Unitary products group WHOLE HOUSE DEHUMIDIFIER Installation, Operating And Maintenance Manual Download Page 7

DUCT CONNECTION (Dependent Operation)

In this arrangement, the dehumidifier is connected
either upstream or downstream of the air
conditioner air handler. Both the discharge and
the return of the dehumidifier are connected to
the same side of the air handler. When the
dehumidifier is connected for dependent
operation, the central air conditioner fan and the
dehumidifier fan MUST operate simultaneously.

CONTROLS CONNECTION
(Dependent Operation)—Illustration on page 8

The dehumidifier controls must interface with the
main air conditioning unit. This interface is
required to do the following:

Ensure that the air handler/furnace fan is on
when the dehumidifier is operating

Two wires run from the air conditioner to the
dehumidifier to accomplish this interface, per Unit

DAMPER CONNECTION

If an optional damper(s) is used in the discharge/
return duct, this may be controlled by the
dehumidifier. See Unit Connection Diagram
(Independent Operation) for connection details.
When connected as shown in the Unit Connection
Diagram, the dehumidifier provides only the
switching interface for the damper(s). Power for

these devices must be provided with a separate
transformer, not from the transformer located in
the dehumidifier.

The damper control wiring must meet national
and local electrical codes. Entry into the
dehumidifier unit is through the control wire entry
located on the air-entering end of the unit. Note
that this is separate from the power entry.

DEPENDENT OPERATION

• Dehumidifier installed on floor
• Piped return/return
• Dependent operation (furnace blower and

dehumidifier must operate at the same time)

Dehumidifier Connected for Dependent Operation

with Vertical Air Handler/Furnace

Connection Diagram (Dependent Operation) and
per the following:

Connect the D terminals on the dehumidifier
unit to the R terminal on the air handler/
furnace. Do not disconnect any of the existing
wires from the air conditioning unit.

Connect the DH terminal on the dehumidifier
to the G terminal on the air handler/furnace.
Do not disconnect any of the existing wires
from the air conditioning unit.

All controls wiring, including connection to a
remote dehumidistat, must be 18-22 gauge and
must meet national and local electrical codes.
Entry into the dehumidifier unit is through a 7/8"
diameter hole located on the air entry end of the
unit, adjacent to the unit mounted dehumidistat.
Note that this is separate from the power entry.

DAMPER CONNECTION (Dependent
Operation)

Although not necessary, if an optional damper(s)
is utilized in the discharge/return duct, this may be
controlled by the dehumidifier. See Unit
Connection Diagram (Dependent Operation) for
connection details. When connected as shown in
the Unit Connection Diagram, the dehumidifier
provides the switching interface for the damper(s)
as well as the line voltage power to the
transformer (by others). Power for the damper(s)
is provided by the dehumidifier.

The damper control wiring must meet national
and local electrical codes. Entry into the
dehumidifier unit is through the control wire entry
located on the air-entering end of the unit. Note
that this is separate from the power entry.

See Illustration on page 8

7

DEHUMIDIFIER

Summary of Contents for WHOLE HOUSE DEHUMIDIFIER

Page 1: ...WHOLE HOUSE DEHUMIDIFIER Installation Operating and Maintenance Manual UNITARY PRODUCTS GROUP ...

Page 2: ...10 7 Maintenance 11 a Filter 11 8 Wiring Diagram 11 9 Troubleshooting 12 10 Physical Dimensions 12 Installation Operation and Maintenance Instructions SAFETY INSTRUCTIONS WARNING This dehumidifier must be installed by a qualified heating ventilation and air conditioning professional in compliance with all codes local and national Failure to comply with this WARNING could result in severe personal ...

Page 3: ... be considered when determining the location If the unit is mounted above a ceiling or in an attic a secondary drain pan under the entire unit is recommended This pan should have a visible overflow drain that will alert the end user that a problem exists with dehumidifier s primary drainage system SPECIFICATIONS Place the unit in a location that will allow a minimum of 22 clearance for filter remo...

Page 4: ...ING The cabinet must be permanently grounded Connect the ground wire to the Ground terminal provided in the unit Failure to ground the cabinet can result in fire electrical shock personal injury or death The electrical supply requirements are listed on the unit rating plate and in the specification table above CONDENSATE DRAIN The condensate drain must be trapped external to the unit The trap dime...

Page 5: ... C22 1 and local building electric codes using copper conductors only ALTERNATE REMOTE DEHUMIDISTAT The dehumidifier is supplied with its own self contained dehumidistat control which includes an air sampling sequence however the unit can also be controlled by a remote dehumidistat located in a conditioned space DO NOT LOCATE THE DEHUMIDISTAT IN THE DUCTWORK It is recommended that the remote dehum...

Page 6: ...t any of the existing wires from the C W or Y terminals on the air handler furnace Disconnect the existing thermostat wire from the G terminal on the air handler furnace Using a wire nut splice this wire to a new wire and then connect to the G1 terminal on the dehumidifier Connect the G2 terminal on the dehumidifier to the G terminal on the air handler furnace All controls wiring including connect...

Page 7: ...talled on floor Piped return return Dependent operation furnace blower and dehumidifier must operate at the same time Dehumidifier Connected for Dependent Operation with Vertical Air Handler Furnace Connection Diagram Dependent Operation and per the following Connect the D terminals on the dehumidifier unit to the R terminal on the air handler furnace Do not disconnect any of the existing wires fr...

Page 8: ...Dependent Operation REMOVE JUMPER ON S1 S2 WHEN OPTIONAL DEHUMIDISTAT IS USED WALL MOUNTED DEHUMIDISTAT OPTIONAL in the space at comfortable levels however there are times during cool or rainy weather when the air conditioning does not operate often enough to keep the humidity at a comfortable level Oftentimes homeowners lower the thermostat to try to compensate for this and cause the air conditio...

Page 9: ...y This dry air is drawn through the fan and then expelled through the discharge duct back to the conditioned space Dehumidifiers take latent heat heat removed from water vapor when it condenses and convert it to sensible heat heat you can feel in the form of temperature increase This exchange causes the discharge air temperature to be warmer than the entering air temperature The amount of this tem...

Page 10: ...has become excessively dirty when cleaned at this interval it may be necessary to adjust the cleaning schedule to more frequent cleaning Excess dirt on the filter will reduce the air that can flow through it and reduce the overall effectiveness of the dehumidifier The unit Wiring Diagram is shown on page 11 and the Troubleshooting Guide is on page 12 Insure that power to the dehumidifier unit is t...

Page 11: ...11 UNIT WIRING DIAGRAM ...

Page 12: ...and dehumidifier is correct Unit door switch is not mechanically actuated due to loose door Dehumidifier operates Filter may be dirty Clean filter continuously but does not Dehumidistat set at unrealistically low setting Reset to dehumidify approximately 50 RH Unit is noisy Ensure unit is sitting level and on all four feet Verify all panel screws are tight Water drips from unit Ensure unit is leve...

Page 13: ...Whole House Dehumidifier Exploded View 13 ...

Page 14: ... D R E T L I F 4 1 D F 7 2 4 7 8 1 1 R O S S E R P M O C 4 1 S C 8 2 4 7 9 1 1 N A P M O T T O B 4 1 T B 9 2 4 7 0 2 21 7430 SD14 PANEL 1 N O I T A L U S N I w E D I S 22 7431 SP14 PANEL FIL 2 N O I T A L U S N I w R E T 1 N I A M B C P 4 1 P P 2 3 4 7 3 2 24 7433 HC14 SENSOR MODULE HUMIDITY W HARNESS 1 1 L O R T N O C B O N K 4 1 C N 4 3 4 7 5 2 4 R E B B U R R O T A L O S I 4 1 I R 5 3 4 7 6 2 4...

Page 15: ...LIMITED WARRANTY THE MANUFACTURER WILL IN NO EVENT BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES This limited warranty gives you specific legal rights and you may also have other rights which vary from state to state Some states do not allow either limitations on implied warranties or exclusions from incidental or consequential damages so the above exclusion and limitation may not apply to you...

Page 16: ...Design material performance data and components subject to change without notice 12 14 06 Rev A FORM 16007 UNITARY PRODUCTS GROUP 5005 YORK DRIVE NORMAN OK 73069 ...

Reviews: