background image

035-14511-000 REV B (1299)

Unitary Products Group

13

® 

sor in the second stage mode. Additionally, the control
outputs a 24v signal (at Y2 OUT) to control the indoor blower
at the correct CFM.

If there is a call for second stage cooling (Y2) prior to the unit
operating the first stage (i.e. if call occurs during the five
minute anti-short cycle period), then the control will switch the
control circuit and will energize the contactor starting the out-
door fan and the compressor in the second stage mode.
Additionally, the control outputs a 24v signal (at Y2 OUT) to
control the indoor blower at the correct CFM.

When the second stage of the room thermostat is satisfied
only, the unit will continue to operate in the second stage
mode.

When the first stage of the room thermostat is satisfied, the
control will de-energize the contactor stopping the outdoor
fan and the compressor.

If the room thermostat calls for second stage cooling (Y2) on
two consecutive cooling cycles, the next call for cooling for
either first (Y1) or second (Y2) stage will energize the unit in
the second stage mode. The above mode will be reset to per-
mit start up on first stage with only a Y1 call when the second
stage operational cycle runs less than 15 minutes. This mode
can also be reset when servicing the equipment by removing
24 V to the control.

NOTE: The control with not operate on Y2 without a Y1 signal.

SYSTEM CONTROL BOARD FUNCTIONS

Refer to Figure 11 for view of Control Board.

Five Minute Anti-Short Cycle Timer

The control has a five minute time delay to prevent the sys-
tem from short cycling after a thermostat off cycle or power
interrupt. This five-minute delay is initiated following the com-
pletion of a first stage cooling call (Y1) or the 24v power up of
the control. During this mode the control will not respond to
any thermostat inputs and the LED will flash a code 1 at the
control board.

For servicing or during installation of the condensing unit, the
time delay may be by-passed by momentarily jumping the
two test pins when there is a call for cooling (Y1 or Y2).

Pressure Switch Operation

The condensing unit is provided with high and low pressure
switches installed and wired into the control to provide addi-
tional protection for the system if any abnormal operating
conditions occur. The high pressure switch is threaded on a
Schrader fitting located in the liquid line of the outdoor unit
and a low pressure switch is brazed in the suction line of the
outdoor unit. These two controls are wired in series to the unit
control.

If the pressure switches detect a fault condition, they will
open (high pressure opens with pressures greater than 400
psi and low pressure opens with pressures less than 25 psi)
and the control will immediately shut down the unit. The con-
trol will go into a five-minute anti-short cycle mode inhibiting
any thermostat inputs. Following the anti-short cycle mode,
the control will permit the unit to start normally with the next
call for cooling as long as the pressure switches have reset
(high pressure resets at 300 ± 15 psi, low pressure resets at
65 ± 7 psi).

If the control detects a second pressure switch fault within
one hour of compressor run time, the unit will again shut
down and the unit control will lock out the unit until the fault
condition is reset. During this period, a code “2” will be
flashed at the control and provide a 24v signal on the X/L line
to flash at the room thermostat.

Indoor Blower Operation

The indoor blower operation is controlled directly by the Y1 or
G thermostat signal for the first stage of cooling and by
Y2OUT from the control for the second stage of cooling. The
reason the unit control controls the second stage blower is
that the control will override the thermostat and continue sec-
ond stage once the second stage of the thermostat is satis-
fied and there is still a first stage demand. Additionally, during
the five second switching from first to second stage, the
blower ramp up is delayed.

.

FIGURE 11 : COMFORT ENHANCER

CONTROL

BOARD

T E S T

R

L

Y 2

Y 1

M

C

Y 2   O U T

P S

S T A T U S

E X T E R N A L   R L Y

T S   C O N T R O L

TEST
PINS

LED

Summary of Contents for H4TS024

Page 1: ...WIRING 8 THERMOSTAT MOUNTING WIRING 8 DE HUMIDIFICATION CONTROL 8 CONTROL WIRING 8 WIRING DIAGRAMS 9 10 INDOOR BLOWER SPEED SETTINGS 8 SYSTEM START UP 11 ENERGIZE CRANKCASE HEATER 11 CHECKING SYSTEM...

Page 2: ...erly INSPECTION As soon as a unit is received it should be inspected for possi ble damage during transit If damage is evident the extent of the damage should be noted on the carrier s freight bill A s...

Page 3: ...jectionable if the unit is placed directly under windows of certain rooms bed rooms study etc ROOF INSTALLATION When installing units on a roof the structure must be capable of supporting the total we...

Page 4: ...7 Install TXV equalizer line in 1 8 hole previously made in vapor line Equalizer line can be bottomed out in vapor line as end of equalizer line is cut on 45 degrees angle to prevent blockage Braze e...

Page 5: ...ter 3 Care must also be taken to isolate the refrigerant lines to minimize noise transmission from the equipment to the structure 4 The vapor line must be insulated with a minimum of 1 2 foam rubber i...

Page 6: ...d line to the evaporator liquid connection The nitrogen shouldnowbeflowing throughtheevaporator coil 5 Slide the grommet away from the vapor connection at the coil Braze the vapor line to the evaporat...

Page 7: ...supply to be sure that it meets the values specified on the unit nameplate and wiring label Power wiring control low voltage wiring disconnect switches and over current protection to be supplied by t...

Page 8: ...RING The recommended field connections for specific indoor air handlers and furnaces are shown in Figures 7 through 10 All connects to the outdoor unit are made in the low voltage junc tion box in the...

Page 9: ...H I S W I R E I F N O T U S E D 2 T H E R M O S T A T T S C O N T R O L G R D L U G 2 H U M I D I S T A T M A K E S C I R C U I T O N H U M I D I T Y F A L L J U M P E R O N C F M S E L E C T I O N B...

Page 10: ...I R I N G 2 0 8 2 3 0 1 6 0 C O N T A C T O R M 1 T 1 L 1 L 2 T 2 P O W E R C O N T R O L F A C T O R Y C L A S S 2 W I R I N G C L A S S 1 W I R I N G H I G H L O W 2 D E H U M I D I S T A T M A K E...

Page 11: ...age 2 cylinder operation the recommended sub cooling for H TS036 is 14 F and 20 F for all other models For 1st stage 1 cylinder operation the recommended sub cooling is 10F for all models 1 Set the sy...

Page 12: ...ar single speed compressor system This additional run time provides for better dehumidification and consistent room temperatures However there may be installation environ ments that the humidity level...

Page 13: ...y may be by passed by momentarily jumping the two test pins when there is a call for cooling Y1 or Y2 Pressure Switch Operation The condensing unit is provided with high and low pressure switches inst...

Page 14: ...to be driven out of the compressor The installer should also instruct the owner on proper opera tion and maintenance of all other system components INDICATIONS OF PROPER OPERATION Cooling operation i...

Page 15: ...035 14511 000REVB 1299 Unitary Products Group 15 NOTES...

Page 16: ...o n d i t i o n i n g Unitary Products Group 5005 York Drive Norman Oklahoma 73069 Subject to change without notice Printed in U S A Copyright by Unitary Products Group 1999 All rights reserved Super...

Reviews: