Unit Dimensions
All specifications and performance data subject to change without notice.
TROUBLESHOOTING
PROBLEM
POSSIBLE SOLUTION
Dehumidifier will not run
•
Verify there is power to the unit
•
Check that any disconnect switch is ON
•
Check that the circuit breaker is not tripped (a separate 15 amp
circuit breaker is recommended)
•
Verify the dehumidistat is not in the OFF position
•
Verify low voltage wiring between AC and dehumidifier is correct
•
Unit door switch is not mechanically actuated due to loose door.
Dehumidifier operates
•
Filter may be dirty. Clean filter
continuously but does not
•
Dehumidistat set at unrealistically low setting. Reset to
dehumidify
approximately 50% RH
Unit is noisy
•
Ensure unit is sitting level and on all four feet
•
Verify all panel screws are tight
Water drips from unit
•
Ensure unit is level
•
Verify condensate drain is properly trapped
•
Check for plugged condensate trap or condensate line
Heat/AC unit is OFF, but
•
This is normal operation as long as there is power to the
dehumidifier runs
dehumidifier.
12