efficient operation to a very narrow band of

operating temperatures.

SEQUENCE
Unit Controls

If no wall mounted dehumidistat is used, the unit

will be controlled by the integral control system.

This system operates the internal fan for 15

minutes approximately every hour to “sample” the

air in the system. The air sample passes over the

unit mounted humidity sensor. The unit mounted

control should be set at approximately mid level. If

the humidity level in the sampled air is greater

than the set point, the compressor will be turned

on, after a 3 minute delay. The fan and the

compressor will operate until the humidity level of

the air entering the dehumidifier satisfies the

humidity sensor/setpoint.

Wall Control

When this control method is selected, the unit

mounted control must be adjusted to its minimum

(lowest relative humidity) level and never

readjusted. The room dehumidistat should be set

in the comfort area at approximately 50% RH

(relative humidity). When the dehumidistat senses

that the RH in the space is above its set point, an

electrical contact within the dehumidistat closes

causing the dehumidifier to start. The unit runs to

dehumidify the air from the conditioned space

until the

dehumidistat is

satisfied, that is,

the RH has been

lowered to the set

point.

Wall Mounted

Dehumidistat

Summary of Contents for WHOLE HOUSE DEHUMIDIFIER

Page 1: ...WHOLE HOUSE DEHUMIDIFIER Installation Operating and Maintenance Manual UNITARY PRODUCTS GROUP ...

Page 2: ...10 7 Maintenance 11 a Filter 11 8 Wiring Diagram 11 9 Troubleshooting 12 10 Physical Dimensions 12 Installation Operation and Maintenance Instructions SAFETY INSTRUCTIONS WARNING This dehumidifier must be installed by a qualified heating ventilation and air conditioning professional in compliance with all codes local and national Failure to comply with this WARNING could result in severe personal ...

Page 3: ... be considered when determining the location If the unit is mounted above a ceiling or in an attic a secondary drain pan under the entire unit is recommended This pan should have a visible overflow drain that will alert the end user that a problem exists with dehumidifier s primary drainage system SPECIFICATIONS Place the unit in a location that will allow a minimum of 22 clearance for filter remo...

Page 4: ...ING The cabinet must be permanently grounded Connect the ground wire to the Ground terminal provided in the unit Failure to ground the cabinet can result in fire electrical shock personal injury or death The electrical supply requirements are listed on the unit rating plate and in the specification table above CONDENSATE DRAIN The condensate drain must be trapped external to the unit The trap dime...

Page 5: ... C22 1 and local building electric codes using copper conductors only ALTERNATE REMOTE DEHUMIDISTAT The dehumidifier is supplied with its own self contained dehumidistat control which includes an air sampling sequence however the unit can also be controlled by a remote dehumidistat located in a conditioned space DO NOT LOCATE THE DEHUMIDISTAT IN THE DUCTWORK It is recommended that the remote dehum...

Page 6: ...t any of the existing wires from the C W or Y terminals on the air handler furnace Disconnect the existing thermostat wire from the G terminal on the air handler furnace Using a wire nut splice this wire to a new wire and then connect to the G1 terminal on the dehumidifier Connect the G2 terminal on the dehumidifier to the G terminal on the air handler furnace All controls wiring including connect...

Page 7: ...talled on floor Piped return return Dependent operation furnace blower and dehumidifier must operate at the same time Dehumidifier Connected for Dependent Operation with Vertical Air Handler Furnace Connection Diagram Dependent Operation and per the following Connect the D terminals on the dehumidifier unit to the R terminal on the air handler furnace Do not disconnect any of the existing wires fr...

Page 8: ...Dependent Operation REMOVE JUMPER ON S1 S2 WHEN OPTIONAL DEHUMIDISTAT IS USED WALL MOUNTED DEHUMIDISTAT OPTIONAL in the space at comfortable levels however there are times during cool or rainy weather when the air conditioning does not operate often enough to keep the humidity at a comfortable level Oftentimes homeowners lower the thermostat to try to compensate for this and cause the air conditio...

Page 9: ...y This dry air is drawn through the fan and then expelled through the discharge duct back to the conditioned space Dehumidifiers take latent heat heat removed from water vapor when it condenses and convert it to sensible heat heat you can feel in the form of temperature increase This exchange causes the discharge air temperature to be warmer than the entering air temperature The amount of this tem...

Page 10: ...has become excessively dirty when cleaned at this interval it may be necessary to adjust the cleaning schedule to more frequent cleaning Excess dirt on the filter will reduce the air that can flow through it and reduce the overall effectiveness of the dehumidifier The unit Wiring Diagram is shown on page 11 and the Troubleshooting Guide is on page 12 Insure that power to the dehumidifier unit is t...

Page 11: ...11 UNIT WIRING DIAGRAM ...

Page 12: ...and dehumidifier is correct Unit door switch is not mechanically actuated due to loose door Dehumidifier operates Filter may be dirty Clean filter continuously but does not Dehumidistat set at unrealistically low setting Reset to dehumidify approximately 50 RH Unit is noisy Ensure unit is sitting level and on all four feet Verify all panel screws are tight Water drips from unit Ensure unit is leve...

Page 13: ...Whole House Dehumidifier Exploded View 13 ...

Page 14: ... D R E T L I F 4 1 D F 7 2 4 7 8 1 1 R O S S E R P M O C 4 1 S C 8 2 4 7 9 1 1 N A P M O T T O B 4 1 T B 9 2 4 7 0 2 21 7430 SD14 PANEL 1 N O I T A L U S N I w E D I S 22 7431 SP14 PANEL FIL 2 N O I T A L U S N I w R E T 1 N I A M B C P 4 1 P P 2 3 4 7 3 2 24 7433 HC14 SENSOR MODULE HUMIDITY W HARNESS 1 1 L O R T N O C B O N K 4 1 C N 4 3 4 7 5 2 4 R E B B U R R O T A L O S I 4 1 I R 5 3 4 7 6 2 4...

Page 15: ...LIMITED WARRANTY THE MANUFACTURER WILL IN NO EVENT BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES This limited warranty gives you specific legal rights and you may also have other rights which vary from state to state Some states do not allow either limitations on implied warranties or exclusions from incidental or consequential damages so the above exclusion and limitation may not apply to you...

Page 16: ...Design material performance data and components subject to change without notice 12 14 06 Rev A FORM 16007 UNITARY PRODUCTS GROUP 5005 YORK DRIVE NORMAN OK 73069 ...

Reviews: